Kampmann PowerKon LT, electromechanical control version Installation Plan

Category
Thermostats
Type
Installation Plan
Project Number:
Cable routing plan
10.07.2023
Version number: 01
PowerKon LT
Blatt-Nr.:
6
Projekt-Nr.:
Bearbeiter:
Erstelldatum:
Projekt:
10.07.2023 2von
General Information
Information on cable laying:
The following information on cable types and cable laying must be observed in compliance with VDE 0100.
The installation, operation and maintenance of these devices must comply with the country-specific applicable laws, standards, regulations and directives.
Without *: NYM-J. The required number of cores incl. protective conductor is indicated on the cable. Cross sections are not indicated, as the cable length is included in the calculation of the cross
section.
*): Shielded cable, J-Y(ST)Y 0.8mm. Lay separately from power lines.
**): Shielded cable stranded in pairs, e.g. UNITRONIC® BUS LD 2x2x0.22, UNITRONIC® BUS LD 3x2x0.22. Install separately from power lines.
- If other cable types are used, they must be at least equivalent.
- The connection terminals on the device are suitable for a maximum wire cross-section of 2.5 mm², the mains plug for max. 4.0 mm².
- When using residual current circuit breakers, these must be at least mixed frequency sensitive (type F). For the design of the rated residual current, the specifications from DIN VDE 0100 Parts 400
and 500 must be observed.
- For the design of the on-site mains supply and fuse protection (C16A, max. 10 devices), the electrical data in the table below must be observed.
- Lines for data or bus signals are shown with shield connected at one end. Lines for analog signals are shown with the shield not connected. Due to structural or local conditions and depending on
the type and level of interference, which can be caused by magnetic and/or electric fields in high and/or low frequency ranges, among other things, a different connection of the shield (connected at
both ends or not connected) may be necessary. This must be checked by the customer and, if necessary, carried out deviating from the specifications in the documentation!
Electromechanical:
- Cable length between room thermostat and temperature sensor or switching contact: max. 50 m.
Display control:
- Maximum number of units in parallel: 30.
- BUS cable length from unit 1 to unit 30: maximum 150 m.
- A terminating resistor (120 Ohm) must be set at the first and last participant of a line. Use jumpers 2 and 3 on the control board for this. Jumper closed = terminating resistor set. Before setting the
terminating resistor, the control unit must be disconnected from the power supply.
Blatt-Nr.:
6
Projekt-Nr.:
Bearbeiter:
Erstelldatum:
Projekt:
10.07.2023 3von
PowerKon LT, 2-wire, electromechanical,
valve drive 24V, open/close, condensate pump optional,
Control via GA
5*
W3
gn/ge
1
2
L N PE GND Uc VHi1 2 3 4
Ri 100 K
5*
W4
2
24V
AA1
GND
AA1
0-10V
AA2
GND
AA2
0-10V DA2PEPE
NPEL
1
2
gn/ge
Main supply
230V
Fuse protection on site.
Observe the „Electrical data“
table.
Main supply
230V
PowerKon LT
Electromechanical
Unit no. 1
Building Automation (BA)
Valve actuator Open/Close Unit 2
Valve actuator Open/Close Unit 1
Speed unit No. 2
Note internal resistance of device!
Speed unit No. 1
Note internal resistance of device!
1
2
gn/ge
gn/ge
1
L N PE GND Uc VHi1234
Ri 100 K
DA1
1
2
3
24V
1
2
3
DI1
Condensate alarm unit 1
Contact open = fault
DI1
4
5
DI2
Condensate alarm unit 2
Contact open = fault
DI2
4
5
4
5
3
1
2
3
W1
3
W2
1
5
4
2
3
Connection box
24V 24V
Condensate alarm
PowerKon LT
Electromechanical
Unit no. 2
Connection box
Condensate alarm
Blatt-Nr.:
6
Projekt-Nr.:
Bearbeiter:
Erstelldatum:
Projekt:
10.07.2023 4von
PowerKon LT, 2-wire, electromechanical,
valve drive 24V, open/close,
Room thermostat 342924
4*
W3
gn/ge
1
2
L N PE GND Uc VHi1 2 3 4
Ri 100 K
4*
W4
2
NPEL
1
2
gn/ge
Main supply
230V
Fuse protection on site.
Observe the „Electrical data“
table.
Main supply
230V
1
2
gn/ge
gn/ge
1
L N PE GND Uc VHi1234
Ri 100 K
4
2
3
3
W1
3
W2
1
2
2
54321
GND VH Uc 24V DI
4
3
Room thermostat
Type 342924
24V 24V
1
4
2
3
1
4
2
3
1
4
2
1
4*
W5
2*
W6
COMNO
1
2
Contact
Day/Eco
- Options -
For more information, see the
instructions for the room thermostat
4
2
3
1
4
2
3
1
4
2
3
1
4
2
1
2*
W7 to additional devices
(Max. number see
information)
PowerKon LT
Electromechanical
Unit no. 1
Connection box Connection box
PowerKon LT
Electromechanical
Unit no. 2
Blatt-Nr.:
6
Projekt-Nr.:
Bearbeiter:
Erstelldatum:
Projekt:
10.07.2023 5von
PowerKon LT, 2-pipe, electromechanical,
valve drive 230VAC, open/close, condensate pump optional,
Air conditioner type 30155
gn/ge
1
2
gn/ge
2
3
1
2
gn/ge
1
2
1
2
1
2
1
2
1
2
12345678910 11 12 13 14
N N N L H K AI GND AO GND UI GND DI GND
3
1
2
COMNO
1
2
1
2
COMNO 1 2
1
2
3
W1
4
1
2*
W5
5
W2
3
Terminal box on site
Room sensor
Contact
e.g. Heat/Cool
Contact
e.g. window
Climate controller
Type 30155
- optional -
More information see Instruction Climate controller
L N PE GND Uc VHi1 2 3 4
Ri 100 K
NPEL
1
2
gn/ge
Main supply
230V
Fuse protection on site.
Observe the „Electrical data“
table.
Main supply
230V
1
2
gnge
1
2
3
4
1
2
gnge
5
W6
3
4
L N PE GND Uc VHi1234
Ri 100 K
4
3
5
W4
4*
W3
1
2
2*
W12
2*
W13
2*
W14
2*
W11
gn/ge
1
2
gn/ge
2
3
4
1
Terminal box on site
3
4
gn/ge
1
2
3
45
W9
2*
W10
to additional devices
(Max. number see
information)
5
W7
2*
W8
PowerKon LT
Electromechanical
Unit no. 1
Connection box Connection box
Condensate alarm Condensate alarm
PowerKon LT
Electromechanical
Unit no. 2
On-site bridge On-site bridge
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6