Amana AMVM97 Owner's manual

Category
Split-system air conditioners
Type
Owner's manual

This manual is also suitable for

19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com • www.amana-hac.com
© 2018-2019, 2021 Goodman Manufacturing Company, L.P.



RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.


INSTALLATION
INSTRUCTIONS FOR






     -
-


is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
IOG-2017D
08/2021
TABLE OF CONTENTS
Safety Considerations .........................................................2
Product Application ..............................................................4
Location Requirements & Considerations ...........................5
Combustion & Ventilation Air Requirements ........................7
Installation Positions ............................................................7
Horizontal Applications & Considerations ............................9
Vent Pipe & Combustion Air Pipe ......................................10
Condensate Drain Lines & Drain Trap ...............................18
Gas Supply and Piping ......................................................23
Propane Gas/High Altitude Installations ............................23
Circulating Air & Filters ......................................................26
Electrical Connections .......................................................29
Startup Procedure & Adjustment .......................................36
Normal Sequence of Operation .........................................39
Operational Checks ...........................................................40
Safety Circuit Description ..................................................40
Troubleshooting .................................................................40
Maintenance ......................................................................41
Filters .................................................................................41
Before Leaving an Installation ...........................................42
Repair and Replacement Parts .........................................42
Menu Options ....................................................................43
Status Codes .....................................................................44
Troubleshooting Chart .......................................................45
Wiring Diagram ..................................................................49
Start-up Checklist ..............................................................50
This device, which was assembled by Goodman Manufacturing


FCC: FCC ID QOQBGM111. And this international radiator has an
Industry Canada ID: IC 5123A-BGM111.
This device complies with Part 15 of the FCC’s Rules. Operation of
this device is subject to two conditions:
(1) This device may not cause harmful interference; and
(2) This device must accept any interference received, including
interference that may cause undesirable operation.
And this device meets the applicable Industry Canada technical

The manufacturer of the intentional radiator (model no. BGM111) is
Silicon Laboratories Finland Oy, which can be contacted by calling
617-951-0200. (www.silabs.com)
Goodman Manufacturing Company, L.P. may be contacted by calling
713-861-2500, or at 19001 Kermier Rd., Waller TX 77484.
(www.goodmanMFG.com)
90% HEX
DO NOT LIFT
PRODUCT USING
HEAT EXCHANGER





-
-








WARNING
2
WARNING




WARNING



AVERTISSEMENT
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result
in serious injury, death or property damage.
Never test for gas leaks with an open flame.
Use a commercially available soap solution made
specifically for the detection of leaks to check all
connections. A fire or explosion may result causing
property damage, personal injury or loss of life.
RISQUE D'INCENDIE OU D'EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la lettre,
cela peut entraîner la mort, de graves blessures ou des
dommages matériels.
Ne jamais vérifier la présence de fuites de gaz au moyen
d'une flamme nue. Vérifier tous les raccords en utilisant
une solution savonneuse commerciale conçue
spécialement pour la détection de fuites. Un incendie ou
une explosion risque de se produire, ce qui peut entraîner
la mort, des blessures ou des dommages matériels.
WARNING










Adhere to the following warnings and cautions when install-
ing, adjusting, altering, servicing, or operating the furnace.
To ensure proper installation and operation, thoroughly read
        
application of this product.
This furnace is manufactured for use with natural gas. It

appropriate L.P. conversion kit listed in the PROPANE
 section of this
manual.
Install this furnace only in a location and position as spec-
     -
ATIONS section and INSTALLATION POSITIONS section
of this manual.
Provide adequate combustion and ventilation air to the fur-
COMBUSTION & VENTILATION AIR
REQUIREMENTS section of this manual.
Combustion products must be discharged to the outdoors.
Connect this furnace to an approved vent system only, as
 
section of this manual.
-
   

 section of this manual.
Always install a furnace to operate within the furnace’s in-
tended temperature-rise range with a duct system which
has external static pressure within the allowable range, as
ed on the furnace rating plate and OPERATIONAL
CHECKSsection of these instructions.
        
LOCATION REQUIRE-
section of this manual.
This furnace may be used as a construction site heater only
if certain conditions are met. These conditions are listed in
the Product Application section.
WARNING




3
B10259-216
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
B10259-216
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
B10259-216
RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE
Le monoxyde de
des
carbone peut causer des maladies graves telles que
dommages permanents au cerveau et meme la mort.
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.
WARNING
-




WARNING











-

-

WARNING




-



-




All units are securely packed in shipping containers tested
-
cations. The carton must be checked upon arrival for exter-
nal damage. If damage is found, a request for inspection by
carrier’s agent must be made in writing immediately. The
furnace must be carefully inspected on arrival for damage
and bolts or screws which may have come loose in transit.
In the event of damage the consignee should:
1. Make a notation on delivery receipt of any visible
damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. 

