Sanyo SAP–C92A Technical & Service Manual

Type
Technical & Service Manual
TECHNICAL & SERVICE MANUAL
SAPK92A + SAPC92A
SAPK122A + SAPC122A
SAPK182A + SAPC182A
SAPK252A + SAPC252A
FILE NO.
REFERENCE NO. SM700569
Indoor Unit
Outdoor Unit
SPLIT SYSTEM AIR CONDITIONER
SAPK92A
SAPK122A
SAPC92A
SAPC122A
Indoor Model No. Product Code No. Destination
SAP–K92A–S 1 852 083 68
SAPK122A–S 1 852 083 69
Outdoor Model No. Product Code No. Destination
SAP–C92A–S 1 852 084 09
SAP–C122A–S 1 852 084 10
SAP–C182A–S 1 852 084 11
SAPK182A–S 1 852 083 70
SAPC182A
SAPC252A
SAPK182A
SAPK252A
SAPC252A–S 1 852 084 13SAPK252A–S 1 852 083 72
Australia Australia
i
Important!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person,
it is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before
beginning.
Follow each installation or repair step exactly as
shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or
death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help
for a special problem, contact our sales/service outlet
or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR
DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIAN SHOULD
ATTEMPT TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and
tubing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections
and inadequate grounding can cause accidental
injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your
knees when lifting to reduce strain on your back. Sharp
edges or thin aluminum fins on the air conditioner can
cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
units weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to
prevent “sweating” that can cause dripping and water
damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to
provide a solid, level foundation for the outdoor unit.
This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces
of the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leak-
free connection.
Check carefully for leaks before starting the test run.
When Servicing
Turn the power off at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
Keep your fingers and clothing away from any
moving parts.
Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
Others
Ventilate any enclosed areas when installing or
testing the refrigeration system. Escaped refrigerant
gas, on contact with fire or heat, can produce
dangerously toxic gas.
Confirm upon completing installation that no
refrigerant gas is leaking. If escaped gas comes in
contact with a stove, gas water heater, electric room
heater or other heat source, it can produce
dangerously toxic gas.
CAUTION
Table of Contents
Page
1. OPERATING RANGE .............................................................................................................................. 1
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 2
2-2. Major Component Specifications.................................................................................................... 6
2-3. Other Component Specifications.................................................................................................... 14
3. DIMENSIONAL DATA.............................................................................................................................. 16
4. REFRIGERANT FLOW DIAGRAM ......................................................................................................... 20
5. PERFORMANCE DATA
5-1. Performance charts ....................................................................................................................... 22
5-2. Air Throw Distance Chart .............................................................................................................. 24
5-3. Cooling Capacity ........................................................................................................................... 26
6. ELECTRICAL DATA
6-1. Electrical Characteristics................................................................................................................ 30
6-2. Electric Wiring Diagrams................................................................................................................ 32
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection ............................................................................................................... 36
7-2. Remote Control Unit Installation Position....................................................................................... 38
7-3. Recommended Wire Length and Diameter ................................................................................... 39
8. FUNCTION
8-1. Room Temperature Control ........................................................................................................... 40
