Johnson Controls DSH048B Installation Operation & Maintenance

Type
Installation Operation & Maintenance
AIRSIDE ECONOMIZER KIT
MODELS DSH/DSV
AIR COOLED AIR CONDITIONING UNITS
R-410A
STYLE B
Issue Date:
April 2015
INDOOR PACKAGED EQUIPMENT
INSTALLATION, OPERATION, MAINTENANCE
NEW RELEASE Form 145.10-IOM3 (415)
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDLINES
This equipment is a relatively complicated apparatus.
During installation, operation, maintenance or service,
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants
, oils,
materials under pressure, rotating components and
both high and low voltage. Each of these items has the
potential, if misused or handled improperly, to cause
bodily injury or death. It is the obligation and respon-
sibilty of operating/service personnel to identify and
recognize these inherent hazards, protects
themselves, and proceed safely in completing their
tasks. Failure to comply with any of these
requirements could result in serious damage to the
equipment and the property in which it is situated, as
well as sever personal injury or death to themselves
and people at the site.
This document is intended for use by owner-authorized
operating/service personnel. It is expected that this
individual possesses independent training that will en-
able them to perform their assigned tasks properly and
safely. It is essential that, prior to performing any task
on this equipment, this individual shall have read and
understood this document and any referenced materials.
This individual shall also be familiar with and comply with
all applicable governmental standards and regulations
pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard.
DANGER indicates an imminently haz-
ardous situation which, if not avoided,
will result in death or serious injury.
WARNING indicates a potentially haz-
ardous situation which, if not avoided,
could result in death or serious injury.
CAUTION identifies a hazard which
could lead to damage to the machine,
damage to other equipment and/or
environmental pollution. Usually and
instruction will be given, together with a
brief explanation.
NOTE is used to highlight additional in-
formation which may be helpful to you.
All wiring must be in accordance with published specifications and must be performed ONLY by
qualified service personnel. Johnson Controls will not be responsible for damages/problems
resulting from improper connections to the controls or application of improper control signals.
Failure to follow this will void the manufacturer’s warranty and cause serious damage to property or
injury to persons.
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls policy for
continuous product improvement, the information
contained in this document is subject to change
without notice. While Johnson Controls makes no
commitment to up-date or provide current
information automatically to the manual owner, that
information, if applicable, can be obtained by
contacting the nearest Johnson Controls service
office.
It is the responsibility of operating/service personnel
as to the applicability of these documents to the
equipment in question. If there is any question in the
mind of operating/service personnel as to the
applicability of these documents, then, prior to
working on the equipment, they should verify with
the owner whether the equipment has been modified
and if current literature is available.
TABLE OF CONTENTS
1 …… Installation
2 ……Mixing Box Dimensions &
Component Layout
3 …….Interconnection Harness
4 ……Damper & Actuator Set-up
5 …. Wiring Schematics
6 …. Sequence of Operation
7 …. Parameter Table
PRIOR TO INSTALLING OR SERVICING THE UNIT, LOCK ALL ELECTRICAL POWER SUPPLY
SWITCHES IN THE OFF POSTION. FAILURE TO DISCONNECT POWER SUPPLY MAY RESULT IN
ELECTRICAL SHOCK OR EVEN DEATH.
1. INSTALLATION
Horizontal/Vertical Economizers
1. Attach mixing box to unit evaporator return,
using the metal securing strip provided.
Fasteners may also be used around the
perimeter of the mixing box, at the location of
the filter frame, for additional security. This is
intended to connect the units, and not to support
the full weight of the economizer mixing box
ADDITIONAL FIELD SUPPORT IS REQUIRED.
This may be from the ceiling, or from beneath
the unit.
2. Determine which inlet will be outside air, and
which will be return air. If the normal
open/closed position of the dampers needs to be
reversed, remove the actuator, reset the damper
positions so that the outside air damper is
closed and the return air damper is fully open.
Adjust the linkage rod to these normal positions,
and secure. Reattach the actuator so that it is
rotating in the appropriate direction.
3. The module is connected to the unit wiring via a
2-part molex wiring harness. Minimal field
rewiring of the unit is required in order to
accommodate the Air-Side Economizer option.