4. File the claim with the following support documents
within a nine month statute of limitations.
         
indemnity bond.
Original paid freight bill or indemnity in lieu thereof.
       
trade and other discounts or reductions.
Copy of the inspection report issued by carrier’s
representative at the time damage is reported to
carrier.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim. The
distributor or manufacturer will not accept claims from deal-
ers for transportation damage.
WARNING




Before installing this unit, please read this manual thor-

be adhered to, including but not limited to: unit maximum
       
proper electrical connections, circulating air temperature
rise, minimum or maximum CFM.
4
WARNING




Furnace Alone - - -
Furnace + 1 Stage Non-Communicating A/C
Furnace + 2 Stage Non-Communicating A/C
Furnace + 1 Stage Non-Communicating H/P
Furnace + 2 Stage Non-Communicating H/P
Furnace + Communicating A/C
Furnace + Communicating H/P
Furnace + Communicating A/C Inverter
Furnace + Communicating H/P Inverter

This furnace is primarily designed for residential home-heat-
ing applications. It is NOT  
mobile homes, trailers or recreational vehicles. Neither is it

must be installed indoors (i.e., attic space, crawl space, or
garage area provided the garage area is enclosed with an
operating door).
This furnace can be used in the following non-industrial
-
es, retail stores, nursing homes, hotels/motels, common or
-
stalled with the following stipulations:
It must be installed per the installation instructions
provided and per local and national codes.
It must be installed indoors in a building constructed
on site.
It must be part of a ducted system and not used in
a free air delivery application.
It must not be used as a “make-up” air unit.
It must be installed as a two-pipe systems for
combustion air.
All other warranty exclusions and restrictions apply

is appropriate for use with natural or propane gas


 
is optional and the furnace can be vented as a: Non-direct
vent (single pipe) central forced air furnace in which com-
bustion air is taken from the installation area or from air
ducted from the outside or, Direct vent (dual pipe) central
forced air furnace in which all combustion air supplied di-
rectly to the furnace burners through a special air intake
system outlined in these instructions.

ONLY-

The vent system is permanently installed per these
installation instructions.
A room thermostat is used to control the furnace.
Fixed jumpers that provide continuous heating
CANNOT be used and can cause long term
equipment damage. Bi-metal thermostats, or any

during construction.
Return air ducts are provided and sealed to the
furnace.
A return air temperature range between 60ºF (16ºC)
and 80ºF (27ºC) is maintained.
MERV 11 (Example P/N AMP-11-2025-45) air
       
daily and replaced as needed during construction
and upon completion of construction.
The input rate and temperature rise are set per the
furnace rating plate.
The furnace must be installed as a two pipe system,
using 100% outside air for combustion during
construction.
The furnace heat exchanger, components, duct



All furnace operating conditions (including ignition,


instructions.
Furnace doors must be in place on the furnace while
the furnace is operating in any mode.
Damage or repairs due to failure to comply with these
requirements are not covered under the warranty.

-

Gas furnaces must be installed by a licensed

A T-handle gas cock must be used.
If the unit is to be installed in an attic, the passageway
to and the service area around the unit must have

To ensure proper furnace operation, install, operate and
maintain the furnace in accordance with these installation
and operation instructions, all local building codes and or-
dinances. In their absence, follow the latest edition of the
National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or
CAN/CSA B149.1-15 Installation Codes, local plumbing or
waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
5
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Independence, OH 44131
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning Con-
tractors of America.
A copy of the CAN/CSA B149.1-15 Installation Codes can
also be obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
LOCATION REQUIREMENTS &

Follow the instructions listed below and the guidelines pro-
vided in the 
section when selecting a furnace location.
WARNING



WARNING




Centrally locate the furnace with respect to the
proposed or existing air distribution system.
Ensure the temperature of the return air entering
the furnace is between 55°F and 100°F when the
furnace is heating.
Provide provisions for venting combustion products
outdoors through a proper venting system. Special
      
routing and combustion air intake pipe when
applicable. Refer to 
    for appropriate
termination locations and to determine if the
piping system from furnace to termination can be
accomplished within the guidelines given. NOTE:

be a limiting factor in the location of the furnace.

to the drain. Do not locate the furnace or its
condensate drainage system in any area subject to
below freezing temperatures without proper freeze
protection. Refer to    
 for further details.
Ensure adequate combustion air is available for

can expose building occupants to gas combustion
products that could include carbon monoxide. Refer
to
         


a concrete base sized approximately 1-1/2” larger
than the base of the furnace. Refer to the 
   for leveling of
horizontal furnaces.

directly on carpeting, or any other combustible
material. The only combustible material allowed is
wood.
A special accessory subbase must be used for
upright counterflow unit installations over any
combustible material (including wood). Refer to
subbase instructions for installation details. (NOTE:
A subbase will not be required if an air conditioning
coil is located beneath the furnace between the

Exposure to contaminated combustion air will result
in safety and performance-related problems. Do
not install the furnace where the combustion air is
exposed to the following substances:
- permanent wave solutions
- cleaning solutions (such as perchloroethylene)
- printing inks
- chlorinated waxes or cleaners
- paint removers
- chlorine-based swimming pool chemicals
- varnishes
- water softening chemicals
- hydrochloric acid
- carbon tetrachloride
- cements and glues
- deicing salts or chemicals
- halogen type refrigerants
- antistatic fabric softeners for clothes dryers
- masonry acid washing materials
Isolate a   furnace if it is installed
near an area frequently contaminated by any of
the above substances. This protects the 
 furnace from airborne contaminants. To ensure
that the enclosed   furnace has an
adequate supply of combustion air, vent from a
nearby uncontaminated room or from outdoors.
Refer to the   
 for details.
If the furnace is used in connection with a cooling
coil unit, install the furnace upstream or in parallel
with the cooling coil unit. Premature heat exchanger
failure will result if the cooling unit is placed ahead
of the furnace.
6

minimum cooling coil width shall not be less than
furnace width minus 1”. Additionally, a coil installed
       
furnace may be the same width as the furnace or
may be one size larger than the furnace.
 

