Polyaire Zonemaster ZoneTouch V2 Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Polyaire Zonemaster ZoneTouch V2 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ZoneTouch V2
Zone Control System
Installation Manual
www.polyaire.com.au
©2014 Polyaire Pty Ltd
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 1
1) Application 2
2) Features 2
3) Components 3
4) Configuration 4
5) Pre-Installation 6
6) Component Installation 7
7) Recommended Commissioning Procedure 10
7.1 Setting Parameters 10
1) Touch Screen Address 11
2) Number of Groups in the System 11
3) Supply Air Safety High & Low Limits 12
4) Spill/Bypass Mode 13
5) Installer Settings Password 14
7.2 Grouping Zones 15
7.3 Balancing Zones 15
7.4 Naming Groups 16
7.5 Enabling/Disabling Service Reminder 17
7.6 Testing Damper On/Off 18
8) Troubleshooting Guide for Installers 19
TABLE OF CONTENTS
Liability
Please read the instructions before installing this Zonemaster Zoning Control System.
Polyaire Pty Ltd does not accept any responsibility for loss or damage that may occur as a result of the incorrect
installation of this Zonemaster Control System.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
2
1) Application
The Zonemaster ZONETOUCH V2 control system is a fully featured and engineered
 systemthatisdesignedtomanagetheairowfromtheACunitprovidingabalanced
 andmanagedairowtoalloutlets.Itiswellsuitedtoallductedreversecycle,ducted
 heatingandcoolingsystemsinlightcommercial,residentialandapartmentapplications.
2) Features
For Installers
 24voltsforeasyandsafeinstallationandmaintenance.
• Userfriendly5”touchscreeninterfacetosimplifysetupprocess.
• Supportsupto16individualzones(Zone1,2…9,A,B…G),16groups(Group1,
29,A,B…G)withmaximumof4zonesinagroup.Ninezones/groupsand
  abovewillrequireanextensionmodule.
• Remotezonebalancing---eachzone’sopeningpositioncanbeprogrammedfor
  balancingviatouchscreenbetween10-100%.
• Autospill/bypass(dedicatedbypasszoneport)---thedesignatedzonedampers
areforcedopenwhenallzonesareturnedo.
• Safetysystem---Opensalldampersifthesupplyairtemperaturereaches
low or high limit.
 Dampersareconnecteddirectlytothemaincontrolmoduleoritsextension
module for easy diagnosis.
For End Users
• Userfriendlylargetouchscreencontrolinterface.
• Intuitiveuserinterface.
 Controlairowtoindividualgroups.
 ColourLCDforclearerdisplay.
 Personalizedsystemsettingsandgrouplabelling
 Wallmountedwithuptotwotouchscreensavailableinasystem.
 5-1-1ProgrammableOn/Otimeprograms.
• Oneselectableturbogrouptocool/heataparticularareaquicker.
• Halfyear,OneyearandTwoyearservicealertsremindcustomerstocall
  technicianforcleaningandservicingACsystem.
• Allzonesautomaticallyresumetheiroriginalon/ostateoncepowerisrestored
after power outage.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 3
3) Components
Note: Each component is sold separately or in kits.
3.1 Wall Controller (Touch Screen)
Users can input control commands from the wall
   controllertoturnagroup/zoneonando.Itisused
toinputallprogramparameters.ThecolourLCD
   displaysclock,zonestatus,temperatureandother
statuses.
3.2 Main Control Module and Extension Module
(optional)
Maincontrolmodule(8zoneswithbypassport)and
itsoptionalextensionmodule(extra8zones)control
thepositionofmotorizeddamperofeachzone.
3.3 Motorized Damper (Bright Green)
Motorizeddamperdrivesthebladeofthedamperto
   adjusttheairow.
3.4 Cables
   Cableswithleftlatch(fordata)orcentrallatch(for
   control)plugsconnectthemaincontrolmodule,
   extensionmodule(ifapplicable),touchscreen,and
   motorizeddampertogether.
3.5 Supply Air Sensor (optional)
Supply air sensor measures the temperature of the
supply air for safety purposes.
3.6 Power Supply
24VACtransformersprovidepowertothemaincontrol
   moduleandextensionmodule.