Refer to Section 6 for detailed instructions.
Connect the wiring harness to the
microprocessor board as indicated in Section 4
Wiring Harness Installation.
4. With the power to the module, the actuator
springs will wind and lock. The enthalpy
changeover setting may be altered, and the
outside air damper minimum position adjusted.
See the attached Honeywell JADE W7220
Economizer Controller Manual for details.
NOTE: Jade will be in the "set up" mode for the
first 60 minutes after powered. If a sensor for
Outdoor Air (OA) is disconnected during the set
up mode, the Jade will not alarm that failure. The
Mixed Air (MA) sensor is a system "critical"
sensor, if the MA sensor is removed during the
set up mode, the Jade will alarm. After 60
minutes the Jade controller will change to
operation mode and all components removed or
failed will alarm in the operation mode.
Prior to installing or servicing the
unit, lock all electrical power supply
switches in the OFF position. Failure
to disconnect power supply may
result in electrical shock or even
death.
Additional field support of the mixing
box is required. Failure to provide
adequate support for the unit may
result in injury or even death.
Exercise care when working around
the sharp metal edges of door panels
or flanges. These edges are sharp
and can cause injury.
2. VERTICAL MIXING BOX DIMENSIONS
Vertical Unit
Model Number
Economizer
Model Number
MIXING BOX DIM'N
DAMPER
DIM'N
CONTROL
MODULE
A
B
C
D
F
G
DSV060B
VASE-060B-1
49.00
27.75
24.00
40.00
8.00
15.00
DSV096B/120B
VASE-120B-1
66.50
36.25
26.50
58.00
8.00
15.00
DSV144B/180B
VASE-180B-1
78.00
35.75
28.50
70.00
8.00
15.00
DSV240B
VASE-240B-1
86.00
41.25
34.00
78.00
8.00
15.00
DSV300B
VASE-300B-1
104.00
45.00
34.00
90.00
8.00
15.00
3. HORIZONTAL MIXING BOX DIMENSIONS
Horizontal Unit
Model Number
Economizer
Model Number
MIXING BOX DIM'N
DAMPER
DIM'N
CONTROL
MODULE
A
B
C
D
F
G
DSH024B/036B
HASE-036B-SF
26.06
23.32
23.44
17.00
8.00
15.00
DSH048B/060B
HASE-060B-SF
29.68
23.44
30.44
24.00
8.00
15.00
DSH096B/120B
HASE-100B-SF
33.63
25.25
33.63
28.00
8.00
15.00
Horizontal Unit
Model Number
Economizer
Model Number
MIXING BOX DIM'N
DAMPER
DIM'N
CONTROL
MODULE
A
B
C
D
F
G
DSH024B/036B
HASE-036B-BF
26.06
23.32
23.44
17.00
8.00
15.00
DSH048B/060B
HASE-060B-BF
29.68
23.44
30.44
24.00
8.00
15.00
DSH096B/120B
HASE-100B-BF
33.63
25.25
33.63
28.00
8.00
15.00
STANDARD SIDE & FRONT
DAMPER ARRANGEMENT
OPTIONAL BOTTOM & FRONT
DAMPER ARRANGEMENT
4. WIRING HARNESS INSTALLATION -
AIRSIDE ECONOMIZER TO UNIT
CONNECTION
Each Air-Side Economizer is shipped complete with
a two-part wiring harness. The terminated end of the
wiring harness that is shipped in a package with the
economizer must be field wired into microprocessor
board. The second part of the harness assembly is
pre-wired into the Economizer module panel. The
two parts of the harness are connected together by
integrated polarized molex plugs.
For split unit applications (horizontal units only)
the harness will need to be extended in the field
using 18 gauge wire.
Locate the Mixed Air sensor (C7250A1001) inside
supply discharge duct. Wire other end into the MAT
terminals of the W7220 module.
Locate the Outdoor Air Temp/Humidity Sensor
(C7400S1000) in the outdoor air duct. This will be
wired into the S-BUS terminals of W7220 module.