the coil and furnace must face the same direction.
If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)

damage by vehicles.
If the furnace is installed horizontally, ensure the
access doors are not on the “up/top” or “down/
bottom” side of the furnace.

serves a separate appliance designed to burn solid
fuel.

must be downstream on the supply (positive) side
of the furnace heat exchanger.
 
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth
and level. A tight seal should be made between the
 
caulking compound or cement grout.
      
      
necessary, use an accessory subbase (see
      
details). A special accessory subbase must be

any combustible material including wood. Refer
to subbase instructions for installation details.
Follow the instructions with the subbase for proper
installation. Do not install the furnace directly on
carpeting, tile, or other combustible material other




BOTTOM
BOTTOM


-




-



-

-
-



-


POSITION* SIDES REAR FRONT BOTTOM FLUE TOP
Upflow 0" 0" 3" C0" 1"
Horizontal 6" 0" 3" C0" 6"
C = If placed on combustible floor, floor MUST be wood only.
*M VM 97 M INIM UM CLEARANCES TO COM BUSTIBLE M ATERIALS
(INCHES)
POSITION* SIDES REAR FRONT BOTTOM FLUE TOP
Counterflow 0" 0" 3" NC 0" 1"
Horizontal 6" 0" 3" C0" 6"
C = I f placed on combustible floor, floor MUST be wood only.
NC = For installation on non-combustible floors only. A combustible subbase
must be used for installations on combustible flooring.
*CVM 97 M INIM UM CLEARANCES TO COM BUSTIBLE M ATERIALS
(INCHES)




7
-
ity room) must have two ventilation openings with a total

-
ble to your model for minimum clearances to combustible
surfaces. One of the ventilation openings must be within
12 inches of the top; the other opening must be within 12
-
struction, the clearance between the door and door frame
is usually adequate to satisfy this ventilation requirement.





The following vent testing procedure is repro duced from
the American National Standard/National Standard of
Canada for Gas-Fired Central Furnaces ANSI Z21.47,
CSA-2.3 latest edition Section 1.23.1.
The following steps shall be followed with each appliance
connected to the venting system placed in operation, while
any other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the National Fuel Gas
Code, ANSI Z223.1 or the Natural Gas and Propane
Installation Code, CAN/CSA B149.1-15 and these
instructions. Determine that there is no blockage or

which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. 
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they shall operate at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
7. Test for spillage from draft hood appliances at the draft
hood relief opening after 5 minutes of main burner

8. If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with the National Fuel Gas Code ANSI
Z223.1/NFPA 54 and/or National Gas and Propane
Installation Code CAN/CSA B149.1-15.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
     
burning appliance to their previous conditions of use.
If resizing is required on any portion of the venting system,
use the appropriate table in Appendix G in the latest edi-
tion of the National Fuel Gas Code ANSI Z223.1 and/or
CAN/CSA B149.1-15 Installation Codes.
COMBUSTION & VENTILATION
AIR REQUIREMENTS
WARNING
-



Improved construction and additional insulation in build-

escape around doors and windows. These changes have
helped in reducing heating/cooling costs but have created
a problem supplying combustion and ventilation air for gas

-
es, etc.) increase the problem by starving appliances for air.
House depressurization can cause back drafting or improp-
      
building occupants to gas combustion products that could
include carbon monoxide.
If this furnace is to be installed in the same space with oth-
er gas appliances, such as a water heater, ensure there is
an adequate supply of combustion and ventilation air for
the other appliances. Refer to the latest edition of the Na-
tional Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/CSA
B149.1-15 Installation Codes or applicable provisions of the
local building codes for determining the combustion air re-
quirements for the appliances.
Most homes will require outside air be supplied to the fur-
nace area by means of ventilation grilles or ducts connect-
ing directly to the outdoors or spaces open to the outdoors
such as attics or crawl spaces.
INSTALLATION POSITIONS
This furnace may be installed in an upright position or hori-
zontal on either the left or right side panel. Do not install this
furnace on its back. For  furnaces, return air
ductwork may be attached to the side panel(s) and/or base-
pan. For   furnaces, return air ductwork
must be attached to the basepan. For both 
  furnaces, return ductwork must be at-
tached to the basepan (top end of the blower compartment).
8
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning or
death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1) Seal any unused openings in the venting system.
2) Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or the Natural Gas and Propane
Installation Code, CSA B149.1 and these instructions.
Determine that there is no blockage or restriction,
leakage, corrosion and other deficiencies which could
cause an unsafe condition.
3) As far as practical, close all building doors and windows
and all doors between the space in which the
appliance(s) connected to the venting system are located
and other spaces of the building.
4) Close fireplace dampers.
5) Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are
operating at maximum speed. Do not operate a summer
exhaust fan.
6) Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7) Test for spillage from draft hood equipped appliances at
the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8) If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or Natural Gas and Propane
Installation Code, CSA B149.1.
9) After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows, exhaust
fans, fireplace dampers and any other gas-fired burning
appliance to their previous conditions of use.
RISQUE D'INTOXICATION AU MONOXYDE DE CARBONE
Si les étapes décrites ci-dessous ne sont pas suivies pour
chacun des appareils raccordés au système de ventilation
au moment de sa mise en marche, cela peut entraîner une
intoxication au monoxyde de carbone ou la mort. Les
étapes suivantes doivent être suivies pour chacun des
appareils raccordés au système de ventilation au moment
de sa mise en marche, alors que tous les autres appareils
raccordés au système de ventilation ne sont pas en marche:
1) Sceller toutes les ouvertures inutilisées du système
de ventilation.
2) Inspecter le système de ventilation afin de vérifier si la
taille et l'inclinaison par rapport à l'horizontale sont
conformes aux exigences du National Fuel Gas Code,
ANSI Z223.1/NFPA 54 ou du Code d'installation du gaz
naturel et du propane, CSA B149.1 et à ces instructions.
Vérifier qu'il n'y a pas d'obstruction ou de restriction, de
fuite, de corrosion et d'autres problèmes qui pourraient
entraîner une situation dangereuse.
3) Si possible, fermer toutes les portes et fetres du
timent ainsi que toutes les portes séparant l'endroit
où se trouvent les appareils raccors au système de
ventilation et les autres zones du bâtiment.
4) Fermer le registre des foyers.
5) Mettre les sécheuses en marche ainsi que tous les
autres appareils qui ne sont pas raccordés au système de
ventilation. Mettre en marche tous les ventilateurs de
tirage, comme celui des hottes de cuisine et des salles de
bains, et les régler à la puissance maximale. Ne pas
mettre en marche les ventilateurs d'été.
6) Suivre les instructions d'allumage. Mettre en marche
l'appareil soumis à l'inspection. Régler le thermostat
de manière à ce que l'appareil fonctionne en continu.
7) Vérifier la présence de fuite au niveau de l'ouverture
du coupe-tirage des appareils qui en sont dotés après 5
minutes de fonctionnement du brûleur principal. Utiliser
la flamme d'une allumette ou d'une bougie.
8) Si un problème de ventilation est observé pendant
l'un des essais décrits ci-dessus, des correctifs doivent
être apportés au système de ventilation conformément
au National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou)
au Code d'installation du gaz naturel et du propane, CSA
B149.1.
9) Une fois qu'il a été déterminé que chaque appareil
raccordé au système de ventilation fonctionne
correctement au moyen des essais décrits ci-dessus,
les portes, les fenêtres, les ventilateurs, les registres
de foyer et tous les autres appareils de combustion
alimentés au gaz doivent être remis dans leur état
initial.
AVERTISSEMENT
9
NOTE: 


number of required ductwork connections. Refer to “Rec-
     
installation positions, ductwork connections, and resulting

HORIZONTAL APPLICATIONS &

2" 2" 3/8" ANGLE IRON
(3 PLACES)
X X

When installing a furnace horizontally, additional consider-
ation must be given to the following:

If suspending the furnace from rafters or joists, use 3/8”
-
lowing diagram. The length of rod will depend on the appli-
cation and the clearances necessary.
If the furnace is installed in a crawl space it must be sus-

Never install the furnace on the ground or allow it to be ex-
posed to water.

When a furnace is installed horizontally with left side down
the front cover pressure switch tube must be re-located to
the lower port of the collector box cover.
1. Remove tube from front cover pressure switch and
collector box cover.
2. Remove rubber plug from bottom collector box port
and install on top collector box port.
3. 
4. Install one end on front cover pressure switch.
5. Route tube to lower port on collector box cover and


In horizontal applications the condensate drain trap is se-
cured to the furnace side panel, suspending it below the
furnace. A minimum clearance of 5 ½” below the furnace
must be provided for the drain trap. Additionally, the appro-
priate downward piping slope must be maintained from the
drain trap to the drain location. Refer to 
 for further details. If the drain trap and drain
line will be exposed to temperatures near or below freezing,
adequate measures must be taken to prevent condensate
from freezing.

Leveling ensures proper condensate drainage from the heat

be level lengthwise from end to end. The furnace should
have a slight tilt from back to front with the access doors

The slight tilt allows the heat exchanger condensate, gener-
-
ator coil front cover.


       

        -
 
air piping to be run vertically through the side of the furnace.
      
for further detail. The standard piping connections may also
be used in these positions. Refer to   
 for details concerning the conversion

10






This furnace has provisions allowing for electrical and gas
line connections through either side panel. In horizontal ap-
plications the connections can be made either through the
“top”or “bottom” of the furnace.

A drain pan must be provided if the furnace is installed
above a conditioned area. The drain pan must cover the
entire area under the furnace (and air conditioning coil if
applicable).