3.7 Rechargeable Battery
Thebackupbatteryisusedtostorethetimeand
settings when there is a power surge.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
4
4)Conguration
The Zonemaster ZONETOUCH V2 system is a star architecture system that allows
 communicationsbetweentheZONETOUCHV2maincontrolmodule,extensionmodule,
 upto16zonedampers,anduptotwotouchscreens.Figure1showstheconnection
 ofdevicessuchasZONETOUCHV2extensionmodule,twotouchscreens,andeight
 damperstothemainmodule.Figure2showstheconnectionofeightdamperstothe
 extensionmodule.Figure3showsthelinkingofthemainmoduletotheextension
module and touch screens.
Eightmotorizeddamperscanbeconnectedtothemaincontrolmodule.
Ninedampersandabove(upto16)willneedtheextensionmodule.
Inaddition,thereisadedicatedbypassportwhereadamperisusedtoreturnthe
supplyairdirectlytothereturnairduct.(SeeSpill/BypassModeonpage13)
Extension Module
Anextensionmodulecanbepluggedintothemaincontrolmoduletoexpandthe
numberofzonesto16asshowninFigure2.Aseparate24VACpowersupplyis
requiredtosupplypowertotheeightextrazones.
Figure 1: ZoneTouch Main Module connected to 2 Touchpads and 8 Dampers
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 5
The wiring of the ZONETOUCH V2 system is straightforward. A cable with central
latchedplugsconnectsamotorizeddampertotherelevantoutputportclearlymarked
onthemaincontrolorextensionmodule.
Themainmoduleandextensionmodulecanbeindierentlocationsandconnected
viaacablewithleftlatchedplugsonbothendsasshowninFigure3.Touchscreenis
connectedtothe‘T’portonmainmoduleusingacablewithleftlatchedplugs.
Up to two touch screens can be joined in a system. The two touch screens are
connected to each other with a double left latched adaptor in serial.
Figure 2: Zone Touch with Extension Module and 8 Zone Dampers
Figure 3: ZoneTouch Main Module with Extension Module and 2 Touchpads
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
6
5) Pre-Installation
Goodplanningleadstoasuccessfulzonesysteminstallation.Beforephysically
 installingandcommissioningazoningsystem,pleasecompletethefollowinglistedtasks:
 5.1Decidehowmanyzones(dampers)aretobecontrolledinthesystem.
5.2 Assign lowerorderzones(1,2,3…)todampersclosesttothereturnairgrille.
  Thesezoneswillautomaticallyopenwhenspillingisrequired.Howeveravoidusing
  lowerorderzonesforbedroomsasthismaycausediscomfortifautospilling
occurs during sleep time.
5.3 Groupzonesaccordingtocustomer’srequirements.Eachgroupinitiallyhasone
  zonebutcanhaveuptoamaximumoffourzones(Example:Therecouldbeone
  ormorezonesgoingintoacommonareasuchasKitchen/DiningorFamily/Dining
  room).Workoutthetotalgroupnumber(Maximumtotalgroupnumberinasystem
is 16).
5.4 Recordtheabovementionedinformationtotable1and2onpage11intheUser
  manualandtothetableonthestickeroftheMainControlModule.
NOTE: It is important to test all cables
before installation. Testing all cables to
be used before the start of the installation
will save considerable diagnostic time if
the fully installed system is subsequently
found to have a problem. Cable testing is
quick and easy with a Zonemaster Cable
tester available from Polyaire
Cable Tester
(ItemNumber:657089)
Note: When installing two touch screens, use a long cable (as long as
practical) between the main module and the double left latched adaptor,
two short cables between the adaptor and two touch screens and try to
maintain the two short cables at the same length.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 7
6) Component Installation
6.1 Mountthemaincontrolmoduleand/orextension
  module(ifusingmorethan8zones)byscrewing
  thebox(es)toaroofframeorPolyaireDiusion
  Fitting(PDF).
 6.2 Remove thetwo-sidecoversonthemaincontrol
  modulesothatallLEDsandsocketsforzone
  dampersareexposed.
6.3 If extensionmoduleisused,connectmainmodule
  toextensionmoduleat‘E’portonbothmodules
  withaonemetreleftlatchedcable(provided).
6.4 Use pre-testedcabletoconnectZ1’portonthe
  mainmoduletothemotorizeddamperofthe1st
  zone.