All Models
6 Pin Molex Plug
Pin #
Color
Connection ID
1
Yellow/Red
Y-OUT
2
Yellow/Red
ECON
3
Gray/Red
G-OUT
4
Pink
OCCUPIED
5
White
COMMON
Installing Harness (Vertical Units):
1) Working from the side access door, feed the
loose pre-terminated ends of the harness in
through the back of the low voltage section of
the electrical box, through the bushed hole.
2) Connect the harness terminations to the
microprocessor board economizer harness
terminations (Y-Out, G-Out, ECON, and
OCCUPIED), as shown in the electrical
schematic.
3) Connect the WHITE COMMON wire from the
harness onto the Common tab on the
microprocessor board, using the provided tab
adapter, as shown in the electrical schematic.
4) Inside the condenser section secure the harness
to the side of the blower housing using the
supplied cable clips. Ensure that the harness is
routed clear of moving parts and sharp edges,
and that there are no loose wires that can be
pulled into the blower inlet. Coil excess wire
length, and secure with cable clips (see photo).
5) The plug end of the harness should terminate
inside the rear corner post. The economizer half
of the harness will enter through the knockout
hole in this area. Ensure the harness is secured
on the outside of the unit using the cable clips
provided.
Installing Harness (Horizontal Units):
1) Working from the evaporator blower access
door, feed the loose pre-terminated ends of the
harness along the base of the unit towards the
right end and back out, using the low voltage
electrical conduit, to the condenser section and
into the condenser electrical panel. For split
unit applications the harness will need to be
extended in the field using 18 gauge wire.
Ensure the cable is protected from damage and
the wiring meets all local code requirements.
2) Inside the condenser electrical box, connect the
harness terminations to the microprocessor
board economizer harness terminations (Y-Out,
G-Out, ECON, and OCCUPIED), as shown in
the electrical schematic. Note the Occupied
terminal is not being used in the standard factory
setup and has been provided if required in the
field.
3) Connect the WHITE COMMON wire from the
harness onto the Common tab on the
microprocessor board, using the provided tab
adapter, as shown in the electrical schematic.
4) Inside the blower section of the evaporator unit
secure the harness along base towards the left
corner post using the supplied cable clips.
Ensure that the harness is routed clear of
moving parts and sharp edges, and that there
are no loose wires that can be pulled into the
blower inlet. Coil excess wire length, and secure
with cable clips (see photo).
5) The plug end of the harness should terminate
inside the bottom left corner post. The
economizer half of the harness will enter through
the knockout hole in this area. Use a punch out
tool or screwdriver. Feed the plug end harness
through and connect to the other half of the
economizer harness. Ensure the harness is
secured on the outside of the unit using the
cable clips provided.
5. ECONOMIZER DAMPER & ACTUATOR SETUP (VERTICAL SETUP)
Installed Harness
VERTICAL ECONOMIZER
HORIZONTAL ECONOMIZER
SINGLE STAGE ECONOMIZER WIRING SCHEMATIC
DUAL STAGE ECONOMIZER WIRING SCHEMATIC
6. SEQUENCE OF OPERATION
NOTE: Refer to the ‘Honeywell JADE (W7220)
ECONOMIZER MODULE’ manual accompanied
with this kit for additional information regarding
additional sensors, enthalpy settings and alarms
Modulating Economizer with Typical Electro -
Mechanical Thermostat
The Honeywell W7220 module, ML series actuators,
JCI damper sections, and factory wiring harness
comprise an integrated economizer. These
economizers are used to provide ventilation and free
cooling for the JCI Series of vertical and horizontal
air handlers.
The Honeywell W7220 can accept inputs from
additional optional sensors (field provided), including
a return-air enthalpy sensor (for differential enthalpy
control) or a CO
2
sensor for Indoor Air quality
strategies.
The economizer module setup is done through the
LCD keypad display. For more information regarding
setup and other features, consult the Honeywell
JADE - W7220 Economizer Controller Manual
included with the Economizer kit.
Powering the Thermostat (24vac) -
Power to the electromechanical thermostat is
provided from R terminal of the JCI unit’s low voltage
terminal strip. Electromechanical thermostats do not
require a 24vac common connection.
Powering the W7220 (24vac) -
The W7220 is powered from the JCI unit’s
microprocessor board at the G-Out pin whenever the
fan of the evaporator section is operating. To ensure
that the W7220 is continuously powered, the fan
switch on the thermostat sub-base should be left on
at all times.