Refer to 

VENT PIPE & COMBUSTION AIR PIPE
This manual will refer to the pipe that discharges products of

The pipe that supplies air for combustion to the furnace will
be referred to as the “intake” pipe or “combustion air” pipe.
-
rect vent (single pipe) or direct vent (dual pipe) appliance.

         
venting and intake pipe materials. All 90° elbows must be
medium or long radius types. A medium radius elbow should
measure ~3-1/16” minimum from the plane of one opening
to the center line of the other opening for 2” diameter pipe,
and ~4-9/16” minimum for 3” pipe.
       
-
proved vent and combustion air materials for installations in

       
instructions for installing, joining and terminating. Do not
mix materials or components of one manufacturer with ma-
terials or components of another manufacturer. Refer to the


All installations in Canada must conform to the require-
ments of CAN/CSA B149.1-15 code. All vent components,


        
must be of the same manufacturer as the vent system. For
Royal Pipe System 636; use GVS-65 Primer (Purple) and
GVS-65 PVC Solvent Cement. For IPEX System 636, use
   -
ment (Gray). For Canadian installations, ABS may be used
as a combustion air pipe only. ABS is not an approved vent
material in Canada. If ABS is used as a combustion air pipe,

instructions in the use of primer and cement. Do not use
primer and cement around potential sources of ignition. Do
not use primer or cement beyond its expiration date.
11
PVC ASTM STANDARD
SCHEDULE 40 PIPE D1785
SCHEDULE 40 CELLULAR CORE PIPE F891
SDR 21 OR 26 PIPE D2241
FITTINGS D2466
ABS
SCHEDULE 40 PIPE D1527
SCHEDULE 40 CELLULAR CORE PIPE F628
FITTINGS D2468
CPVC
SCHEDULE 40 PIPE F441
SDR 21 OR 26 PIPE F442
FITTINGS F438
POLYPROPYLENE
INNOFLUE (CENTROTHERM)
POLYPRO (DURAVENT)
PRIMER & SOLVENT CEMENT
PVC PRIMER F656
CPVC PRIMER F656
PVC SOLVENT CEMENT D2564
CPVC SOLVENT CEMENT F493
ABS SOLVENT CEMENT D2235
ABS / PVC / CPVC ALL PURPOSE CEMENT (FOR PIPE &
FITTINGS OF THE SAME MATERIAL)
D2564, D2235, F493
TRANSITION CEMENT FOR ABS TO PVC or CPVC D3188
INSTALLATIONS I N CANADA
PVC & CPVC PIPE & FITTINGS
PVC & CPVC SOLVENT CEMENT
TRANSITION CEMENT
INNOFLUE (CENTROTHERM)
POLYPRO (DURAVENT)
VENTING MATERIAL REQUIREMENTS
ULC S636

This furnace is manufactured with 2” CPVC vent & intake
       

pipe, the transition from 2” to 3” should be done as close to
the furnace as possible, and only when the piping is sloped
enough to prevent condensation from collecting.
This furnace must not be connected to Type B, BW, or L
vent or vent connector, and must not be vented into mason-
ry chimney. A masonry chimney may be used as a chase or
passage way for approved venting materials providing the
masonry chimney is not also being used to vent products
of combustion. Never common vent this appliance with an-
other appliance. Never use a vent which is used by a solid
fuel appliance.
Piping may run vertically or horizontally and must be ade-
quately supported to prevent strain on joints, sagging, sepa-
ration, and detachment from the furnace. Horizontal runs of

Condensation within the furnace secondary heat exchang-
er and in the vent pipe is a normal occurrence. Vent pipe
          
downward slope toward the furnace to return condensate to
the furnace’s drain system. Condensation may also occur
in the intake pipe. This commonly takes place during the
summer months when humid air enters an intake pipe that
runs through a cool basement or other conditioned space.
If the combustion air intake pipe is to be installed above
 -
sate will be objectionable, insulating the combustion air pipe

where required. Refer to intake pipe options for using the
RF000142 kit and managing condensation.
WARNING





WARNING



WARNING




PREFERRED

12
TRANSITION NO LESS
THAN 45 DEGREES TO
HORIZONTAL PLANE TO
AVOID CREATING A WATER
TRAP IN VENT PIPING.
ACCEPTABLE

NO TRANSITION ON
HORIZONTAL PLANE,
THIS CREATES A
WATER TRAP AND

GASES

Precautions must be taken to prevent condensate from
freezing inside the vent pipe. All vent piping exposed to
       
closed cell foam. Inspect piping for leaks prior to installing
insulation.

