MULTISPAN CC-515 Owner's manual

  • Hello! I'm a chat assistant and I've analyzed the provided user manual for the cryo Cooling Controller CC-515. This manual contains important information about the controller's features, settings, and installation guidelines. The document explains how to configure temperature ranges, alarm settings, and compressor relay behavior. I'm ready to answer any questions you have about the device based on this manual.
  • What is the default setting for the temperature difference to restart the compressor relay (Hysteresis)?
    What is the default setting for the time delay between compressor relay restarts?
    What to do when sensor is open?
    What is the default setting for the temperature unit?
MECHANICAL INSTALLATION
MODEL
A37mm
78mm
71mm
30mm
B
C
D
E
DIMENSIONS
3mm
A
B
SET
ENT
CC 515
E
C
D
OPERATING MANUAL
COOLING CONTROLLER
TECHNICALSPECIFICATION
CC-515
ModelModel CC-515
Display
Size (mm)
37 (H) x 78 (W) x 70 (D) mm
Power Supply
Operating
Temperature
Relative
Humidity
Panel Cutout
Input
Range
Output
30 X 71 mm
1 Relay, (NO-C-NC)
Relay For Compressor
BUZZER
230V AC,50/60Hz,Approx 3VA
-50.0° To 99.9°
C C
3 Digit 0.62” 7 Segment
RED / WHITE Display
CN
CY
Range:1Minuteto99Minute
CompressorrelayOFFTime
(Note:E1=2)
DEFAULTSETTING:4MINUTE
Range:1Minuteto99Minute
CompressorrelayONTime
(Note:E1=2)
DEFAULTSETTING:10MINUTE
RST
°
c
10A
( Resistive load )
WIRINGDIAGRAM
230V AC
50/60Hz,3VA
CC 515-B1-01
LN
!
BUZZER
NTC Sensor
-50.0°C to 99.9°C
Relay
NCC NO
-
+
NOTE
PressKeyforgo

intotheparameter
Press&to
parameter
changethe
Presskeyforexit
theprogram
from
ENT
RST
Presskeytoreset
WhenSensorisopen
ENT
RST
theAlarmRelaywhen
BuzzerwillON
continuously(Ifis1)
Alarmcondition
Occurs
IfNokeyisPressed,
Menuwill
Automatically
exitafter15SEC.
withsaving.
aL
SensoropenorBreak
Sensorisnotconnected
Temperaturevaluegoes
downto-50.0orgoesup
to99.9
1
1
1
OPN
ProcessValue
Range:-
-50.0℃to+99.9℃
2 5.0
1 0.0
S E T
PressKeyfor3Sec
f2
f3
f4
f5
f6
E1
LP
fst
dp
SetHighTemperature(HT)
ToSetControllerfor
Range:LTto99.9°
Heating&Coolingmode
C
DEFAULTSETTING:99.9°
DEFAULTSETTING:COOLING
SetLowTemperature(LT)
Range:-50.0°
CtoHT
DEFAULTSETTING:-50.0°
Range:0.1°
TemperatureDifferencetorestart
(Hysteresis)
compressorrelay
DEFAULTSETTING:3.0°
ProbeCalibration(Offset)
Range:-9.0°
DEFAULTSETTING:0.0°
Range:0to999Minute
TimeDelaybetweenCompressor
RelayRestart
DEFAULTSETTING:3MINUTE
Parameter:

CompressorRelayStatusincase
ofprobefailure
1-CompressorON,
2-CompressorPerformDutyCycle
0-CompressorOFF,
DEFAULTSETTING:2
ToSetDecimalPoint
Yes/No
DEFAULTSETTING:YES
ToLockKeypad
0:Keypadunlocked,1:KeypadLock
DEFAULTSETTING:0
TorestoreFactorysetparameter
Yes/No
DEFAULTSETTING:NO
f7
r2
TosettheAlarmDelayTime

Tochangerelaypolarity

(IFAL=1,2,3)
nO:-Temp.abovesetpointrelayon
Range:0to999Second
DEFAULTSETTING:0Second
f8
TosettheAlarmONTime

Range:0to99Minute
nC:-Temp.belowsetpointrelayon
DEFAULTSETTING:0Minute
DEFAULTSETTING:nO
TosetPassword

0:Disable,1:Enable
DEFAULTSETTING:0
PasswordisAppearbefore
programmingmenu
IfSelect1thenPasswordis39
C
C
C
to20.0°
to9.0°
C
C
C
(IFAL=1,2,3)
aL
AlarmEnable/Disable
0:AlarmRelayOFF,1:AlarmONHT,LT,OPN
DEFAULTSETTING:1
2:AlarmONHT,3:AlarmONLT
TU
ToSetTemperatureUnit
°
C/
°
F
DEFAULTSETTING:°
C
Press key
CompressorrelayOFFTime
CompressorrelayONTime
(Note:E1=2)
(Note:E1=2)
Range:1Minuteto99Minute
Range:1Minuteto99Minute
DEFAULTSETTING:4MINUTE
DEFAULTSETTING:10MINUTE
OPN
SensoropenorBreak
Sensorisnotconnected
Temperaturevaluegoesdown
to-50orgoesupto99.9
ManualMode
FactorySetData
Hysteresis
TimeDelay
DefrostFrequency
DefrostTime
SetLowerLimit
SetHigherLimit
Offset
Open
Parameter
(SLL)
(SHL)
WarningGuidelines
InstallationGuidelines
1)Topreventtheriskofelectricshockpower
supplytotheequipmentmustbekeptOFFwhile
doingthewiringarrangement.Donottouchthe
terminalswhilepowerisbeingsupplied.
2)Toreduceelectromagneticinterference,use
wirewithadequateratingandtwistsofthesame
ofequalsizeshallbemadewithshortest
connection.
3)Cableusedforconnectiontopower
source,musthaveacrosssectionof1mm
orgreater.Thesewiresshouldhave
insulationscapacitymadeofatleast1.5kV.
3)Cableusedforconnectiontopower
source,musthaveacrosssectionof1mm
orgreater.Thesewiresshouldhave
insulationscapacitymadeofatleast1.5kV.
3.0
0min
0hours
0min
-50C
99.9C
0.0C
OFF
°
°
°
4)Whenextendingthethermocouplelead
wires,alwaysusethermocouple
compensationwiresforwiringfortheRTD
type,useawiringmaterialwithasmall
leadresistance(5Ωmaxperline)andno
resistancedifferentialsamongthree
wiresshouldbepresent.
5)Abetteranti-noiseeffectcanbeexpected
byusingstandardpowersupplycable
fortheinstrument.
2
1)Thisequipment,beingbuilt-in-type,
normallybecomesapartofmaincontrol
panelandsuchincasetheterminalsdo
notremainaccessibletotheenduser
afterinstallationandinternalwiring.
2)Donotallowpiecesofmetal,wireclippings,
orfinemetallicfillingsfrominstallationto
entertheproductorelseitmayleadtoa
safetyhazardthatmayinturnendangerlife
orcauseelectricalshocktotheoperator.
3)Circuitbreakerormainsswitchmustbe
installedbetweenpowersourceand
supplyterminaltofacilitatepower‘ON’
or‘OFF’function.Howeverthismains
switchorcircuitbreakermustbeinstalled
atconvenientplacenormallyaccessible
totheoperator.
4)Useandstoretheinstrumentwithinthe
specifiedambienttemperatureandhumidity
rangesasmentionedinthismanual.
3
0min
0hours
0min
-50C
99C
0C
OFF
°
°
°
69
and
1)Preparethepanelcutoutwithproper
dimensionsasshowabove.
2)Fittheunitintothepanelwiththehelpof
clampgiven.
3)Theequipmentinitsinstalledstatemust
notcomeincloseproximitytoanyheating
source,causticvapors,oilssteam,orother
unwantedprocessbyproducts.
4)Usethespecifiedsizeofcrimpterminal
(M3.5screws)towiretheterminalblock.
Tighteningthescrewsontheterminalblock
usingthetighteningtorqueoftherangeof
1.2N.m.
5)Donotconnectanythingtounusedterminals.

Maintenance
1)Theequipmentshouldbecleanedregularly
toavoidblockageofventilatingparts.
2)Cleantheequipmentwithacleansoftcloth.
Donotuseisopropylalcoholoranyother
cleaningagent.
3)Fusibleresistormustnotbereplacedby
operator.
MechanicalInstallationGuideline
WIRINGDIAGRAM
CC 515-B1-01
OPERATING MANUAL
COOLING CONTROLLER
CC-515
FactorySetData
Hysteresis
Parameter
3.0
3min
0Min
0Sec
-50.0C
99.9C
0.0C
DutyCycle DutyCycle
°
°
°
3
3min
0Min
0Sec
-50C
99C
0C
°
°
°
1)Preparethepanelcutoutwithproper
dimensionsasshowabove.
2)Fittheunitintothepanelwiththehelpof
clampgiven.
3)Theequipmentinitsinstalledstatemust
notcomeincloseproximitytoanyheating
source,causticvapors,oilssteam,orother
unwantedprocessbyproducts.
4)Usethespecifiedsizeofcrimpterminal
(M3.5screws)towiretheterminalblock.
Tighteningthescrewsontheterminalblock
usingthetighteningtorqueoftherangeof
1.2N.m.
5)Donotconnectanythingtounusedterminals.

MechanicalInstallationGuideline
InstallationGuidelines
1)Thisequipment,being
built-in-type,
normallybecomesapart
ofmaincontrolpaneland
suchincasetheterminals
donotremainaccessible
totheenduserafter
installationandinternal
wiring.
Maintenance
1)Theequipmentshouldbe
cleanedregularlytoavoid
blockageofventilatingparts.
2)Cleantheequipmentwitha
cleansoftcloth.Donotuse
isopropylalcoholoranyother
cleaningagent.
3)Fusibleresistormustnotbe
replacedbyoperator.
WarningGuidelines
SafetyPrecautions
Allsafetyrelatedcodifications,
symbolsandinstructionsthatappear
inthisoperatingmanualoronthe
equipmentmustbestrictlyfollowed
toensurethesafetyoftheoperating
personnelaswellastheinstrument.
Ifalltheequipmentisnothandledin
amannerspecifiedbythe
manufacturer,itmightimpairthe
protectionprovidedbythe
equipment.
=>Readcompleteinstructions
priortoinstallationand
operationoftheunit.
WARNING:Riskofelectricshock.
Productimprovementandupgradeisaconstantprocedure.
Soformoreupdatedoperatinginformationandsupport,
Pleasecontactourhelpline:+91-9978991483/81or
Emailat[email protected]Ver:2208
A brand by
Temperature & Humidity Controllers
Designed for Refrigeration & HVAC
A wide range of controllers for
managing various refrigeration applications.
www.multispanindia.com
1)Topreventtheriskofelectricshock
powersupplytotheequipment
mustbekeptOFFwhiledoingthe
wiringarrangement.Donottouch
theterminalswhilepowerisbeing
supplied.
2)Toreduceelectromagnetic
interference,usewirewith
adequateratingandtwistsofthe
sameofequalsizeshallbemade
withshortestconnection.
2)Donotallowpiecesof
metal,wireclippings,or
finemetallicfillingsfrom
installationtoenterthe
productorelseitmaylead
toasafetyhazardthatmay
inturnendangerlifeor
causeelectricalshockto
theoperator.
3)Circuitbreakerormains
switchmustbeinstalled
betweenpowersourceand
supplyterminaltofacilitate
power‘ON’or‘OFF’
function.Howeverthis
mainsswitchorcircuit
breakermustbeinstalled
atconvenientplace
normallyaccessibleto
theoperator.
4)Useandstorethe
instrumentwithinthe
specifiedambient
temperatureandhumidity
rangesasmentionedin
thismanual.
Open
Offset
SetHigherLimit
SetLowerLimit
AlarmONTime
AlarmDelayTime
TimeDelay
ManualMode
If+keypressedfor3sec,
Therelaygoesinmanual
Defrostmodeanddisplay
shows“OFF”message.
Pressandhold+key
toturnonrelay.
3)Cableusedforconnectionto
powersource,musthaveacross
sectionof1mmorgreater.
Thesewiresshouldhaveinsulations
capacitymadeofatleast1.5kV.
4)Whenextendingthethermocouple
leadwires,alwaysusethermocouple
compensationwiresforwiringforthe
RTDtype,useawiringmaterialwitha
smallleadresistance(5Ωmaxperline)
andnoresistancedifferentialsamong
threewiresshouldbepresent.
5)Abetteranti-noiseeffectcanbe
expectedbyusingstandardpower
supplycablefortheinstrument.
Setpoint,DPselectionandTemperaturewillnot
change,Whenyourestorethefactorydata.
230V AC
50/60Hz,3VA
LN
!
BUZZER
NTC Sensor
-50.0°C to 99.9°C
Relay
NCC NO -
+
/