High Enthalpy Sequence:
Enthalpy sensor C7400S on all units should be
located in the outdoor air duct. When the outside air
enthalpy exceeds the enthalpy set-point, the
economizer W7220 module Y1-In and Y1-Out
terminals are closed and economizer will be forced
into the minimum damper position setting. The JCI
unit’s microprocessor board will control cooling
requirements.
Low Enthalpy Sequence:
When the outside air enthalpy is below the enthalpy
set-point, W7220 economizer Y1-In and Y1-Out
terminals are opened and free cooling is activated.
The JCI unit’s microprocessor board turns off
compressor operation.
Damper Modulation:
On all JCI units' the C7250A temperature sensor
should be located in the supply discharge air duct.
Locating the sensor in the discharge air provides
effective 'low-limit' sensing and control. The outside-
air damper remains at minimum position if the
discharge air temperature is below 50
0
F or 10
0
C. If
the discharge air temperature is between 50
0
to 56
0
F (10
0
to 13.3
0
C) the outside air damper will
modulate between minimum position and fully open.
Above 56
0
F (13.3
0
C) the outside air damper will
remain in the fully open position.
Occupied:
The OCCUPIED harness terminal is not connected
to the economizer OCC terminal in the economizer
box. It has been provided if site conditions require
field connection of an Occupied function. Consult the
Honeywell JADE - W7220 Economizer Controller
Manual for more information.
7. PARAMETER TABLES
Menu Parameter
Parameter
Default Value
Parameter Range Notes
STATUS ECON AVAIL NO YES/NO YES = economi zing a vai l a ble; the s ystem can use Outdoor Ai r for
free cooling when required.
ECONOMIZING NO YES/NO YES = Outdoor Ai r bei ng us ed for 1st s tage cool i ng.
OCCUPIED NO YES/NO YES = OCC si gna l recei ved from space thermos ta t or uni ta ry
controller.
YES = 24 Vac on termi nal OCC
No = 0 Va c on termina l OCC.
COOL Y1-IN OFF ON/OFF Y1-I signa l from s pace thermos ta t or uni ta ry control l er for
cooling s ta ge 1.
ON = 24 Va c on term Y1-I
OFF = 0 Va c on term Y1-I
COOL Y1-OUT OFF ON/OFF Cool Stage 1 Relay Output to mechani ca l cool i ng (Y1-OUT
termina l ).
MA TEMP _ _._ ºF -40 to 150 ºF Di s pl a ys value of mea s ured mi xed air from MAT s ens or.
Di s pl a ys --.-°F if not connected, s hort, or out- of-ra nge.
DA TEMP _ _._ ºF -40 to 150 ºF Di s pl a ys when Dis charge Ai r Syl k Bus s ensor is connected a nd di s pl a ys
mea s ured di s charge a i r te mperature. Di s pl a ys --.-°F
OA TEMP _ _._ ºF -40 to 140 ºF Displays mea s ured val ue of outdoor air temperature.
Di s pl a ys --°F
OA HUM _ _ % 0 to 100% Di s pl a ys mea s ured val ue of outdoor humi dity from QA Sylkbus s ens or.
Di s pl a ys --%
DAMPER OUT 2.0V 2.0 to 10.0 V Di s pl a ys output voltage or pos i ti on to the da mper a ctuator.
ACT POS n/a 0 to 100% Di s pl a ys a ctua l pos iti on of a ctua tor
ACT COUNT n/a 1 to 65,535 Di s pl a ys number of times a ctuator ha s cycled. 1 Cycle equals
the s um of 180° of movement in a ny di rection.
ACTUATOR OK/Al a rm (on Di s pl a ys Error i f vol ta ge or torque is below a ctuator ra nge
Alarm menu)
SETPOINTS MAT SET 53ºF 38 to 70 ºF; The economi zer will modul a te the OA dampe r to ma i nta i n the
increment by 1 mi xed air tempera ture a t the s etpoint.
LOW T LOCK 32ºF -45 to 80 ºF; Setpoi nt determi nes outdoor te mperature when the mecha ni cal
increment by 1 cool i ng cannot be turned on. Commonl y referred to a s the
Compres s or l ockout. At or bel ow the setpoint the Y1-O a nd
Y2-O wi l l not be energize d on the control l er.