Consult table 4 to determine what diameter piping is required
for your installation. Lengths shown in the chart apply to sin-
gle pipe & two pipe installations. In a two pipe installation the
length shown refers to only one pipe, vent or intake. Both

longest pipe must be within the limits of table 4. It is prefer-
able to up-size from 2” to 2.5” or 3” pipe if the pipe length
& elbow count are near maximum. This will help avoid nui-
sance pressure switch opening caused by prevailing winds &
sudden changes in atmospheric pressure.
1 2 3 4 5 6 7 8
 115 110 105 100 95 90 85 80
137 130 123 116 109 102 95 88
 115 110 105 100 95 90 85 80
147 140 133 126 119 112 105 98
 60 55 50 45 40 35 30 25
120 113 106 99 92 85 78 71
 40 35 30 25 20 15 10 5
144 137 130 123 116 109 102 95
 40 35 30 25 20 15 10 5
144 137 130 123 116 109 102 95
 95 90 85 80 75 70 65 60
144 137 130 123 116 109 102 95
 95 90 85 80 75 70 65 60
144 137 130 123 116 109 102 95
 60 55 50 45 40 35 30 25
120 113 106 99 92 85 78 71
 40 35 30 25 20 15 10 5
103 96 89 82 75 68 61 54



Size
Model
Number of Elbows










1. Maximum allowable limits listed on individual lengths

2. 
in length and one elbow/tee.
3. 
when determining the number of elbows in the piping
system.
4. 
diameter pipe.
5. 
Long Sweep elbows should be considered equivalent
to one 90 degree elbow.
6. One 90° elbow should be secured to the combustion
air intake connection.



The vent pipe outlet is sized to accept 2” pipe. Secure vent
        
glue. Alternately, a small section of 2” pipe may be glued
in the furnace socket and a rubber coupling installed to al-
low removal for future service. Piping should be routed in
a manner to avoid contact with refrigerant lines, metering
devices, condensate drain lines, etc. If necessary, clearanc-
          
elbows (Figure 7).
13
WARNING








If the furnace is being installed without a combustion air
pipe, a 90° elbow should be used on the combustion air
intake to guard against blockage.

intake pipe to the air intake coupling using a rubber cou-
pling supplied with the furnace. The rubber coupling may
be omitted by inverting the intake coupling and gluing pipe
directly to it. Piping may also be glued to the intake coupling
in its original position by using a plastic coupling. On coun-

intake coupling using the rubber coupling and worm gear

coupling allows service removal of air intake piping internal
to the furnace blower compartment. The combustion air in-
         
unit air intake pipe coupling.
     
coupling (Figure 9) can be secured directly to the furnace
intake coupling if condensation/rain water is a concern. If
the RF000142 is used on the combustion air inlet, it must
be installed with the arrow pointing up. It should be noted,
the combustion air will actually be moving in a direction op-
posite of the arrow on the RF000142 coupling. It must have

condensate disposal location. A loop in the drain tube can
         

is also an acceptable method of catching condensation.
          
free-draining to a proper condensate disposal location. A
loop in the drain tube can serve as a trap.
Combustion Air
Exhaust



When installing a furnace horizontally with the left side down,


to be run vertically through the side of the furnace (facing up
in horizontal left). The alternate vent location is the 3” hole
directly in line with the induced draft blower outlet.

must use the RF000142 vent drain kit. See Figures 8, 9, 10
& 11 and follow steps below.

-




WARNING


14
Insert flange. Cut 2 ½” long. RF000142

VENT-DRAIN


1. 
top the furnace.
2. Remove the internal elbow, vent pipe & gasket.
3. 

4. Remove the 3” plastic plug (in line with the inducer
outlet) and insert it in the space vacated by removal
of the internal vent pipe.
5. Install the RF000142 drain coupling with arrow facing
up, on the draft inducer outlet.
6.          
through the 3” hole and connect to RF000142 drain
coupling. Secure it with gear clamp provided.
7. 

8. Connect drain hose to the uncapped port on the
RF000142 coupling, refer to page 21, section entitled
      
Down – Alternate” for drain connection details.
When using the alternate venting location, either in a hori-
zontal left side down installation or a vertical installation us-
ing down – venting, the alternate combustion air opening
can be used. A locating dimple is located on the right side of

from the front edge of the cabinet in line with the knock out.
To use the alternate combustion air location:
1. 
from cabinet.
2. Insert the 3” cabinet plug from the drain bag assembly
in the unused combustion air hole.
3. Drill a pilot hole at the cabinet dimple (size dictated by
knockout tool used).
4. 
5.         
furnace cabinet using the self-tapping screws removed
in step 1.

Products of combustion must always be vented outside. A
vent pipe must never terminate in an attic, crawl space, or
any other part of a dwelling. Follow the vent pipe & intake
pipe termination requirements listed below as well as all ap-
plicable local, State and National codes.
All terminations (vent and/or intake) must be located at least
12” above ground level or the anticipated snow level.
All vent terminations (non-direct and direct vent) must termi-
nate at least 3 feet above any forced air inlet located within
10 feet.
The vent termination of a non-direct vent application must
terminate at least 4 feet below, 4 feet horizontally from, or
1 foot above any door, window, or gravity air inlet into any
building.
The vent termination of a direct vent application must termi-

may enter a building (door, window, or gravity air inlet).
The vent termination of vent pipe run vertically through a
roof must terminate at least 12” above the roof line (or the
anticipated snow level) and be at least 12” from any vertical
wall (including any anticipated snow build up).
A vent termination shall not terminate over public walkways
or over an area where condensate or vapor could create a
nuisance or hazard or could be detrimental to the operation
of regulators, relief valves, or other equipment.
15
Vent Pipe
Use alternate vent
& combination
air locations
Combustion Air Pipe
Field Supplied
Drain Tee on Vent Pipe
Condensate trapped
to prevent flue gas from escaping
and routed to field supplied
condensate disposal
1/4” per foot min.
slope to furnace
6’ Max.
Floor
Basement / Crawlspace
DOWN VENTING UPFLOW MODEL FURNACES ONLY
All piping and fittings must be joined per material manufacturers specifications
to prevent separation and flue gas leaks.
STRAIGHT
ELBOWS


VENT & INTAKE PIPE TERMINATIONS

16
The combustion air intake termination of a direct vent appli-
cation should not terminate in an area which is frequently
dusty or dirty.
Vent & combustion air pipes may terminate vertically
through a roof, or horizontally through an outside wall. The
combustion air intake and vent pipe terminations must be in
the same atmospheric pressure zone. Vertical vent pipe ter-

of pipes through the roof must be sealed water tight with

Horizontal vent pipe terminations should be as shown in the
        
wall and prohibit damage to piping connections, a coupling
should be installed on either side of the wall and solvent
cemented to a length of pipe connecting the two couplings.
The length of pipe should be the wall thickness plus the

outside of the wall. The wall penetration should be sealed
with silicone caulking material.
CAUTION


-
pling can be secured directly to the furnace intake coupling
if condensation is a concern. If the RF000142 is used on the
combustion air inlet, it must be installed with the arrow point-
ing up. It should be noted, the combustion air will actually be
moving in a direction opposite of the arrow on the RF000142
         
free-draining to proper condensate disposal location. A loop
in the drain tube can serve as a trap. The unused RF000142
         
pipe is also an acceptable method of catching condensa-

free-draining to proper condensate disposal location. A loop
in the drain tube can serve as a trap.
Non-Direct Vent
Vent/Flue Termination
No Terminations
Above Walkway
Non-Direct Vent
Vent/Flue Termination
Direct Vent
Vent/Flue Termination
Forced Air
Inlet
Non-Direct Vent
&
Direct Vent
Vent/Flue Terminations
Grade or Highest
Anticipated
Snow Level



or










90°
ELBOWS



17

TEE
COMBUSTION
AIR INTAKE.

COMBUSTION AIR






ELBOWS
3”-24” BETWEEN PIPES



3” MIN
12” MIN TO GRADE OR HIGHEST
ANTICIPATED SNOW LEVEL
3”MIN
24”MAX
12 M IN SEPA RAT ION


-
tically, as through a roof, or horizontally, as through an out-
side wall.


If more than one direct vent furnace is to be installed ver-
tically through a common roof top, maintain the same min-
imum clearances between the exhaust vent and air intake
terminations of adjacent units as with the exhaust vent and
air intake terminations of a single unit.
If more than one direct vent furnace is to be installed hori-
zontally through a common side wall, maintain the clearanc-

vent outlets at the same elevation and always terminate all
air intakes at the same elevation.




This kit is to be used with 2” or 3” direct vent systems. The
vent kit must terminate outside the structure and may be
installed with the intake and exhaust pipes located side-by-
side or with one pipe above the other. These kits are NOT
intended for use with single pipe (indirect vent) installations.
Refer to the directions furnished with the Side Wall Vent






For all side wall horizontally vented gas fueled equipment in-
stalled in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned
or operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above

limited to decks and porches, the following requirements

1. INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing

carbon monoxide detector with an alarm and battery

equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector
with an alarm is installed on each additional level of
the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall
be the responsibility of the property owner to secure

installation of hard wired carbon monoxide detectors.
18
a. In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space
or an attic, the hard wired carbon monoxide
detector with alarm and battery back-up may be

b. In the event that the requirements of this
subdivision can not be met at the time of
completion of installation, the owner shall have a
period of thirty (30) days to comply with the above
requirements; provided, however, that during said
thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in
accordance with the above provisions shall comply


3. 
permanently mounted to the exterior of the building at
a minimum height of eight (8) feet above grade directly
in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2)
inch in size, 

4. INSPECTION. The state or local gas inspector of the
side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a)1 through 4.
EXEMPTIONS
The following equipment is exempt from 248 CMR 5.08(2)
(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used
in whole or in part for residential purposes.
c.    
   
When the manufacturer of Product Approved side
wall horizontally vented gas equipment provides
a venting system design or venting system
components with the equipment, the instructions
provided by the manufacturer for installation of the
equipment and the venting system shall include:
1. Detailed instructions for the installation of the
venting system design or the venting system
components; and
2. A complete parts list for the venting system
design or venting system.
d.    
   
PROVIDED. When the manufacturer of a Product
Approved side wall horizontally vented gas fueled
equipment does not provide the parts for venting
the flue gases, but identifies “special venting
systems”, the following requirements shall be

1. The referenced “special venting system”
instructions shall be included with the appliance
or equipment installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions
for that system shall include a parts list and
detailed installation instructions.
e. A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design
instructions shall remain with the appliance or
equipment at the completion of the installation.
6.
#3
#1 #2
#4 #5
#6
#7 #8
#9
#10
#11
100 Degree
Elbow
Coupling





-
cy by extracting heat from the products of combustion to
the point where condensation takes place. The condensate
must be collected in the furnace drain trap and routed to
an appropriate drain location in compliance with local and
national codes.
19
Follow the bullets listed below when installing the drain

concerning furnace drain trap installation and drain hose
hook ups.
The drain trap supplied with the furnace must be
used.
The drain trap must be primed at time of installation.
The drain line between furnace and drain location
must meet local and nation codes.
The drain line between furnace and drain location
     
toward the drain.
Do not trap the drain line in any other location than
at the drain trap supplied with the furnace.
If the drain line is routed through an area which
may see temperatures near or below freezing,
precautions must be taken to prevent condensate
from freezing within the drain line.
If an air conditioning coil is installed with the furnace,
a common drain may be used. An open tee must be
installed in the drain line, near the cooling coil, to
relieve positive air pressure from the coil’s plenum.
This is necessary to prohibit any interference with
the function of the furnace’s drain trap.






All furnace models come with a factory installed drain trap.
For vertical installations, the trap will remain in the factory

the drain to exit the right side. All furnace models installed
horizontally require the trap to be relocated. Many drain
hoses have a built–in grommet which will provide a cabinet
seal when installed. See instructions below for your model
and installation position.



Drain the furnace and air conditioning coil if applicable, in
compliance with code requirements. In horizontal or coun-
-
low the drain trap to be removed for cleaning. The drain trap
must be primed before initial furnace start up. When an air
-
nace drain, it must be vented, with an open tee installed at
a height no higher than the bottom of the furnace collector
box to prevent air conditioning condensate from backing up
into the furnace if the common drain was blocked.

The trap and factory installed hoses remain as shipped.
The furnace drain may exit either the right or left side of the
furnace cabinet. Both sides of the cabinet have two .875”
diameter holes which can be used interchangeably for drain
and low voltage wiring purposes. If a higher drain exit is
needed, a .875” diameter hole may be added in the area
shown in Figure 22. Any unused cabinet opening must be
sealed. Do not allow drain hose to sag or trap water.

1. Locate and Install the 45º pipe / hose drain coupling
from the outside of the cabinet (barbed end goes in the
cabinet) through hole in the right side of the cabinet
       
screws (see Figure 23).
2. Locate the long drain hose #3 and cut at line “A” .
3. Install large end of hose #3 to trap outlet and secure
with 1.25” clamp.
4. Install smaller end of hose #3 on 45º elbow and secure
with 1” clamp.
5. Refer to Field Supplied Drain section for instructions on

Side Cut-Out
12”
3” Right side shown.
Acceptable
area for
drain hole.

Installer selects right or left side drain
and installs this hose accordingly.
Hose #1
Hose #2
45 degree
barb-pipe
adapter
45 degree
barb-pipe
adapter

20

1. Install the 45 degree pipe / hose drain coupling from
the outside of the cabinet (barbed end goes in the
cabinet) through the hole in the left side of the cabinet
       
screws (see Figure 23).
2. Locate the long drain hose #3 and cut at “B” line for a
17.5” cabinet; cut at line “C” for a 21” cabinet; do not
cut for a “D” width cabinet.
3. Install large end of hose #3 to trap outlet and secure
with 1.25” clamp.
4. Install smaller end of hose #3 on 45º elbow and secure
with 1” clamp.
5. Refer to Field Supplied Drain section for instructions on



½

Hose #11
Hose #2

1. Remove the clamps from both ends of the drain hoses.
2. Remove the two screws holding the drain trap to the
blower deck.
3. Remove the trap and two hoses from the blower deck
4. Remove the two plugs from the right side of the cabinet
and install them in the blower deck.
5. (Draining the Vent Elbow) Locate hose #2 (factory
installed) and cut 1” away from the 45 degree bend,
discard the 45 degree section. Insert hose #2 from
outside the cabinet through the cabinet drain hole

elbow with a red clamp.
6. (Draining the Collector Box) Install the non-grommet
end of hose #11 from outside the cabinet in the bottom
drain hole. Install on collector box and secure with a
silver clamp.
7. 
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws through
the large set of holes in the top mounting tabs of the
trap into the two predrilled holes in the side of the
cabinet.
8. Refer to Field Supplied Drain section for instructions on



½

     

Hose #6
Hose #5 Hose #11

1. Remove the clamps from the two drain tubes on the
trap.
2. Remove the two screws holding the drain trap to the
blower deck.
3. Remove the trap and hoses from the blower deck.
4. Remove the two plugs from the left side of the cabinet
and install them in the blower deck.
5. (Draining the Vent Elbow) Locate hose #6. Measuring

for a “D” width cabinet, 5” for a “C” width cabinet, 8 ½”
for a “B” width cabinet.
6. Remove the rubber plug from vent – drain elbow side
port. Place hose #6 on the vent – drain elbow side port
and secure with a silver clamp .
7.     




       
insertion.
8. Locate hose #5 and cut 3” from the non-grommet end.
Discard the section without the grommet.
9. Insert the cut end of tube #5 through the lower cabinet
drain hole.
10. Connect hose #6 & hose #5 using 100º elbow and
secure with two red clamps
11. (Draining the Collector Box) Remove cap from left
side collector box drain port (bottom in horizontal left
position) and install it on the right side (top) collector
box drain port.
12. Install the non-grommet end of hose #11 from outside
the cabinet in the upper drain hole. Install on collector
box and secure with a silver clamp.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52