 6.5 Repeat step6.4toconnectotherzonedampers,
  includingbypassdamper(‘B’port)ifinstalled,
  totheirrelevantzoneportsonthemaincontrol
  moduleandextensionmodule.
6.6 Mount the supply air sensor in the supply air duct
  betweenthefancoilandtherstdamperandpush
the plug of supply air temperature sensor into the
  socketonthemaincontrolmodule(Optional).
6.7 Connectthetouchscreentothe‘T’portonthe
  mainmodule.Iftwotouchscreensareused,
  usetheprovidedleftlatchedcablesanda1-to-2
  female-femalesplittercouplertojoinalltouch
  screens.(Seeinstructionsbelowontmentof
touch screen to wall).
6.8 Connect the 24VAC transformer to screw terminals
  onthemaincontrolmodule.Ifextensionmoduleis
  used,connectanother24VACtransformertothe
  screwterminalsoftheextensionmodule.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
8
6.9 Ifbothtransformers(mainmoduleandextension
  module)sharethesamepowerswitch,switchthe
power on. (IMPORTANT NOTE) If NOT, switch on
  thepowertoextensionmodulerst.Thenturn
on the power to main module.Otherwise,the
  extensionmodulewillNOTbeinitializedproperly.
  CircularRedLEDonthemainmodule(and
  extensionmodule)shouldbeonandthesystemwill
  startinitializing&nishinabout30secondsafter
power on.
6.10 Install the battery as shown in the picture on the
main control module. It is recommended to install
the battery after power is on. Otherwise the system
  maynotbeinitializedproperlyduetothelow
  voltageofthenewbattery.
6.11 Replacethesidecoversbackonthemaincontrol
  andextensionmoduleoncenishedsettingand
commissioning.
6.12 Recordthegroupedzonesandbalancingdetails
  onthestickerotheMainControlModuleafter
commissioning the system.
6.13 FittheTouchScreen to wall
Theplasticcasingofthetouchscreenconsistsoftwohalves.Thefrontcover
  containsthePCBboardalongwiththeLCD/touchscreen.Thebackcover
  attachestothewallasamountingbase.Duringtheinstallationprocessthecase
  willhavetobeopenedtomountthetouchscreenonthewall.Followthesteps
  belowtocarefullyinstallthetouchscreentothewall:
a) Slidethebackbasetobottomsidetoclearthestopsonthefrontcover
b) Removethebasefromthefrontcover
c) Position thebackbaseonthewallwherethecableis(about1.5mhighfrom
 theoor).Ensureitisawayfromanyheatorcoolsourceandmarkthecable
hole and screw holes.
NOTE: The correct back cover direction is marked on its surface; follow that
  markwhenxingthebackcover.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 9
d) Cut therectangularholeforthecableandxthebackbasetothewallby
 usingfourscrewsonthemarkedpositions.
e) Retrieve thetouchscreencable(frommain
control module) out of the cable hole and plug it
into the touch screen.
f) Alignthebottomedgeofthebackbasewiththe
 bottominsideofthefrontcoverandthetwoside
 edgesofthebackbasewiththefrontcover.
g) Gentlypushthefrontcoveragainstthewalland
 makesurethebackoffrontcoverisushagainst
 thewall.Andthenpushthefrontcover
 downwardswithtwoguresholdingthetopside
 ofthefrontcoverwheretherearetwoslotstill
 thetwosnap-onsclickin.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
10
7) Recommended Commissioning Procedure
7.1 Setting Parameters
System parameters canbesetupfrom‘InstallerSettings’screen.
Followthestepsbelowtosetrequiredvalues.Touchingbuttoninthe
  settingprocesswillgobackto the home screen from any setting pages.
a) Touchonthehomescreen(Figure3)toenter‘Settings’screen
 ( F i g u r e 4).
b) On‘Settings’screen,touchbuttontoshowthekeyboardfor
 e n t e r i n g thepasswordofinstallersettings(Figure5).
c) Enter thepasswordofinstallersettings(Figure6),thedefaultpasswordis
‘Polyaire.
NOTE: The password is case sensitive. Maximum length for the password is
eight characters but it can also be blank.
Figure 3.
Figure 5.