DRYBLB SET 63ºF 48 to 80 ºF; Setpoint determi nes where the economizer wi l l a s s ume outdoor
increment by 1 a i r temperature i s good for free cool i ng; e.g.; a t 63 ºF s etpoint
uni t will economizer a t 62 ºF and be l ow a nd not economi ze a t
64 ºF and above. There i s a a 2 ºF deadba nd.
ENTH CURVE ES3 ES1, ES2, ES3, Entha l py boundary “curves for economizi ng us ing s ingle
ES4, or ES5 entha l py.
MIN POS 2.8 V 2 to 10 Vdc Displ a ys ONLY if a CO2 sens or is NOT connected. Wi th 2-s peed
fa n uni ts MIN POS L (l ow s peed fa n) a nd MIN POS H (hi gh
spe ed fan) s ettings a re requi red. Defa ult for MIN POS L i s 3.2V
and MIN POS H i s 2.8V.
SYSTEM INSTALL 01/01/11 Di s play order = MM/DD/YY
SETUP Setti ng order = DD, MM, then YY
UNITS DEG ºF ºF or ºC Sets economi zer controller i n degrees Fa hrenhei t or Cel s i us .
EQUIPMENT CONV CONV CONV = conventi ona l .
HP HP O/B = Ena bl es Heat Pump mode
OCC INPUT INPUT or When us ing a s etba ck thermos ta t with occupa ncy out (24 Vac),
ALWAYS the 24 Va c is i nput “INPUT” to the OCC termi nal. If no
occupa ncy output from the thermos tat then change program to
“ALWAYS” OR a dd a jumper from termi nal R to OCC terminal.
FACTORY DEFAULT NO YES/NO Res ets a l l s et points to factory defa ults when s et to YES. LCD
will briefly flas h YES and cha nge to NO but a l l parameters wi l l
cha nge to factory default val ues .
ADVANCED MA LO SET 45ºF 35 to 55 ºF; Temp to a cti vate Freeze Protecti on (clos e da mper or modul a te to
SETUP increment by 1º MIN POS i f temp fa l l s bel ow s et val ue)
SD DMPR POS CLO CLO Indi ca tes s hutdown s i gna l from spa ce thermos tat or unitary
OPN controller. When control l er recei ves 24 Va c i nput on the SD
termi na l in conventi ona l mode, the OA da mper will open i f
programmed for OPN and OA da mper wi l l clos e if programmed
for CLO. All other control s , e.g., Y1-O, etc. wi l l shut off.
MAT T CAL 0.0 F° +/-2.5F° Al lows for the opera tor to adjus t for a n out of calibration
temperature sens or
OA T CAL 0.0 F° +/-2.5F° All ows for the opera tor to adjus t for a n out of cal i bration
temperature sens or
OA H CAL 0% RH +/-10% RH Allows for the operator to a djus t for a n out of ca l i brati on
humidity s ens or
RA T CAL 0.0 F° +/-2.5F° Allows for the operator to a djus t for a n out of ca l i brati on
temperature sens or
RA H CAL 0% RH +/-10% RH Allows for the operator to a djus t for a n out of ca l i brati on
humidity s ens or
DA T CAL 0.0 F° +/-2.5F° Allows for the operator to a djus t for a n out of ca l i brati on
temperature sens or
CHECKOUT DAMPER VMIN-HS n/a n/a Pos i ti ons da mper to VMIN pos i ti on.
DAMPER VMAX n/a n/a Pos iti ons damper to VMAX pos i ti on
DAMPER OPEN n/a n/a Pos iti ons damper to the ful l open pos i ti on
DAMPER CLOSE n/a n/a Pos iti ons damper to the ful l y clos ed pos i ti on.
CONNECT Y1-O n/a n/a Clos es the Y1-O relay (Y1-O).
P.O. Box 1592, York, Pennsylvania USA 17405-1592 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2015 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 145.10-IOM3 (415)
NEW RELEASE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Johnson Controls DSH048B Installation Operation & Maintenance

Type
Installation Operation & Maintenance

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI