AIREDALE TurboChill & TurboChill FreeCool 200kW – 1830kW Technical Manual

Category
Split-system air conditioners
Type
Technical Manual
1
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Technical Manual
Original Instructions
TurboChill™
200kW to 1700kW
Air Cooled (TCC) and FreeCool (TCF) Chiller
R134a
2Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Special Precautions
The guidance in this manual must be followed to provide safe, efcient and trouble-free operation. In addition, particular care must be
exercised regarding the special precautions listed below. Failure to properly address these critical areas could result in property damage
or loss, personal injury or death. These instructions are subject to any additional restrictive local or national codes.
Hazard Intensity Levels
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern.
5. NOTE: Indicates information that is not a safety concern but may invalidate warranty if not adhered to.
CAUTION
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance being carried out
in accordance with the recommendations provided during the warranty period. Failure to have the maintenance
procedures carried out will invalidate the warranty and any liabilities by Airedale International Air Conditioning Ltd.
When working with any air conditioning units, ensure that the electrical isolator is switched off prior to servicing or
repair work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as re alarm circuits, BMS circuits, crankcase heater
permanent supplies etc.
Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent
and trained personnel in accordance with local relevant standards and codes of practice.
These Airedale chillers use R134a refrigerant which requires careful attention to proper storage and handling
procedures in accordance with EN 378. Maximum water temperature owing through the chiller should be 40°C.
CAUTION PACEMAKER WEARERS
To avoid any risk of injury, any work to be carried out on or around the compressor and magnetic check valve should
be done with personnel that do not have pacemakers tted.
Care must be taken when working around the discharge pipe work of the unit.
High surface temperatures may exist during unit operation.
The refrigerant has a boiling point of -26°C.
Units without compressor enclosures are class A group 1 products and are only intended to be used at locations where
there is a distance greater than 30 m between the equipment and third party sensitive radio communication equipment.
****Feature is un clear on the table?! required if unit is to be shut down for winter with water still circulating
through unit. Freeze protection.This is to stop potential liquid migration.
The Pump Interlock and Flow Switch are ow proving devices, and 2 out of the 3 should be tted to any unit to
validate warranty.
The Pump Interlock and Water Flow Switch are ow proving devices, and 2 out of the 3 should be tted to any unit to
validate warranty.
Password Protection
The control system integrity shall be maintained by restricting access with a password PIN number.
When adding to an existing controls scheme, please consult Airedale Controls to ensure strategy compatibility.
Only use the SHC data when calculating uid VOLUME. Use gure for 0% concentration (100% water) when applying
Glycol Correction Factors, refer to Glycol Data.
The unit water connections are NOT designed to support external pipe work, pipe work MUST be supported
separately.
The standard installation recommendations should be adhered to. Failure to do this may invalidate the chiller warranty.
The water ow commissioning valve set is not shown in the diagram, as the valve can be tted elsewhere within the
chilled water circuit.
Full design water ow MUST be maintained at all times. Variable water volume is NOT recommended and will
invalidate warranty.
The correct operation of the ow proving device is critical if the chiller warranty is to be valid.
Failure to install both safety devices will invalidate the chiller warranty.
Do not rely solely on the BMS to protect the chiller against low ow conditions.
3
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
The unit should be lifted from the base and where possible, with all packing and protection in position. If any other type
of slinging is used, due care should be taken to ensure that the slings do not crush the casework or coil.
Do not connect any services until all anti vibration mounts have been fully adjusted.
Mountings must be adjusted incrementally in turn. Do not fully adjust 1 mount at a time as this may overload and
damage springs. Do not connect any services until all anti vibration mounts have been fully adjusted.
A fused and isolated electrical supply of the appropriate phase, frequency and voltage should be installed.
Wires should be capable of carrying the maximum load current under non-fault conditions at the stipulated voltage.
A separately fused permanent single phase and neutral supply MUST BE FITTED for the evaporator trace heating and
control circuits and for the leak detection and ventilation systems to work in the event of a leak being detected.
FAILURE to do so will INVALIDATE WARRANTY.
ALL work MUST be carried out by technically trained competent personnel.
Isolate REMOTELY the mains incoming supply to the BUSBAR chamber prior to maintenance or repair work.
ALL work MUST be carried out by technically trained competent personnel.
The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work.
If the unit is operated without water the unit will be damaged.
The L4 permanent supply also provides power to the leak detector and compressor ventilation fans.
Check phase rotation of electrical supply prior to running the compressor as it’s direction sensitive.
When the chiller has been re-started it will go through its start-up sequence. Pressing will turn the unit off.
The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work. Ensure lock off
procedures are carried out accordingly.
If inverter driven pumps are used ensured at least 5 minutes is allowed for them to discharge any electrical charge.
IMPORTANT
To change the PIN number; please contact Airedale at time of order with the preferred 4 digit number.
The equipment and system should be kept clean and free of solid, scale, corrosion and biological fouling. Failure to do so may invalidate the
warranty.
The Water Treatment Guidelines do not give exhaustive list of all the substances found in plant items produced by
Airedale and specic advice should be sought for individual items of equipment or specic applications, if required.
Lines specied on the Interconnecting Wiring diagram MUST be directly wired to the chiller to validate warranty.
2Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Warranty, Commissioning & Maintenance
As standard, Airedale guarantees all non consumable parts only for a period of 12 months, variations tailored to suit
product and application are also available; please contact Airedale for full terms and details.
To further protect your investment in Airedale products, Airedale can provide full commissioning services,
comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland).
For a free quotation contact Airedale or your local Sales Engineer.
All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water,
associated with the risk of contaminants such as Legionella.
For effective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale
recommendations.
ChillerGuard™
In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland
sites. This service will enable customers to contact a duty engineer outside normal working hours and receive
assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less.
Full details will be forwarded on acceptance of the maintenance agreement.
Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on
request.
Airedale Ltd. endeavours to ensure that the information in this document is correct and fairly stated, but none of the
statements are to be relied upon as a statement or representation of fact. Airedale Ltd does not accept liability for any
error or omission, or for any reliance placed on the information contained in this document. The development of Airedale
products and services is continuous and the information in this document may not be up to date. It is important to check
the current position with Airedale Ltd. at the address stated. This document is not part of a contract or licence unless
expressly agreed. No part of this document may be reproduced or transmitted in any form or by any means, electronic
or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other
than the purchaser’s personal use, without the express written permission of Airedale Ltd.
© 2019 Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK.
Training
As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning
Training courses, for further information please contact Airedale.
Customer Services
For further assistance, please e-mail: [email protected] or telephone:
UK Sales Enquiries + 44 (0) 113 239 1000 [email protected]
International Enquiries + 44 (0) 113 239 1000 [email protected]
Spares Hot Line + 44 (0) 113 238 7878 [email protected]
Airedale Service + 44 (0) 113 239 1000 [email protected]
Technical Support + 44 (0) 113 239 1000 [email protected]
Training Enquiries + 44 (0) 113 239 1000 [email protected]
For information, visit us at our Web Site: www.airedale.com
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance
being carried out in accordance with the recommendations provided during the warranty period.
Failure to have the maintenance procedures carried out will invalidate the warranty and any
liabilities by Airedale International Air Conditioning Ltd.
CAUTION
3
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Warranty
All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by
an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or
18 months from the date of despatch, whichever is the sooner.
Parts or Equipment supplied by Airedale for installation within the UK or for Export that are properly commissioned in
accordance with Airedale standards and specication, not commissioned by an Airedale engineer; carry a 12 month
warranty on non consumable Parts only from the date of commissioning or 18 months from the date of despatch,
whichever is the sooner.
Parts or equipment installed or commissioned not to acceptable Airedale standards or specication invalidate all
warranty.
Warranty is only valid in the event that
In the period between delivery and commissioning the equipment,
is properly protected & serviced as per the Airedale installation & maintenance manual provided
where applicable the glycol content is maintained to the correct level.
In the event of a problem being reported and once warranty is conrmed as valid under the given installation and
operating conditions, the Company will provide the appropriate warranty coverage (as detailed above) attributable to the
rectication of any affected Airedale equipment supplied (excluding costs for any specialist access or lifting equipment
that must be ordered by the customer).
Any spare part supplied by Airedale under warranty shall be warranted for the unexpired period of the warranty or 3
months from delivery, whichever period is the longer.
To be read in conjunction with the Airedale Conditions of Sale - Warranty and Warranty Procedure, available upon
request.
Procedure
When a component part fails, a replacement part should be obtained through our Spares department. If the part is
considered to be under warranty, the following details are required to process this requirement. Full description of part
required, including Airedale’s part number, if known. The original equipment serial number. An appropriate purchase
order number.
A spares order will be raised under our warranty system and the replacement part will be despatched, usually within 24
hours should they be in stock. When replaced, the faulty part must be returned to Airedale with a suitably completed and
securely attached “Faulty Component Return” (FCR) tag. FCR tags are available from Airedale and supplied with each
Warranty order.
On receipt of the faulty part, suitably tagged, Airedale will pass to its Warranty department, where it will be fully
inspected and tested in order to identify the reason for failure, identifying at the same time whether warranty is justied
or not.
On completion of the investigation of the returned part, a full “Report on Goods Returned” will be issued. On occasion
the release of this complete report may be delayed as component manufacturers become involved in the investigation.
When warranty is allowed, a credit against the Warranty invoice will be raised. Should warranty be refused the Warranty
invoice becomes payable on normal terms.
Exclusions
Warranty may be refused for the following reasons:
Misapplication of product or component.
Incorrect site installation.
Incomplete commissioning documentation.
Inadequate site installation.
Inadequate site maintenance.
Damage caused by mishandling.
Replaced part being returned damaged without explanation.
Unnecessary delays incurred in return of defective component.
Returns Analysis
All faulty components returned under warranty are analysed on a monthly basis as a means of verifying component and
product reliability as well as supplier performance. It is important that all component failures are reported correctly.
4Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Health and Safety
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical /
electrical equipment, care must be taken if you are to obtain the best results.
Service Equipment
All service personnel must have refrigerant handling training.
Use only manifold gauge sets designed for use with refrigerants. Use only refrigerant recovery units and cylinders
designed for the pressure category of the refrigerants.
The refrigerant used in this range of products is classied under the COSHH regulations as an irritant, with set
Workplace Exposure Levels (WEL) for consideration if this plant is installed in conned or poorly ventilated areas.
A full hazard data sheet in accordance with COSHH regulations is available should this be required.
Refrigerants must only be charged in the liquid state.
The refrigerant must be stored in a clean, dry area away from sunlight. The refrigerant must never be stored above
50°C.
Global Warming Potential
The R134a refrigerant has a GWP of 1430, (Based on EN378-1:2016, 100 year life.
Pressure Equipment Directive
Minimum and Maximum Operation Temperature (TS) and Pressure (PS)
Refrigeration
AllowableTemperature Range (TS), Min -20°C* to Max 120°C**
Maximum Allowable Pressure (PS) High Side 18.8 Barg Low side 10.3 Barg
*Based on the refrigerant temperature in the unit off state in the lowest permitted ambient temperature.
**Based on the maximum allowable super heated refrigerant temperature.
Waterside
AllowableTemperature Range (TS) Min -20°C* to Max 40°C**
Maximum Allowable Pressure (PS) 10.0 Barg
*Based on the waterside temperature in the unit off state in the lowest permitted ambient temperature.
**Based on the waterside temperature in the unit off state in the highest permitted ambient temperature
Pressure System Safety Regulations 2000
Refrigeration assemblies/systems may constitute a Pressure System as dened in the Pressure System Safety
Regulations 2000.
Ecodesign Directive 2009/125/EC
The product range within this document is designed in accordance to the European Ecodesign Directive 2009/125/EC.
The appendix at the rear section of the manual gives the product compliancy metrics. Products sold outside of the EU
are exempt from this directive.
When working with any air conditioning units, ensure that the electrical isolator is switched off prior
to servicing or repair work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as re alarm circuits, BMS circuits,
crankcase heater permanent supplies etc.
Electrical installation commissioning and maintenance work on this equipment should be
undertaken by competent and trained personnel in accordance with local relevant standards and
codes of practice.
These Airedale chillers use R134a refrigerant which requires careful attention to proper storage
and handling procedures in accordance with EN 378. Maximum water temperature owing through
the chiller should be 40°C.
CAUTION
Dangerous Substances and Explosive Atmospheres Regulations
The completion of a DSEAR (Dangerous Substances and Explosive Atmospheres Regulations) risk assessment must
be completed as a legal requirement by the employer of the business where this equipment will be installed. This is not
the responsibility of Airedale International Air Conditioning Ltd to undertake as the manufacturer of the equipment.
5
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
CAUTION PACEMAKER WEARERS
To avoid any risk of injury, any work to be carried out on or around the
compressor and magnetic check valve should be done with personnel that do not
have pacemakers tted.
Care must be taken when working around the discharge pipe work of the unit.
High surface temperatures may exist during unit operation.
The refrigerant has a boiling point of -26°C.
CAUTION
Units without compressor enclosures are class A group 1 products and are only intended to be
used at locations where there is a distance greater than 30 m between the equipment and third
party sensitive radio communication equipment.
CAUTION
Electromagnetic Compatability (EMC)
Protective Personal Equipment
Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning
equipment.
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regards to manual
handling. This requirement is down to the discretion of the engineer.
Remember do not perform a lift that exceeds your ability.
6Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Environmental Considerations
Freeze Protection
The instructions below must be followed to protect the unit during low temperature operation in both the ON and OFF
state.
An appropriate concentration of glycol(1) is required when the unit is operating with a supply water temperature set point
of <=+5°C or if the evaporating temperature is <=+3°C.
Units subject to ambient temperatures lower than 0°C, a minimum of 2 of the following are required:
1. Glycol of an appropriate concentration(1) is used within the system to ensure adequate freeze protection. Please
ensure that the concentration is capable of protection to at least 3K lower than the minimum ambient the chiller can be
subjected to.
2. The water/glycol solution should be continuously circulated through all waterside pipework and coils to prevent static
water from freezing even during shut down periods, when the ambient is within 3K of the solution freeze point(1) (i.e. if
the solution freezes at 0°C, the pump must be operating at 3°C ambient).
3. Trace heating should be adequately sized and provided by others for all interconnecting water pipework between the
chiller and the process.
Trace Heating
Water pipework trace heating is included as standard within the chiller. It is imperative that as soon as the chiller is
lled with water/glycol that a separately fused, permanent, single phase and neutral supply is tted to the trace heating,
evaporator immersion heater and controls circuits. This circuit should be backed up in the event of a power failure to
prevent a potential freeze scenario. Please reference the interconnecting wiring diagram for further information.
The chiller must be lled with water/glycol before power is applied to the trace heating circuit. Failure to do so will
damage any immersion heaters present.
Maintenance
It is important that the glycol concentration is not diluted, if a pressurisation unit is present to maintain system pressure
then Airedale advises that a premixed solution of glycol to the required concentration is used and not water. Airedale
recommends that during prolonged cold periods or during winter months that the frequency of glycol concentration
checks are increased to ensure the glycol meets the required concentration.
During any reclamation of refrigerant from the evaporator during the off state, ensure the water/glycol solution is
continuously circulated to prevent static water from freezing.
If maintenance work is being carried out on the chiller preventing uid ow whilst the ambient temperature is within 3K
of the uid freezing point, then the uid circuit must be fully drained and the evaporator immersion heaters should be
turned off.
Free Cooling Chillers
For free cooling chillers it is mandatory that glycol of an appropriate concentration(1) is used within the coil volume. The
concentration should be capable of protection to at least 3K lower than the minimum ambient.
(1) Refer to your glycol supplier for specic details. Airedale insists that the glycol freeze point (the temperature at which
ice crystals begin to form) is used rather than the burst point (the temperature the uid freezes and becomes expansive)
for all pumped systems. Failure to follow these instructions can damage pumps if slush is present and the pumps start
to run.
Flow Control
For xed ow applications, when the chiller is in operation the design water ow MUST be maintained at all times within
acceptable tolerances (±5%). For variable ow systems, ow variation must not exceed 10% of the design ow per
minute and both the evaporator minimum/maximum ow rates should always be respected. Care to be taken when
selecting a chiller within 5% of the evaporator minimum ow rate. The end user must ensure that ow variation does not
fall below this minimum as the chiller will shut down.
7
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Environmental Policy
It is our policy to:
Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
Train personnel in sound environmental practices.
Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
Manufacture products in a responsible manner with minimum impact on the environment.
Reduce our use of chemicals and minimise their release to the environment.
Measure, control and verify environmental performance through internal and external audits.
Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
Electromagnetic Compatibility Directive (EMC) 2014/30/EU
Machinery Directive (MD) 89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED) 2014/68/EU
Ecodesign 2009/125/EC
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.
8Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Contents
Special Precautions 2
Warranty, Commissioning & Maintenance 2
Health and Safety 4
Environmental Considerations 6
Nomenclature 13
Range Layout 15
Unit Overview 20
Unit Components 22
Refrigeration 22
Danfoss Turbocor® Compressor 24
Condenser 25
Electrical 26
Condenser Fans 28
Waterside 29
Controls 37
Mechanical 41
Design Features & Information 43
Pipework Design 43
Refrigeration Schematic 43
Specic Heat Capacity (SHC) 44
Minimum System Water Volume Calculations 44
Typical Part Load Efciencies 45
Measurement of Sound Data 48
Water System 49
Grooved & Clamped Type Connection 49
Standard Recommended Installation 49
Water Treatment Guidelines 50
Water Systems and Recommended Flow Schemes 51
Technical Data - TCC (R) 54
TCC11R04S-01, TCC11R06S-01, TCC11R08S-01 54
TCC11R06L-02, TCC11R08L-03, TCC11R10L-03 56
TCC12R08S-04, TCC12R10S-04, TCC12R12S-04 58
TCC12R14S-04, TCC12R10L-05, TCC12R12L-06 60
TCC12R14L-06, TCC12R16L-06, TCC12R18L-06, TCC12R20L-06 62
TCC22R08S-14, TCC22R10S-14, TCC22R12S-14, TCC22R14S-14 64
TCC22R10L-15, TCC22R12L-15, TCC122R14L-15 66
TCC22R16L-16, TCC22R18L-16, TCC22R20L-16 68
TCC23R12S-17, TCC23R14S-17, TCC23R16S-17, TCC23R18S-17 70
TCC23R16L-19, TCC23R18L-19 72
TCC23R20L-20, TCC23R22L-20, TCC23R24L-20 74
TCC24R16S-18, TCC24R18S-18 76
TCC24R20S-18, TCC24R22S-18, TCC24R24S-18 78
TCC24R20L-21, TCC24R22L-21, TCC24R24L-21 80
Technical Data - TCC (X) 82
TCC11X04S-01, TCC11X06S-01, TCC11X08S-01 82
TCC11X06L-02, TCC11X08L-03, TCC11X10L-03 84
TCC12X08S-04, TCC12X10S-04, TCC12X12S-04 86
TCC12X14S-04, TCC12X10L-05, TCC12X12L-06 88
9
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Contents
TCC12X14L-06, TCC12X16L-06, TCC12X18L-06, TCC12X20L-06 90
TCC22X08S-14, TCC22X10S-14, TCC22X12S-14, TCC22X14S-14 92
TCC22X10L-15, TCC22X12L-15, TCC22X14L-15 94
TCC22X16L-16, TCC22X18L-16, TCC22X20L-16 96
TCC23X12S-17, TCC23X14S-17, TCC23X16S-17, TCC23X18S-17 98
TCC23X16L-19, TCC23X18L-19 100
TCC23X20L-20, TCC23X22L-20, TCC23X24L-20 102
TCC24X16S-18, TCC24X18S-18, TCC24X20S-18 104
TCC24X22S-18, TCC24X24S-18 106
TCC24X20L-21, TCC24X22L-21, TCC24X24L-21 108
Sound Data - TCC 110
TCC - EC Fans 110
Technical Data - TCF (R) 116
TCF11R06S-07, TCF11R08S-07, TCF11R06L-11 116
TCF11R08L-08, TCF11R10L-10, TCF12R08S-09 118
TCF12R10S-05, TCF12R12S-05, TCF12R14S-05 120
TCF12R12L-12, TCF12R14L-12, TCF12R16L-12 122
TCF12R18L-13, TCF12R20L-13 124
TCF22R10S-22, TCF22R12S-22, TCF22R14S-22 126
TCF22R12L-23, TCF22R14L-23, TCF22R16L-23 128
TCF22R18L-23, TCF22R20L-23 130
TCF23R12S-24, TCF23R14S-24, TCF23R16S-25, TCF23R18S-25 132
TCF23R18L-28, TCF23R20L-28, TCF23R22L-28, TCF23R24L-28 134
TCF24R16S-26, TCF24R18S-26, TCF24R20S-26 136
TCF24R22S-27, TCF24R24S-27 138
TCF24R22L-21, TCF24R24L-21 140
Technical Data -TCF (X) 142
TCF11X06S-07, TCF11X08S-07, TCF11X06L-11 142
TCF11X08L-08, TCF11X10L-10, TCF12X08S-09 144
TCF12X10S-05, TCF12X12S-05, TCF12X14S-05 146
TCF12X12L-12, TCF12X14L-12, TCF12X16L-12 148
TCF12X18L-13, TCF12X20L-13 150
TCF22X10S-22, TCF22X12S-22, TCF22X14S-22 152
TCF22X12L-23, TCF22X14L-23, TCF22X16L-23 154
TCF22X18L-23, TCF22X20L-23 156
TCC22X18L-23, TCF22X20L-23 158
TCF23X12S-24, TCF23X14S-24, TCF23X16S-25, TCF23X18S-25 160
TCF23X18L-28, TCF23X20L-28, TCF23X22L-28, TCF23X24L-28 162
TCF24X16S-26, TCF24X18S-26, TCF24X20S-26 164
TCF24X22S-27, TCF24X24S-27, TCF24X22L-21, TCF24X24L-21 166
Sound Data - TCF 168
TCF - EC Fans 168
Hydronic Data 173
TCC Waterside Pressure Drop kPa (100% Water) 173
TCF Waterside Pressure Drop kPa (20% Ethylene Glycol) 176
Evaporator Pressure Drop - 100% Water 178
10 Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Evaporator Pressure Drop - 20% Ethylene Glycol 180
Strainer Pressure Drop - 100% Water 182
Strainer Pressure Drop - 20% Ethylene Glycol 182
Installation Data 183
Air Cooled Masses & Centre of Gravity (C of G) 183
Point Loadings 187
Unit Lifting 195
Lifting Dimensions 195
General Arrangement 197
Positioning 213
Airow & Maintenance Clearances 213
ISL Anti Vibration Mounting (Optional) 214
Interconnecting Wiring 217
Power Quality & Harmonics 218
Liquid Level Sensor 219
Pre Start Checks 220
pCO5+ Built In Display and Keypad 221
Unit Operation 222
Restarting the Unit 222
Changing the Setpoint 223
Enabling Pumps 224
Maintenance 225
General Inspections 225
Electrical Inspection 226
Refrigeration 227
Waterside 228
Controls 229
System 230
Troubleshooting 231
Alarms 233
Alarm Menu Display 233
Pump Alarms 240
Appendix - Ecodesign 241
Technical Data - TCC R 242
TCC11R04S-01, TCC11R06S-01, TCC11R08S-01 242
TCC11R06L-02, TCC11R08L-03, TCC11R10L-03 243
TCC12R08S-04, TCC12R10S-04, TCC12R12S-04 244
TCC12R14S-02, TCC12R10L-05, TCC12R12L-06 245
TCC12R14L-06, TCC12R16L-06, TCC12R18L-06, TCC12R20L-06 246
TCC22R08S-14,TCC22R10S-14, TCC22R12S-14, TCC22R14S-14 247
TCC22R10L-15, TCC22R12L-15, TCC22R14L-15 248
TCC22R16L-16, TCC22R18L-16, TCC22R20L-16 249
TCC23R12S-17, TCC23R14S-17, TCC23R16S-17, TCC23R18S-17 250
TCC23R16L-19, TCC23R18L-19 251
TCC23R20L-20, TCC23R22L-20, TCC23R24L-20 252
TCC24R16S-18, TCC24R18S-18 253
TCC24R20S-18, TCC24R22S-18, TCC24R24S-18 254
TCC24R20L-21, TCC24R22L-21, TCC24R24L-21 255
Contents
11
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Technical Data - TCC X 256
TCC11X04S-01, TCC11X06S-01, TCC11X08S-01 256
TCC11X06L-02, TCC11X08L-03, TCC11X10L-03 257
TCC12X08S-04, TCC12X10S-04, TCC12X12S-04 258
TCC12X14S-04, TCC12X10L-05, TCC12X12L-06 259
TCC12X14L-06, TCC12X16L-06, TCC12X18L-06, TCC12X20L-06 260
TCC22X08S-14, TCC22X10S-14, TCC22X12S-14, TCC22X14S-14 261
TCC22X10L-15, TCC22X12L-15, TCC22X14L-15 262
TCC22X16L-16, TCC22X18L-16, TCC22X20L-16 263
TCC23X12S-17, TCC23X14S-17, TCC23X16S-17, TCC23X18S-17 264
TCC23X16L-19, TCC23X18L-19 265
TCC23X20L-20, TCC23X22L-20, TCC23X24L-20 266
TCC24X16S-18 , TCC24X18S-18, TCC24X20S-18 267
TCC24X22S-18, TCC24X24S-18 268
TCC24X20L-21, TCC24X22L-21, TCC24X24L-21 269
Technical Data - TCF R 270
TCF11R06S-07, TCF11R08S-07, TCF11R06L-11 270
TCF11R08L-08, TCF11R10L-10, TCF12R08S-09 271
TCF12R10S-05, TCF12R12S-05, TCF12R14S-05 272
TCF12R12L-12, TCF12R14L-12, TCF12R16L-12 273
TCF12R18L-13, TCF12R20L-13 274
TCF22R10S-22, TCF22R12S-22, TCF22R14S-22 275
TCF22R12L-23, TCF22R14L-23, TCF22R16L-23 276
TCF22R18L-23, TCF22R20L-23 277
TCF23R12S-24, TCF23R14S-24, TCF23R16S-25, TCF23R18S-25 278
TCF23R18L-28, TCF23R20L-28, TCF23R22L-28, TCF23R24L-28 279
TCF24R16S-26, TCF24R18S-26, TCF24R20S-26 280
TCF24R22S-27, TCF24R24S-27 281
TCF24R22L-21, TCF24R24L-21 282
Technical Data - TCF X 283
TCF11X06S-07, TCF11X08S-07, TCF11X06L-11 283
TCF11X08L-08, TCF11X10L-10, TCF12X08S-09 284
TCF12X10S-05, TCF12X12S-05, TCF12X14S-05 285
TCF12X12L-12, TCF12X14L-12, TCF12X16L-12 286
TCF12X18L-13, TCF12X20L-13 287
TCF22X10S-22, TCF22X12S-22, TCF22X14S-22 288
Contents
12 Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Contents
TCF22X12L-23, TCF22X14L-23, TCF22X16L-23 289
TCF22X18L-23, TCF22X20L-23 290
TCF23X12S-24, TCF23X14S-24, TCF23X16S-25, TCF23X18S-25 291
TCF23X18L-28, TCF23X20L-28, TCF23X22L-28, TCF23X24L-28 292
TCF24X16S-26, TCF24X18S-26, TCF24X20S-26 293
TCF24X22S-27, TCF24X24S-27 , TCF24X22L-21, TCF24X24L-21 294
13
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Nomenclature
Introduction
The Airedale range of TurboChill air cooled and Freecool liquid chillers uses the technologically superior centrifugal
Danfoss Turbocor® compressors. Designed to cover the high capacity range between 200kW and 1700kW.
Each model is individually selected to provide the optimum solution for each application by offering maximum exibility
and matching customer requirements in terms of:
● Capacity
EER/ESEER (Energy Efciency Ratio and European Seasonal Energy Efciency ratio)
Sound Levels - Quiet (R) and Extra Quiet (X)
Footprint
For guidance the unit’s information within this manual has been generated at nominal conditions, due to the unit’s ability
to modulate capacity individually tailored unit solutions are available.
Please contact Airedale with your specic requirements and we will be pleased to provide you with an individually
tailored selection and technical detail.
Refrigerants
The range has been designed and optimised for operation with ozone benign R134a refrigerant.
1 to 28
11 R 8 S 12
TCC
TCC
TCF
1 or 2
1 to 4
R
X
4 to 24
S
L
TurboChill Air Cooled (TCC) and Freecool (TCF)
Number of Circuits (1 or 2)
Number of Compressors (1 to 4)
Sound Variants (Regular Quiet R, or Extra Quiet X)
Number of Fans (4 to 24)
Compressor Code (S = TT300, L = TT350)
Evaporator Code
14 Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Construction
The base shall be fabricated from galvanised steel to ensure a rigid, durable, weatherproof construction.
Unit panels shall be manufactured from galvanised sheet steel coated with epoxy baked powder paint to provide a
durable and weatherproof nish.
Standard unit colour shall be Light Grey (RAL 7035).
Free Cooling Operation
The TurboChill Free Cool chiller has been designed to provide the cooling load required whilst optimising energy
efciency at all times and as such will take advantage of free cooling whenever available. If the free cooling available
cannot satisfy the required full cooling load, direct expansion cooling is used to supplement the output.
In high ambients where free cooling is not available the fan speed modulates in the conventional manner to maintain
an optimised head pressure. Free cooling is initiated wherever the outdoor ambient is 2°C less than the return water
temperature.
During concurent cooling mode condensing temperature is constantly monitored and intelligently kept within the
compressor envelope to allow the fans to run as fast as possible and therefore achieve the most free-cooling without
having a negative impact on compressor integrity.
In ambients where the free cooling coil is capable of meeting the full cooling demand, the condenser fans are modulated
to provide the desired duty. The condenser fans are capable of being modulated between 15-100% (EC) or 40% - 100%
(AC) of airow to maintain the supply water temperature.
During periods where the condenser fan speed has been reduced to a minimum, the supply water temperature will then
be controlled by the 3 way valve.
0
100
200
300
400
500
600
Hours
Ambient °C
Ambient Hours
57% Full Free Cooling
40% Concurrent Free Cooling
3% Full DX
Free Cooling vs. Mechanical Cooling
15
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Range Layout
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Regular Quiet - Single Circuit - Air Cooled
TCC11R04S-01 240 3.41 4.61 - - 55.9 2800 x 2200 x 2626
TCC11R06S-01 265 3.67 5.17 - - 54.7 2800 x 2200 x 3758
TCC11R08S-01 275 3.86 5.42 - - 54.2 2800 x 2200 x 4890
TCC11R06L-02 390 3.03 4.68 - - 57.4 2800 x 2200 x 3758
TCC11R08L-03 425 3.16 4.82 - - 57.1 2800 x 2200 x 4890
TCC11R10L-03 450 3.24 4.99 - - 56.1 2800 x 2200 x 6022
TCC12R08S-04 470 3.32 4.47 - - 58.7 2800 x 2200 x 4890
TCC12R10S-04 500 3.47 5.11 - - 57.9 2800 x 2200 x 6022
TCC12R12S-04 530 3.54 5.37 - - 57.4 2800 x 2200 x 7154
TCC12R14S-04 560 3.58 5.41 - - 57.1 2800 x 2200 x 8286
TCC12R10L-05 600 3.05 4.82 - - 59.8 2800 x 2200 x 6022
TCC12R12L-06 670 3.16 4.91 - - 59.5 2800 x 2200 x 7154
TCC12R14L-06 750 3.15 4.99 - - 59.4 2800 x 2200 x 8286
TCC12R16L-06 800 3.17 5.04 - - 59.0 2800 x 2200 x 9418
TCC12R18L-06 850 3.09 5.04 - - 59.0 2800 x 2200 x 10550
TCC12R20L-06 900 3.06 5.02 - - 58.8 2800 x 2200 x 11682
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Regular Quiet - Dual Circuit - Air Cooled
TCC22R08S-14 470 3.36 4.30 - - 58.6 2800 x 2200 x 4890
TCC22R10S-14 500 3.52 4.95 - - 57.9 2800 x 2200 x 6022
TCC22R12S-14 530 3.60 5.14 - - 57.4 2800 x 2200 x 7154
TCC22R14S-14 560 3.64 5.21 - - 57.0 2800 x 2200 x 8286
TCC22R10L-15 600 3.13 4.20 - - 59.8 2800 x 2200 x 6022
TCC22R12L-15 670 3.25 4.44 - - 59.4 2800 x 2200 x 7154
TCC22R14L-15 750 3.26 4.57 - - 59.3 2800 x 2200 x 8286
TCC22R16L-16 800 3.30 4.71 - - 58.9 2800 x 2200 x 9418
TCC22R18L-16 850 3.24 4.79 - - 58.9 2800 x 2200 x 10550
TCC22R20L-16 900 3.21 4.86 - - 58.6 2800 x 2200 x 11682
TCC23R12S-17 630 3.35 5.16 - - 59.6 2800 x 2200 x 7154
TCC23R14S-17 680 3.44 5.27 - - 59.3 2800 x 2200 x 8286
TCC23R16S-17 730 3.51 5.30 - - 59.0 2800 x 2200 x 9418
TCC23R18S-17 780 3.53 5.36 - - 58.8 2800 x 2200 x 10550
TCC23R16L-19 840 3.10 4.88 - - 60.5 2800 x 2200 x 9418
TCC23R18L-19 900 3.19 5.00 - - 60.3 2800 x 2200 x 10550
TCC23R20L-20 960 3.26 5.09 - - 60.0 2800 x 2200 x 11682
TCC23R22L-20 1020 3.28 5.12 - - 59.8 2800 x 2200 x 12814
TCC23R24L-20 1080 3.29 5.16 - - 59.7 2800 x 2200 x 13946
TCC24R16S-18 820 3.32 5.21 - - 60.6 2800 x 2200 x 9418
TCC24R18S-18 860 3.40 5.26 - - 60.2 2800 x 2200 x 10550
TCC24R20S-18 900 3.46 5.31 - - 60.0 2800 x 2200 x 11682
TCC24R22S-18 950 3.49 5.33 - - 59.8 2800 x 2200 x 12814
TCC24R24S-18 1000 3.52 5.46 - - 59.6 2800 x 2200 x 13946
TCC24R20L-21 1040 3.02 5.07 - - 61.4 2800 x 2200 x 11682
TCC24R22L-21 1100 3.08 5.11 - - 61.3 2800 x 2200 x 12814
TCC24R24L-21 1160 3.14 5.14 - - 61.0 2800 x 2200 x 13946
Regular Quiet - Single Circuit - Air Cooled
Regular Quiet - Dual Circuit - Air Cooled
16 Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Range Layout
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Extra Quiet - Single Circuit - Air Cooled
TCC11X04S-01 200 3.46 4.36 - - 54.2 2800 x 2200 x 2626
TCC11X06S-01 225 3.90 5.38 - - 54.3 2800 x 2200 x 3758
TCC11X08S-01 235 4.11 5.63 - - 53.9 2800 x 2200 x 4890
TCC11X06L-02 350 3.09 4.76 - - 54.7 2800 x 2200 x 3758
TCC11X08L-03 385 3.40 4.95 - - 54.7 2800 x 2200 x 4890
TCC11X10L-03 410 3.55 5.15 - - 54.8 2800 x 2200 x 6022
TCC12X08S-04 430 3.36 4.98 - - 56.9 2800 x 2200 x 4890
TCC12X10S-04 460 3.60 5.13 - - 56.9 2800 x 2200 x 6022
TCC12X12S-04 490 3.75 5.48 - - 56.9 2800 x 2200 x 7154
TCC12X14S-04 520 3.81 5.67 - - 56.9 2800 x 2200 x 8286
TCC12X10L-05 560 3.01 5.07 - - 57.3 2800 x 2200 x 6022
TCC12X12L-06 630 3.20 5.15 - - 57.3 2800 x 2200 x 7154
TCC12X14L-06 710 3.27 5.19 - - 57.3 2800 x 2200 x 8286
TCC12X16L-06 760 3.32 5.34 - - 57.2 2800 x 2200 x 9418
TCC12X18L-06 810 3.35 5.38 - - 57.2 2800 x 2200 x 10550
TCC12X20L-06 860 3.28 5.37 - - 57.2 2800 x 2200 x 11682
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Extra Quiet - Dual Circuit - Air Cooled
TCC22X08S-14 430 3.33 4.39 - - 56.9 2800 x 2200 x 4890
TCC22X10S-14 460 3.58 4.87 - - 56.9 2800 x 2200 x 6022
TCC22X12S-14 490 3.74 5.28 - - 56.9 2800 x 2200 x 7154
TCC22X14S-14 520 3.81 5.34 - - 56.9 2800 x 2200 x 8286
TCC22X10L-15 520 3.07 4.41 - - 57.3 2800 x 2200 x 6022
TCC22X12L-15 630 3.22 4.47 - - 57.3 2800 x 2200 x 7154
TCC22X14L-15 710 3.29 4.68 - - 57.3 2800 x 2200 x 8286
TCC22X16L-16 760 3.37 4.88 - - 57.2 2800 x 2200 x 9418
TCC22X18L-16 810 3.40 5.00 - - 57.2 2800 x 2200 x 10550
TCC22X20L-16 860 3.34 5.07 - - 57.2 2800 x 2200 x 11682
TCC23X12S-17 590 3.35 5.29 - - 58.4 2800 x 2200 x 7154
TCC23X14S-17 640 3.50 5.38 - - 58.4 2800 x 2200 x 8286
TCC23X16S-17 690 3.60 5.43 - - 58.4 2800 x 2200 x 9418
TCC23X18S-17 740 3.67 5.49 - - 58.3 2800 x 2200 x 10550
TCC23X16L-19 780 3.09 5.03 - - 58.7 2800 x 2200 x 9418
TCC23X18L-19 840 3.22 5.10 - - 58.7 2800 x 2200 x 10550
TCC23X20L-20 900 3.32 5.22 - - 58.6 2800 x 2200 x 11682
TCC23X22L-20 960 3.41 5.25 - - 58.6 2800 x 2200 x 12814
TCC23X24L-20 1020 3.44 5.32 - - 58.6 2800 x 2200 x 13946
TCC24X16S-18 800 3.29 5.31 - - 59.5 2800 x 2200 x 9418
TCC24X18S-18 830 3.45 5.39 - - 59.4 2800 x 2200 x 10550
TCC24X20S-18 860 3.55 5.45 - - 59.3 2800 x 2200 x 11682
TCC24X22S-18 910 3.61 5.48 - - 59.3 2800 x 2200 x 12814
TCC24X24S-18 960 3.65 5.59 - - 59.2 2800 x 2200 x 13946
TCC24X20L-21 1000 2.95 5.19 - - 59.7 2800 x 2200 x 11682
TCC24X22L-21 1040 3.11 5.27 - - 59.7 2800 x 2200 x 12814
TCC24X24L-21 1080 3.20 5.33 - - 59.6 2800 x 2200 x 13946
Extra Quiet - Single Circuit - Air Cooled
Extra Quiet - Dual Circuit - Air Cooled
17
Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Regular Quiet - Single Circuit - FreeCool
TCF11R06S-07 275 3.62 4.44 265.8 20.01 55.0 2800 x 2200 x 3758
TCF11R08S-07 300 3.71 4.60 325.7 18.01 54.4 2800 x 2200 x 4890
TCF11R06L-11 390 2.95 3.91 299.5 22.08 57.4 2800 x 2200 x 3758
TCF11R08L-08 425 2.94 4.22 374.6 20.72 57.5 2800 x 2200 x 4890
TCF11R10L-10 430 3.29 4.43 431.8 19.46 55.9 2800 x 2200 x 6022
TCF12R08S-09 470 3.47 4.33 387.4 21.42 58.6 2800 x 2200 x 4890
TCF12R10S-05 500 3.76 4.74 458.1 20.27 57.8 2800 x 2200 x 6022
TCF12R12S-05 530 3.87 4.89 523.8 19.31 57.3 2800 x 2200 x 7154
TCF12R14S-05 560 3.95 4.95 586.3 18.53 57.0 2800 x 2200 x 8286
TCF12R12L-12 670 3.44 4.40 571.6 21.07 59.3 2800 x 2200 x 7154
TCF12R14L-12 750 3.49 4.42 657.5 20.78 59.1 2800 x 2200 x 8286
TCF12R16L-12 800 3.54 4.47 733.0 20.27 58.7 2800 x 2200 x 9418
TCF12R18L-13 850 3.49 4.54 806.9 19.83 58.6 2800 x 2200 x 10550
TCF12R20L-13 900 3.47 4.58 879.7 19.46 58.4 2800 x 2200 x 11682
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Regular Quiet - Dual Circuit - FreeCool
TCF22R10S-22 490 3.78 4.54 454.7 20.27 57.7 2800 x 2200 x 6022
TCF22R12S-22 530 3.89 4.73 523.8 19.31 57.3 2800 x 2200 x 7154
TCF22R14S-22 560 3.97 4.79 586.3 18.53 57.0 2800 x 2200 x 8286
TCF22R12L-23 650 3.52 4.21 565.7 21.07 59.0 2800 x 2200 x 7154
TCF22R14L-23 720 3.61 4.28 648.0 20.78 58.8 2800 x 2200 x 8286
TCF22R16L-23 765 3.69 4.39 720.7 20.27 58.4 2800 x 2200 x 9418
TCF22R18L-23 850 3.64 4.43 806.9 19.83 58.5 2800 x 2200 x 10550
TCF22R20L-23 900 3.63 4.49 879.7 19.46 58.2 2800 x 2200 x 11682
TCF23R12S-24 630 3.57 4.65 559.6 20.63 59.6 2800 x 2200 x 7154
TCF23R14S-24 680 3.68 4.75 634.4 20.05 59.3 2800 x 2200 x 8286
TCF23R16S-25 730 3.77 4.78 707.6 19.57 58.9 2800 x 2200 x 9418
TCF23R18S-25 780 3.82 4.84 779.7 19.16 58.7 2800 x 2200 x 10550
TCF23R18L-28 900 3.44 4.54 824.6 20.27 60.1 2800 x 2200 x 10550
TCF23R20L-28 960 3.53 4.60 902.2 19.96 59.9 2800 x 2200 x 11682
TCF23R22L-28 1020 3.59 4.62 979.2 19.69 59.6 2800 x 2200 x 12814
TCF23R24L-28 1080 3.63 4.64 1055.6 19.46 59.5 2800 x 2200 x 13946
TCF24R16S-26 820 3.56 4.79 739.6 20.45 60.5 2800 x 2200 x 9418
TCF24R18S-26 860 3.65 4.85 810.6 19.92 60.2 2800 x 2200 x 10550
TCF24R20S-26 900 3.73 4.91 879.7 19.46 59.9 2800 x 2200 x 11682
TCF24R22S-27 950 3.79 4.94 951.6 19.14 59.7 2800 x 2200 x 12814
TCF24R24S-27 1000 3.84 5.12 1022.8 18.85 59.5 2800 x 2200 x 13946
TCF24R22L-21 1100 3.29 4.57 1007.8 20.27 61.2 2800 x 2200 x 12814
TCF24R24L-21 1160 3.37 4.58 1085.6 20.01 60.9 2800 x 2200 x 13946
Regular Quiet - Single Circuit - Free Cooled
Regular Quiet - Dual Circuit - Free Cooled
Range Layout
18 Chiller Technical Manual 7525355 V2.0_07_2023
Chillers
TurboChill™ Air Cooled and FreeCool
Range Layout
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Extra Quiet - Single Circuit - FreeCool
TCF11X06S-07 250 3.25 3.96 216.8 45.63 54.2 2800 x 2200 x 3758
TCF11X08S-07 260 3.47 4.15 266.5 42.07 54.2 2800 x 2200 x 4890
TCF11X06L-11 350 2.32 3.54 237.8 50.04 54.6 2800 x 2200 x 3758
TCF11X08L-08 385 2.47 3.81 301.7 47.62 54.6 2800 x 2200 x 4890
TCF11X10L-10 410 2.67 3.94 359.6 45.40 54.7 2800 x 2200 x 6022
TCF12X08S-09 415 3.20 4.25 308.0 49.61 56.9 2800 x 2200 x 4890
TCF12X10S-05 480 3.44 4.56 376.9 47.59 56.8 2800 x 2200 x 6022
TCF12X12S-05 510 3.60 4.65 436.3 45.91 56.8 2800 x 2200 x 7154
TCF12X14S-05 540 3.69 4.77 493.7 44.53 56.8 2800 x 2200 x 8286
TCF12X12L-12 600 3.01 4.03 457.4 48.76 57.2 2800 x 2200 x 7154
TCF12X14L-12 620 3.23 4.27 515.4 48.31 57.2 2800 x 2200 x 8286
TCF12X16L-12 740 3.15 4.20 596.6 47.44 57.1 2800 x 2200 x 9418
TCF12X18L-13 760 3.24 4.30 653.1 46.71 57.1 2800 x 2200 x 10550
TCF12X20L-13 780 3.31 4.37 707.8 46.07 57.1 2800 x 2200 x 11682
Model No
Nominal
Cooling
(kW)
EER ESEER Free-cooling
(kW)
Free Cooling
EER
Sound
Pressure @
10m (dBA)
Dimensions H x W x L
(mm) ETL
Extra Quiet - Dual Circuit - FreeCool
TCF22X10S-22 440 3.67 4.21 367.4 47.01 56.8 2800 x 2200 x 6022
TCF22X12S-22 490 3.80 4.66 430.9 45.34 56.8 2800 x 2200 x 7154
TCF22X14S-22 520 3.91 4.70 487.7 43.99 56.8 2800 x 2200 x 8286
TCF22X12L-23 600 3.21 3.62 457.4 48.76 57.2 2800 x 2200 x 7154
TCF22X14L-23 620 3.44 4.21 515.4 48.31 57.2 2800 x 2200 x 8286
TCF22X16L-23 740 3.43 4.22 596.6 47.44 57.1 2800 x 2200 x 9418
TCF22X18L-23 760 3.55 4.30 653.1 46.71 57.1 2800 x 2200 x 10550
TCF22X20L-23 780 3.64 4.38 707.8 46.07 57.1 2800 x 2200 x 11682
TCF23X12S-24 590 3.28 4.52 455.3 47.91 58.4 2800 x 2200 x 7154
TCF23X14S-24 640 3.43 4.63 520.3 46.92 58.3 2800 x 2200 x 8286
TCF23X16S-25 690 3.54 4.65 584.3 46.11 58.3 2800 x 2200 x 9418
TCF23X18S-25 740 3.62 4.68 647.8 45.44 58.2 2800 x 2200 x 10550
TCF23X18L-28 820 3.07 4.32 668.2 47.20 58.6 2800 x 2200 x 10550
TCF23X20L-28 900 3.16 4.38 739.8 46.71 58.5 2800 x 2200 x 11682
TCF23X22L-28 915 3.30 4.44 794.6 46.28 58.5 2800 x 2200 x 12814
TCF23X24L-28 1020 3.30 4.41 872.6 45.91 58.4 2800 x 2200 x 13946
TCF24X16S-26 750 3.20 4.70 258.0 47.96 59.0 2800 x 2200 x 9418
TCF24X18S-26 820 3.37 4.69 668.2 46.87 59.3 2800 x 2200 x 10550
TCF24X20S-26 860 3.46 4.71 729.8 46.07 59.2 2800 x 2200 x 11682
TCF24X22S-27 910 3.53 4.73 793.2 45.53 59.2 2800 x 2200 x 12814
TCF24X24S-27 960 3.58 5.01 856.3 45.05 59.1 2800 x 2200 x 13946
TCF24X22L-21 1040 2.91 4.35 825.5 47.38 59.6 2800 x 2200 x 12814
TCF24X24L-21 1080 2.99 4.38 887.8 46.71 59.5 2800 x 2200 x 13946
Extra Quiet - Dual Circuit - Free Cooled
Extra Quiet - Single Circuit - Free Cooled
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298