Figure 4.
Figure 6.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 11
7.1.1 Touch Screen Address
Up to two touch screens can be installed in one system. Each touch screen has
 adefaultaddressof1’.Duringcommissioningeachtouchscreenshouldbe
  assignedauniqueaddressforcommunicatingwiththemaincontrolmodule
  properly.FollowthefollowingstepstosettheTouchscreenAddress: 
a) On‘InstallerSettings’screen(Figure6),touch‘Parametertogetto‘Parameter
 screen(Figure7).
b) Touch theediteldof‘TouchpadAddress’tohighlightit,and
 buttonswillappear(Figure8).
c) Use and buttons to select a touchpad address from 1 to 2.
NOTE: Each controller (touch screen) must have a unique address.
Two touch screens with the same address will cause communication
problems between the main control module and the touch screens.
7.1. 2 Number of Groups in the System
For the purpose of groupstatusdisplayandspill/bypasszonecalculation,the
  systemneedstoknowthetotalnumberofgroupstobeinstalled.Thefactory
default number is 8.
IMPORTANT: This number must be equal to the total group number used
in the system as planned in Pre-Installation process. If this is wrong, the
system may not work properly.
a) Touch the totalgroupeld,and
buttonswillappear(Figure9).
b) Press or button to change
to the total number of groups in the
system. The selectable number is
from 1 to 16.
Figure 7. Figure 8.
Figure 9.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
12
7.1.3 Supply Air Safety High & Low Limits
Forsafetyreasons,thesystemcanmonitorthe supply air temperature. A
supply air sensor must be inserted at the supply air end of the AC and the other
  endistobeconnectedtotheMainmodule,asshownonPage7forthissafety
  functiontobeactivated.Ifthetemperaturemovesoutsidethesetlimits,all
dampers in the system will be forced open. The factory default setting for the
  safetycontrolisdisabled”.Itisoptionalforusingthisfunction.
a) Onthe‘Parameter’screen(Figure6),touch the radio button of high limit and low
limit to enable or disable safety function.
If the supply air sensor has not been installed or the supply air sensor is faulty
 a n d thereplacementsensorisnotavailableimmediately,thesystemcanstillrun
by disabling the safety function.
b) Highlight the high limit or low limit
 b y touchingtheediteldsaccordingly,
 a n d thenadjustthemtotherequired
 v a l u e bytouchingorbutton
 ( F i g u r e 10).
The adjustable range of the high limit
is from 45°C to 75°C and adjustable
range of the low limit is from 0°C to
 15 ° C . Thefactorydefaultvaluesare
60°C for high limit and 5°C for low limit.
NOTE: If the limits are reached,
Safety is Activated’ will be displayed
on the home screen (Figure 11). The
ON/OFF function of groups will be
disabled till supply air temperature
moves back within the limits or the
High Limit and Low Limit protection is
disabled (there is about one minute
delay after disabling the protection).
Check the air conditioning unit.
Figure 10.
Figure 11.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 13
7.1.4 Spill/Bypass Mode
Bypass and spill modes are another safety feature of the ZONETOUCH V2
  systemtopreventpressurefrombuildingupandcausingductdamage.This
  usuallyoccursifsomeonehasturnedoalldamperswhiletheA/Cunitis
  runningleadingtoapressurebuildup(andpotentialofductpuncture,blow-os
or joints splitting).
Whenopenedzonesinthesystemarelessthanthebypass/spillset-point
  whichisapercentageofopenedzonesagainsttotalzones,thedesignatedspill
  dampersorBypassdamperwillbeautomaticallyopenedtopreventpressure
from building up.
Spill Mode
  Thisisaprogramdesignedtoautomaticallyopenseveraldampersifsomeone
  attemptstoshutdownalldampersthuspreventingpressurebuildup.Spillmode
  usesthezoneswithloweraddressesinthesystem.Whenallocatingaddresses
t o zonesinspillmode,itisstronglyrecommendedtogiveloweraddressesto
  thosezonesthathavehigherspillprivileges.Thesezonesarenormallylocated
  closertothereturnairgrilles.Thelowertheaddress,thehigherthespillprivilege
  thezonehas.
AnotherpointtorememberisDONOTusebedroomsasspillzones.Duringsleep
  timeiftheairconditionerisonandspillzonesareautomaticallyforcedtoopen,
t h e spillzoneswillbeverycoldorhot.Thismaycausediscomfortifbedrooms
  areusedasspillzones.
Whenthespillset-pointisreached,themaincontrolmoduleinstructszone1to
  openasspillzone.Iftherstspillzonecannotsatisfythespillaircontrol,zone2
  willautomaticallyopentospillexcessair.Thisprocesswillcontinueuntilthespill
  airset-pointissatisedinthesystem.Example:Inaneightzonesystem,ifset
  pointissetat30%thenitwillhaveatleast3(calculatedvalue=2.4)ormore
  zonesremainingopen.
Bypass Mode
  InBypassModethereisanextradamperandalengthofductthatgoesdirectly
  fromthesupplyairductbacktothereturnairduct.Themaincontrolmodule
  instructsthebypassdampertoopenanddumpexcessairtothereturnairduct.
Thebypassdampershouldbecarefullysizedtobeabletohandleexcessairwhile
  allzonesareclosed.Thebypassdampershouldbeconnectedtothe‘B’porton
the main control module.
Thefactorydefaultissetinspillmodeandtheset-pointis30%.Whenthesetpoint
  isreachedforspill,thehomescreenshows‘SpillisActivated‘andsomeofthe
  lowerorderzonesremainopenandthestatusoftheGroupswilldisplay‘Spill’in
  thehomescreen(Figure12)ifthelowerordergroupswereclosed.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
14
Similarlyifbypassset-pointisreached,thescreendisplays‘BypassisActivated’
  asshowninFigure13.
Spill/Bypass Settings
a) In the‘Parameter’screen(Figure7),touchtheoptionbuttonsofspillorbypass
to select spill mode or bypass mode.
b) Touchspill/bypassediteldtomakeiteditable,andthenand
buttons will appear.
c) Touch orbuttontochangethespill/bypassset-pointtorequired
 v a l u e . Theadjustablerangeisfrom0%to50%with10%increments.
IMPORTANT: DO NOT set spill/bypass set-point to 0% unless there is a
permanent open zone used as spill zone. Otherwise, there will be no spill
zone when all zones are closed and damage may be caused by high
pressure build up inside ducts if air conditioner is running.
Figure 12. Figure 13.
Figure 14.
7.1.5 Installer Settings Password
The password which will be used in
  Figure5istopreventunauthorized
changing of the installer settings.
  Toresetthispassword,touchthe
  passwordediteldinthe‘Parameter’
  screen(Figure7),andthentypeinthe
  newpasswordandtouch‘Enter’key
  toconrmthepasswordchange
  (Figure14).
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 15
Figure 15. Figure 16.
Figure 17.
7.2 Grouping Zones
For ease of control operation,multiplezonescanbegroupedtogether.The
  groupedzonesaretreatedasonegroupwithitsownnameandturnedonoro
  together.Individualbalanceddamperpositionisnotaectedbygrouping,
  whichmeanszonebalancingcanbeconductedbeforeoraftergrouping.
Groupingcanbecarriedoutasfollows:
a ) I n ‘InstallerSettings’screen(Figure6),touch toenterGrouping’
 screen(Figure15).
7.3 Balancing Zones
Remote balancing feature of ZONETOUCH V2oerstheexibilityofbalancing
  theamountofairowtoeachzoneelectronically.Oncetheopeningpositionof
  thedamperisset,thedamperwillonlyopentothisposition.Thedefaultsetting
  foreachdamperis100%openingpositionandtheadjustablerangeisbetween
  10%and100%.Thebalancingsettingscanbeconductedonthetouchscreen
as below.
a) In ‘InstallerSettings’screen(Figure
 6 ) , touch
b) The system will show a prompt
 ( F i g u r e 17)andthenenterthe
 ‘Balancing’screen(Figure18).
b) Touchtheediteldofthegroup, and buttons will appear.
c) Touch or buttontoaddorminuszonestothegroup
d) Repeatstepsb)andc)todeneallgroups.
NOTE: The maximum number of zones in a group is four. The zones to be
grouped will be consecutive zones. The factory default for grouping is that
each group has one zone.
7.4 Naming Groups
Thenameofagroupissetas‘Group_address’(e.g.Group_1)indefaultsetting.
  Thenamescanbecustomizedasfollows:
a) In ‘InstallerSettings’screen(Figure
 6 ) , touchtoenter
 ‘Naming’screen(Figure20).
b) Touchtheediteldofagroupto
rename it. A name list will appear for
 selection(Figure21).
c) Touch a name in the list to specify
 t h e nametothegroup,andalso
you can touch to enter
 o r editanamemanually(Figure22).
d) TouchtoconrmortouchtocancelandbacktoNaminglist
 pageortouchtocancelandbacktothehomescreen.
c) Clicktheediteldtoselectthezonetobebalanced,theeldwillbe
 highlightedthenandbuttonswillappear(Figure19).
d) Touch or button to adjust the balance percentage.
e) Touch button to accept the changes just made.
NOTE:
• Thebalancing menu will display all 16 zones irrespective of the number
of zones actually present in the system.
• Thebalancing percentages of the inactive zones remain locked and show
as N/A.
• The OPEN % value on the Zoning screen can be operated by the user for
 additionalairowadjustmenttothegroups.Theoverallopening%ofthe
zone is calculated as OPEN % x Balance %.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
16
Figure 18. Figure 19.
Figure 20.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual 17
Figure 21. Figure 22.
Figure 23.
Figure 24.
7.5 Enabling/Disabling Service Reminder
Thereisabuilt-inservicereminderintheZONETOUCHV2systemforhalfyear,
one year and two years to automatically display an alert notifying customers
t h a t theairconditioningsystemisdueforservice.Installerscanalsousethis
  featuretoleavetheirdetailssuchastheirnamesandcontactnumbers.
Theservicereminderwilldisplay‘HALFYEARSERVICEDUE’,‘ONEYEAR
  SERVICEDUE’or‘TWOYEARSERVICEDUE’andinstaller’snameandcontact
number on touch screen for the set number of days if it has been enabled for
  halfyear(182days),oneyear(365),twoyears(728days)respectivelysincethe
  airconditioningsystemhadbeencommissionedorservicedasshowningure
  26.ThedaysintheServicescreenwillautomaticallyresetto1after728days
  orcanbemanuallychanged.TheServiceReminderisdisabledbydefaultbut
  canbeenabledasfollows:
a) In the‘InstallerSettings’screen
 ( F i g u r e 6),touch to
 e n t e r the‘Servicescreen(Figure23).
b) Touchtheservicereminderoption
buttons to enable or disable the
 relevantreminders.
c) Touchtheediteldtochangetothe
desired setting. The installer name
and number can be entered by
 usingakeyboard(Figure24).
or buttons can be used to adjust
 reminderandrunningdays(Figure25).
Maximum length of the name is 10
characters and the phone number is
12 digits.
ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM - Installation Manual
18
Figure 25.
Figure 26.
 Reminderinformationwillbe
displayed on the right side of the
 touchscreenwhentheserviceisdue
 ( F i g u r e 26)forthelengthofthe
 reminderdays(5daysinthe
 exampleofgure23).Touchingthe
information area will clear the alert
before the set reminder days has
reached.
The running days show how many
 d a y s havingpassedsincethesystem
 h a s beencommissionedorserviced.
It will automatically start from 1 for
 e v e r y 728days.
NOTE: Record the above parameters
such as Grouped Zones & Balancing
on the sticker of the Main Control
  ModuleandtheSystemConguration,GroupedZonesalongwithNamed
Groups, Balancing and Installer details to table 1, 2, 3 and 4 respectively on
page 11 and 12 of the User manual for future reference.
7.6 TestingDamperOn/O
a) Switch on the air conditioner.
b) Enter the home screen of ZONETOUCH V2.
c) Touch thegroupbuttonstoturngroupsonorotocheckifthedampersare
correctly connected by feeling the air at the outlet.
d) The Turbogroupcanbetestedbyselectingtherelevantchosengroupas
 Tu r b o modeinthe‘UserSettings’andthenpressthegroupbuttonuntil
 a c t i v e turbomodeisdisplayedonthescreenforthatparticulargroup.
NOTE: Bypass zone damper cannot be tested via touch screen. It has to be
checked by observing the indicator on the damper motor.
/