8-2. Dry Operation ................................................................................................................................ 41
8-3. Freeze Prevention ......................................................................................................................... 41
8-4. Outdoor Fan Speed Control .......................................................................................................... 42
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting ........................................................................................ 43
9-2. Air conditioner does not operate .................................................................................................... 44
9-3. Some part of air conditioner does not operate ..............................................................................48
9-4. Air conditioner operates, but abnormalities are observed ............................................................. 50
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance .......................................................................................... 51
10-2. Checking Continuity of Fuse on PCB Ass'y.................................................................................... 52
10-3. Checking Motor Capacitor ............................................................................................................. 52
11. MAINTENANCE
11-1. Changing Address of Remote Control Unit in Indoor Unit ............................................................. 53
.................................................................................................................................................. 54
APPENDIX
ii
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
2
2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz
Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 2.55 / 2.55 / 2.50
BTU/h 8,700 / 8,700 / 8,500
Air circulation (High) m3/h 430
Moisture removal (High) Liters/h 0.80
Available voltage range V 198 to 264
Running amperes A 3.9 / 3.8 / 3.9
Power input W 840 / 860 / 930
Power factor % 98 / 98 / 99
C.O.P. W/W 3.04 / 2.97 / 2.69
Compressor locked rotor amperes A 19 / 20 / 21
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer 1-hour OFF / 12-hour ON or OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R22 / 850
Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 39 / 37 / 33
Outdoor – Hi dB-A 44
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 9.52 (3/8)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 250 530
Width mm 790 680
Depth mm 174 225
Package dimensions Height mm 242 580
Width mm 850 812
Depth mm 312 315
Weight Net
kg 7.0 29.0
Shipping
kg 10.0 31.0
Shipping volume m3 0.06 0.15
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAPK92A
Outdoor Unit SAPC92A
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz
Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 3.40 / 3.40 / 3.40
BTU/h 11,600 / 11,600 / 11,600
Air circulation (High) m3/h 470
Moisture removal (High) Liters/h 1.1
Available voltage range V 198 to 264
Running amperes A 5.8 / 5.8 / 5.9
Power input W 1,240 / 1,250 / 1,290
Power factor % 97 / 94 / 91
C.O.P. W/W 2.74 / 2.72 / 2.64
Compressor locked rotor amperes A 32 / 33 / 35
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer 1-hour OFF / 12-hour ON or OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi, Lo)
Airflow direction (Indoor )
Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R22 / 875
Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 40 / 37 / 34
Outdoor – Hi dB-A 46
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 12.7 (1/2)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 250 530
Width mm 790 680
Depth mm 174 225
Package dimensions Height mm 242 580
Width mm 850 812
Depth mm 312 315
Weight Net
kg 7.0 32.0
Shipping
kg 10.0 34.0
Shipping volume m3 0.06 0.15
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAPK122A
Outdoor Unit SAPC122A
4
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz
Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 5.15 / 5.15 / 5.00
BTU/h 17,600 / 17,600 / 17,100
Air circulation (High) m3/h 760
Moisture removal (High) Liters/h 2.7
Available voltage range V 198 to 264
Running amperes A 9.5 / 9.5 / 10.1
Power input W 2,000 / 2,030 / 2,130
Power factor % 96 / 93 / 88
C.O.P. W/W 2.58 / 2.54 / 2.35
Compressor locked rotor amperes A 50 / 53 / 55
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer 1-hour OFF / 12-hour ON or OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi, Lo)
Airflow direction (Indoor )
Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R22 / 1,350
Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 41 / 38 / 36
Outdoor – Hi dB-A 53
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 12.7 (1/2)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 810
Depth mm 196 275
Package dimensions Height mm 276 704
Width mm 1,070 953
Depth mm 363 396
Weight Net
kg 12.0 49.0
Shipping
kg 15.0 53.5
Shipping volume m3 0.11 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAPK182A
Outdoor Unit SAPC182A
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz
Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 7.00 / 7.00 / 7.00
BTU/h 23,900 / 23,900 / 23,900
Air circulation (High) m3/h 840
Moisture removal (High) Liters/h 3.3
Available voltage range V 198 to 264
Running amperes A 13.1 / 13.1 / 13.4
Power input W 2,730 / 2,730 / 2,800
Power factor % 95 / 91 / 87
C.O.P. W/W 2.56 / 2.56 / 2.50
Compressor locked rotor amperes A 67 / 70 / 73
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer 1-hour OFF / 12-hour ON or OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi, Lo)
Airflow direction (Indoor )
Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R22 / 1,700
Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 43 / 41 / 39
Outdoor – Hi dB-A 55
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 10
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 15.88 (5/8)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 810
Depth mm 196 275
Package dimensions Height mm 276 704
Width mm 1,070 953
Depth mm 363 396
Weight Net
kg 12.0 59.0
Shipping
kg 15.0 62.0
Shipping volume m3 0.11 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAPK252A
Outdoor Unit SAPC252A
6
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K92GJ
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow
Number ... Dia. and length mm 1 ... ø97 / L578
Fan motor model ... Number IBH-884-020 ... 1
No. of poles ... rpm (240 V, High) 2 ... 1,290
Nominal output W 20
Coil resistance (Ambient temp. 20°C) WHT – BRN : 201
WHT – VLT : 261
Safety Type Thermal fuse
devices Operating temp. Open °C 130
Close
Run capacitor µF 1.5
VAC 440
Type Stepping motor
Model MP24GA3
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) A pair of each terminal: 380 ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.4
Face area m
2
0.110
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAPK92A
7
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K122GJ
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow
Number ... Dia. and length mm 1 ... ø97 / L578
Fan motor model ... Number IBH-884-020 ... 1
No. of poles ... rpm (240 V, High) 2 ... 1,350
Nominal output W 20
Coil resistance (Ambient temp. 20°C) WHT – BRN : 201
WHT – VLT : 261
Safety Type Thermal fuse
devices Operating temp. Open °C 130
Close
Run capacitor µF 1.5
VAC 440
Type Stepping motor
Model MP24GA3
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) A pair of each terminal: 380 ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.4
Face area m
2
0.110
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAPK122A
8
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K182GJ
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow
Number ... Dia. and length mm 1 ... ø88 / L746
Fan motor model ... Number UF2-31A5P-S ... 1
No. of poles ... rpm (240 V, High) 2 ... 1,440
Nominal output W 30
Coil resistance (Ambient temp. 20°C) WHT – BRN : 133.7
WHT – PNK : 168.4
Safety Type Internal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440
Type Stepping motor
Model MP24GA2
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area m
2
0.156
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAPK182A
9
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K252G
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow
Number ... Dia. and length mm 1 ... ø88 / L746
Fan motor model ... Number UF2-31A5P-S ... 1
No. of poles ... rpm (240 V, High) 2 ... 1,440
Nominal output W 30
Coil resistance (Ambient temp. 20°C) WHT – BRN : 133.7
WHT – PNK : 168.4
Safety Type Internal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440
Type Stepping motor
Model MP24GA2
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area m
2
0.156
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAPK252A
10
2-2-2. Outdoor Unit
Type Rotary (Hermetic)
Compressor model C–R81H5Q 80682645–S
Nominal output W 800
Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 500
Coil resistance (Ambient temp. 25°C) C – R : 3.38
C – S : 7.49
Type External (OLR A) External (OLR T)
Safety Overload relay MRA99109–9201 CS–7C115
devices Operating temp. Open °C 150 ± 5 115 ± 3
Close °C 69 ± 11 95 ± 5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 16 A
Run capacitor µF 22.5
VAC 400
Type Propeller
Number ... Dia. mm 1 ... ø 370
Fan motor model ... Number UE6-21AH5PB-S ... 1
No. of poles ... rpm (240 V, High) 6 ... 780
Nominal output W 20
Coil resistance (Ambient temp. 20°C) WHT – BRN : 338.3
WHT – PNK : 389.7
Safety Type Thermal fuse
devices Operating temp. Open °C 145 ± 2
Close
Run capacitor µF 1.5
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 1
Fin pitch mm 1.3
Face area m
2
0.333
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAPC92A
11
Type Rotary (Hermetic)
Compressor model CR112H5X 80616745–S
Nominal output W 1,100
Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 550
Coil resistance (Ambient temp. 25°C) C – R : 1.96
C – S : 5.38
Type External (OLR A)
Safety
Overload relay MRA99122–9201
devices Operating temp. Open °C 150 ± 5
Close °C 69 ± 11
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 25 A
Run capacitor µF 25.0
VAC 400
Type Propeller
Number ... Dia. mm 1 ... ø 370
Fan motor model ... Number UE6S–21AC5P–S ... 1
No. of poles ... rpm (240 V, High) 6 ... 780
Nominal output W 20
Coil resistance (Ambient temp. 20°C) BRN – WHT : 341.2
WHT – YEL : 212.7
YEL – PNK : 190.0
Safety
Type Thermal fuse
devices Operating temp. Open °C 145 ± 2
Close
Run capacitor µF 1.5
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.2
Face area m
2
0.329
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAPC122A
12
Type Rotary (Hermetic)
Compressor model 2JS350D5BC02 8520452625100
Nominal output W 1,700
Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 1,130
Coil resistance (Ambient temp. 25°C) C – R : 0.981
C – S : 2.845
Type Internal protector
Safety
Overload relay
devices Operating temp. Open °C Automatic opening
Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C)
Run capacitor µF 45.0
VAC 400
Type Propeller
Number ... Dia. mm 1 ... ø 420
Fan motor model ... Number KFG6S–51A5P–S ... 1
No. of poles ... rpm (240 V, High) 6 ... 880
Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 67.09
WHT – YEL : 68.12
YEL – PNK : 15.66
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 4.0
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 1
Fin pitch mm 1.3
Face area m
2
0.506
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAPC182A
13
Type Rotary (Hermetic)
Compressor model C-R221H5S 80687145
Nominal output W 2,200
Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 1,350
Coil resistance (Ambient temp. 25°C) C – R : 0.777
C – S : 2.408
Type Internal protector External (OLR T)
Safety
Overload relay OL–D24
devices Operating temp. Open °C Automatic opening 150 ± 5
Close °C Automatic reclosing 63 ± 11
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 59 A
Run capacitor µF 40.0
VAC 400
Type Propeller
Number ... Dia. mm 1 ... ø 420
Fan motor model ... Number KFG4S–51C5PA–S ... 1
No. of poles ... rpm (240 V, High) 4 ... 1,000
Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 55.1
WHT – YEL : 37.2
YEL – PNK : 15.5
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 5.0
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.2
Face area m
2
0.499
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAPC252A
2-3. Other Component Specifications
14
<Except SAP-C92>
Thermostat (Fan Speed Control 23S) MQT5S
Switching temp. °C
high LOW 28.5°C ± 1.5
low HIGH 31.5°C ± 2
Contact rating AC 220V, 3A
Power Relay (PR) EL1U
Coil rating AC 200240V, 50/60Hz
Contact rating AC 277V, 30A
Outdoor Unit SAPC92A
SAPC122A
Thermistor (Room sensor) DTN-TKS128B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A
Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAPK92A
SAPK122A
15
Thermostat (Fan Speed Control 23S) MQT5S
Switching temp. °C
high LOW 28.5°C ± 1.5
low HIGH 31.5°C ± 2
Contact rating AC 220V, 3A
Power Relay (PR) EL1U
Coil rating AC 200240V, 50/60Hz
Contact rating AC 277V, 30A
Outdoor Unit SAPC182A
SAPC252A
Thermistor (Room sensor) DTN-TKS142B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A
Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAPK182A
SAPK252A
16
3. DIMENSIONAL DATA
Indoor Unit SAPK92A
SAPK122A
790
250
174 (3)
Narrow tube ø6.35 (1/4")
Drain hose ø18
58.5
132
41.0
41.0
Center of tubing
hole (2 places)
Wide tube ø9.52 (3/8")
Wide tube ø12.7 (1/2")
K92
K122
Remote control unit
22.2
14
59.7
64.6
1401037.6
69.5
Unit : mm
17
Indoor Unit SAPK182A
SAPK252A
28545
995
45
147.5 147.5
196 (3)
Center of tubing
hole (2 places)
Narrow tube ø6.35 (1/4")
Drain hose ø18
Wide tube ø12.7 (1/2") K182
Wide tube ø15.88 (5/8") K252
Remote control unit
22.2
14
59.7
64.6
1401037.6
69.5
Unit : mm
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58

Sanyo SAP–C92A Technical & Service Manual

Type
Technical & Service Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI