Regulus UR1 Controller Owner's manual

Type
Owner's manual

This manual is also suitable for

Regulus UR1 Controller

The Regulus UR1 Controller is an analog differential controller that can be used to switch a circulation pump depending on the adjustable temperature difference. It can also be used as a simple controller for solar thermal heating of domestic hot water (DHW), pools, thermal stores, and other applications.

The UR1 Controller is designed for indoor installation only, in dry and frost-free rooms. It features a front panel with LED indicators for power and pump status, as well as a trimmer to set the temperature difference between two temperature sensors.

The UR1 Controller comes with two PT1000 temperature sensors, which should be placed in sheaths or T/X-pieces at the outlet of the last solar collector (for solar thermal heating applications) or in sheaths near the heat exchanger, in the lower part of a storage water heater, or at the inlet of pool water into a heat exchanger (for other applications).

Regulus UR1 Controller

The Regulus UR1 Controller is an analog differential controller that can be used to switch a circulation pump depending on the adjustable temperature difference. It can also be used as a simple controller for solar thermal heating of domestic hot water (DHW), pools, thermal stores, and other applications.

The UR1 Controller is designed for indoor installation only, in dry and frost-free rooms. It features a front panel with LED indicators for power and pump status, as well as a trimmer to set the temperature difference between two temperature sensors.

The UR1 Controller comes with two PT1000 temperature sensors, which should be placed in sheaths or T/X-pieces at the outlet of the last solar collector (for solar thermal heating applications) or in sheaths near the heat exchanger, in the lower part of a storage water heater, or at the inlet of pool water into a heat exchanger (for other applications).

UR1 A-DT Analog Differential Controller
EN
v. 1.1
Installation and Operation Manual
2
R
E
G
ULU
S
-
C
ontroller UR1 A-DT - www.re
g
ulus.e
u
UR1 A-DT Analog Differential Controller
The Controller switches a circulation pump depending on the adjustable temperature difference. It can be also
used as a simple controller for solar thermal heating of DHW, pool, thermal store etc.
The Controller is designed for indoor installation only, for dry and frost-free rooms. When installed
into other environments, esp. outdoors, defects that appear are not covered by warranty.
Front panel
„Power“ - green LED
(on=the appliance is
energized at 230V)
„Pump“ - yellow LED
(on=the pump is running)
Controller wiring and sensor locations
The electric installation shall respect valid rules! Electric wiring may be done by a qualied person
only!
Temperature sensor for a solar collector shall be placed into a sheath or into a sheath of a T/X-piece
at the outlet from the last collector.
Temperature sensor for a heat-consuming appliance shall be placed in a sheath near the heat
exchanger, in the lower part of a storage water heater (thermal store), or at the inlet of pool water into
a heat exchanger. The min. distance of 100 mm from an electric heating element shall be respected.
Never place the sensor above an electric heating element.
Use a twisted cable, 2×1 mm2, unshielded, separate from power conductors. Its max. length is 100 m.
Try to minimize the number of wiring boxes and terminal boards.
connection length: up to 25 m, cross section area: 0,25 mm2
connection length: up to 50 m, cross section area: 0,5 mm2
connection length: up to 100 m, cross section area: 1,0 mm2
The thermal and mechanical resistance of the conductor used shall correspond to the environment
it runs through.
The temperature sensors are of PT1000 type, with resistance of 1kΩ at 0 °C, 3850 ppm / °C.
Sensors shall be always connected.
Fuse Jumper Relay
15 K 8 K
T1 T2
PE
Examples of hydraulic connection
Thermal Store
heated from a boiler
Heating circuit
pre-feed
Heat exchange
between 2 tanks
DHW heating
control
T1
T2 T1 T2
T1 T2
T1
T2
3
R
E
G
ULU
S
-
C
ontroller UR1 A-DT - www.re
g
ulus.e
u
Electricity data
Controller
Power supply 2 AC 230 V
Nominal voltage 230 VAC
Nominal current 16 mA
Operating temperature 5 to 40 °C non-condensing
Storage temperature 0 to 60 °C
Mounting on a wall
Fuse 200 mA / 250 V
IP rating IP 20
Max. conductor cross section area 1,5 mm2
Relay
Max. voltage 250 VAC, 30 VDC (min. 100 mA / 5 VDC)
Max. current 5 A
Load resistive
Terminal marking
PE – power supply
T1 – temperature sensor
T2 – temperature sensor
Rele – relay terminals
Jumper - when closed, the relay is permanently closed disregarded of sensor temperatures
(however the sensors need to be connected).
Trimmer – to set temperature difference between T1 and T2 temperature sensors. At the counterclockwise
end stop, the difference is 15 K, at the clockwise end stop, the difference is 8 K. The pump is switched
off as soon as the temperature difference between the sensors drops below 4 K.
Relay
Power supply Pump
12
/
2
0
14
REGULUS spol. s r.o.
Do Koutů 1897/3 http://www.regulus.eu
143 00 Praha 4 E-mail: [email protected]
CZECH REPUBLIC
WARRANTY CONDITIONS
- electrical surge or insufcient voltage from the mains
- improper handling
- tampering by a third person
- improper installation manner
- improper stocking and installation place
- natural disaster
Date of Purchase
COMMISSIONING NOTE
Company:
Technician:
Date:
1. When claiming warranty, this Warranty Certicate must be submitted
together with the purchase receipt.
2. The warranty is valid only when the technical conditions set by the
Manufacturer, installation manual and instructions in the documentation
and on the product itself are maintained.
3. The product will be installed and commissioned by a competent person.
4. The warranty does not cover defects caused by external conditions or
improper operation conditions, defects caused by usual wear and tear,
further when the product is not used in compliance with its purpose and
when the defect was caused by:
THE SELLER GRANTS THE BUYER (CONSUMER) A GUARANTEE PERIOD
OF 24 MONTHS
User:
Signature:
UR1 A-DT Analog Differential Controller
WARRANTY CERTIFICATE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Regulus UR1 Controller Owner's manual

Type
Owner's manual
This manual is also suitable for

Regulus UR1 Controller

The Regulus UR1 Controller is an analog differential controller that can be used to switch a circulation pump depending on the adjustable temperature difference. It can also be used as a simple controller for solar thermal heating of domestic hot water (DHW), pools, thermal stores, and other applications.

The UR1 Controller is designed for indoor installation only, in dry and frost-free rooms. It features a front panel with LED indicators for power and pump status, as well as a trimmer to set the temperature difference between two temperature sensors.

The UR1 Controller comes with two PT1000 temperature sensors, which should be placed in sheaths or T/X-pieces at the outlet of the last solar collector (for solar thermal heating applications) or in sheaths near the heat exchanger, in the lower part of a storage water heater, or at the inlet of pool water into a heat exchanger (for other applications).