Magnetrol Echotel 355 Operating instructions

Category
Measuring, testing & control
Type
Operating instructions
Two-Wire Non-Contact
Ultrasonic Transmitter
For Level, Volume,
and Open Channel Flow
Measurement



Cast aluminum housing with
Kynar
®
transducer
Lexan
®
housing with
polypropylene transducer
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
Read this Manual Before Installing
T
his manual provides information on the Echotel
®
Model 355 Ultrasonic Transmitter. It is important that
all instructions are read carefully and followed in sequence.
Detailed instructions are included in the Installation sec-
tion of this manual.
Conventions Used in this Manual
Certain conventions are used in this manual to convey spe-
cific types of information. General technical material, sup-
port data, and safety information are presented in narrative
form. The following styles are used for notes, cautions, and
warnings.
NOTES
Notes contain information that augments or clarifies an
operating step. Notes do not normally contain actions.
They follow the procedural steps to which they refer.

Cautions alert the technician to special conditions that
could injure personnel, damage equipment, or reduce
a component’s mechanical integrity. Cautions are also
used to alert the technician to unsafe practices or the
need for special protective equipment or specific mate-
rials. In this manual, a caution box indicates a poten-
tially hazardous situation which, if not avoided, may
result in minor or moderate injury.
WARNINGS
Warnings identify potentially dangerous situations
or serious hazards. In this manual, a warning indicates
an imminently hazardous situation which, if not
avoided, could result in serious injury or death.
Safety Messages
Follow all standard industry procedures for servicing elec-
trical and computer equipment when working with or
around high voltage. Always shut off the power supply be-
fore touching any components. Although high voltage is
not present in this system, it may be present in other sys-
tems.
Electrical components are sensitive to electrostatic dis-
charge. To prevent equipment damage, observe safety pro-
cedures when working with electrostatic sensitive
components.
Low Voltage Directive
For use in Installations Category I, Pollution Degree 2.
If equipment is used in a manner not specified by the man-
ufacturer, protection provided by equipment may be im-
paired.
WARNING Explosion hazard. Do not connect or dis-
connect designs rated Explosion-proof or Non-incendive
unless power has been switched off and/or the area is
known to be non-hazardous
Notice of Copyright and Limitations
Magnetrol & Magnetrol logotype, and Echotel are regis-
tered trademarks of Magnetrol International.
Copyright © 2019 Magnetrol
®
International, Incorporated
Performance specifications are effective with date of issue
and are subject to change without notice. MAGNETROL
reserves the right to make changes to the product described
in this manual at any time without notice. Magnetrol
makes no warranty with respect to the accuracy of the in-
formation in this manual.
Warranty
All MAGNETROL electronic level and flow controls are
warranted free of defects in materials or workmanship
for eighteen months from the date of original factory
shipment.
If returned within the warranty period; and, upon factory
inspection of the control, the cause of the claim is deter-
mined to be covered under the warranty; then, MAG-
NETROL will repair or replace the control at no cost to
the purchaser (or owner) other than transportation.
MAGNETROL shall not be liable for misapplication,
labor claims, direct or consequential damage or expense
arising from the installation or use of equipment. There
are no other warranties expressed or implied, except
special written warranties covering some MAGNETROL
products.
Quality Assurance
The quality assurance system in place at MAGNETROL
guarantees the highest level of quality throughout the
company. MAGNETROL is committed to providing
full customer satisfaction both in quality products and
quality service.
The MAGNETROL quality assurance system is
registered to ISO 9001 affirming its commitment to
known international quality standards providing the
strongest assurance of product/service quality available.
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
3
Table of Contents
1.0 Introduction
1.1 Principle of Operation .............................................4
2.0 Installation
2.1 Unpacking ...............................................................5
2.2 Electrostatic Discharge (ESD) Handling Procedure......5
2.3 Mounting and Application Considerations ..............6
2.3.1 Position .........................................................6
2.3.2 Orientation ...................................................6
2.3.3 Temperature..................................................6
2.3.4 Obstructions .................................................7
2.3.5 Pipe Nozzles..................................................7
2.3.6 Foam.............................................................7
2.3.7 Vapors...........................................................7
2.3.8 Wind.............................................................7
2.3.9 Open Channel Flow Measurement................7
2.4 Wiring .....................................................................8
2.4.1 General Purpose or Non-Incendive ...............8
2.4.2 Intrinsically Safe............................................9
2.4.3 Explosion Proof.............................................9
2.5 Configuring the Transmitter...................................10
2.5.1 Basic Operating Parameters .........................10
2.5.2 Setting Up for Bench Configuration ...........10
2.5.3 Transmitter Initialization.............................10
2.5.4 Transmitter Display and Keypad .................11
2.5.4.1 Menu Traversal Mode......................11
2.5.4.2 Character Data Entry Mode............11
2.5.4.3 Numeric Digit Entry Mode.............12
2.5.4.4 Increment/Decrement Entry Mode ..12
2.5.5 Password Protection (Default = 0) ...............13
2.5.6 Configuration Menu Overview ...................13
2.5.7 Measured Values Menu ...............................13
2.5.8 System Configuration Menu .......................16
2.5.8.1 Level Applications ...........................17
2.5.8.2 Volume Applications .......................18
2.5.8.3 Open Channel Flow Applications ...23
2.5.9 I/O Configuration Menu ............................30
2.5.10 Advanced Configuration Menu ...................34
2.5.11 Diagnostics Menu .......................................41
2.5.12 Factory Configuration Menu.......................45
2.6 Configuration Using HART
®
................................46
2.6.1 Connections................................................46
2.6.2 Display Menu .............................................46
2.6.3 HART
®
Menu.............................................47
3.0 Reference Information
3.1 Troubleshooting.....................................................49
3.1.1 Troubleshooting System Problems...............50
3.1.2 Error Messages ............................................50
3.2 Measurement Range Calculations ..........................52
3.3 Speed of Sound Through Gases..............................53
3.4 Parts.......................................................................53
3.4.1 Replacement Parts .......................................53
3.4.2 Replacement Spare Parts..............................54
3.5 Agency Approvals...................................................54
3.5.1 Agency (FM/FMc) Drawing and
Entity Parameters
.....................................55
3.6 Specifications .........................................................56
3.6.1 Transmitter .................................................56
3.6.2 Transducer ..................................................56
3.6.3 Performance ................................................56
3.6.4 Physical .......................................................57
3.7 Model Number ......................................................58
Model 355 Configuration Data Sheet ..................................59
Echotel
®
Model 355
Non-Contact Ultrasonic Transmitter
4
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
1.0 Introduction
Echotel Model 355 is a two-wire non-contact transmitter
that performs level, volume, and open channel flow meas-
urements in a wide variety of industrial and municipal ap-
plications. A maximum range of 20 feet (6 meters) can be
measured under ideal conditions. The maximum range will
be less than this if there is excessive turbulence, foam or
other adverse application conditions. The user should con-
sult section 3.2, Measurement Range Calculations, to make
sure that the Model 355 is suited for the specific applica-
tion.
1.1 Principle of Operation
Non-contact ultrasonic measurement is obtained by emit-
ting an ultrasonic pulse from the transducer and measuring
the time required for the echo to reflect from the liquid
surface and return to the transducer. The Model 355 meas-
ures the time of the round trip pulse and calculates the dis-
tance using the equation:
D = Distance to target
Va = Velocity of sound through air (1,128 ft/sec.)
T = Time for one round trip sound pulse
Since the speed of sound is temperature dependent, the
transducer also measures the temperature at the transducer
to provide compensation for changing air temperatures.
Level is computed by the 355 electronics using the meas-
ured distance and the configuration data that has been en-
tered for the vessel dimensions.
By knowing the vessel type and its dimensions, the electron-
ics can calculate the liquid volume in the vessel. In a similar
operation, the Model 355 can perform open channel flow
measurement by converting the level reading into units of
volume per unit of time. Common tank shapes, flumes and
weirs are stored in the 355 software. A 20-point linearization
table is also available for unusual tanks or primary flow ele-
ments.
D =
Va T
2
Range
Blocking
Distance
Distance (measure
Level
(range - distance)
Model 355
Flow
Parshall
Flume


51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
5
2.0 Installation
This section provides detailed procedures for properly in-
stalling, configuring, and, as needed, troubleshooting the
Model 355 Ultrasonic Transmitter.
2.1 Unpacking
Unpack the instrument carefully. Make sure all components
have been removed from the packing material. Check all the
contents against the packing slip and report any discrepancies
to the factory.
Before proceeding with the installation, do the following:
Inspect all components for damage. Report any damage to
the carrier within 24 hours.
Make sure the model number on the nameplate agrees with
the packing slip and purchase order.
Record the model and serial numbers for future reference
when ordering parts.
Model Number
Serial Number
2.2 Electrostatic Discharge (ESD)
Handling Procedure
Magnetrols electronic instruments are manufactured to the
highest quality standards. These instruments use electronic
components that may be damaged by static electricity pres-
ent in most work environments.
The following steps are recommended to reduce the risk of
component failure due to electrostatic discharge.
Ship and store circuit boards in anti-static bags. If an anti-
static bag is not available, wrap the board in aluminum foil.
Do not place boards on foam packing materials.
Use a grounding wrist strap when installing and removing
circuit boards. A grounded workstation is recommended.
Handle circuit boards only by the edges. Do not touch com-
ponents or connector pins.
Make sure that all electrical connections are completely
made and none are partial or floating. Ground all equipment
to a good earth ground.
6
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
2.3 Mounting and Application Considerations
 Unit should only be hand-tightened into the process con-
nection. Overtightening may cause transducer errors and
will void the warranty.
 The Model 355 uses a thermoplastic transducer that should
not be used in liquid media that have esters or ketones.
Special Conditions for Safe Use:
1.
Materials marked as Category I equipment and used in haz-
ardous areas requiring this category shall be installed in such a
way that, even in the event of rare incidents, the aluminum en-
closure cannot be an ignition source due to impact or friction
2. The transmitter shall be installed so that electrostatic
discharges on plastic parts are prevented.
NOTE: Remove the black protective plastic cap from the end of the
transducer.
There are several application considerations that should be
evaluated prior to installing a non-contact ultrasonic trans-
mitter. The next few pages should be read thoroughly to
ensure that the Model 355 will perform as expected in
the given application. Section 3.2, Measurement Range
Calculations, provides derating multipliers that should be
used to determine the maximum potential range in diffi-
cult applications.
 
The optimum mounting position of the Model 355 is be-
tween
1
2 and
1
3 of the radius of the (cylindrical) tank. This
will position the unit to minimize any interference that the
10° beam (5° half angle) has with the tank walls or any agi-
tator blades that exist in the tank. Refer to the Beam Ra-
dius vs. Distance figure at left.
 
The face of the transducer must be parallel to the liquid
surface within 2° to 3° for proper operation.
 
Ensure that the Model 355 will be protected against overheat-
ing by intense direct sunshine. When the unit will be subjected
to severe direct sun, the use of a sunshade is recommended.
Sunshade
1
/2
Radius
1
/2
Radius
r=5.2 inches5 feet
r=10.5 inches10 feet
r=15.7 inches15 feet
r=21.0 inches20 feet
r
Beam Radius (r) vs. Distance



51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
7
 
Preferred mounting is such that no obstacles (e.g., fill
pipes, ladders, bracing members, agitator blades, etc.) ob-
struct the ultrasonic beam. Minor obstacles in the path of
the ultrasonic beam can be programmed out through the
use of the Echo Profile menu in Advanced Configuration.
For further information on vessel obstructions, see Section
3.2, Measurement Range Calculations.
 
Ideally, the 355 should be mounted so that the transducer
face is at least 10
" (250 mm) above the highest anticipated
level. In applications where the material level may come
into the blocking distance, the transducer can be mounted
in a pipe nozzle (standpipe). The inner rim of the nozzle
must be smooth and free of burrs. False echoes can some-
times be produced by the change in impedance at the end
of a nozzle. Cutting the bottom of the nozzle at a 45°
angle is suggested to help eliminate false echoes by reduc-
ing this impedance change. The maximum length for a
given diameter of nozzle is shown at left.
 
Foaming of the liquid surface may render ultrasonic level
measurement impossible. If possible, a mounting location
should be found where foaming is at a minimum. Another
alternative is to install the transducer in a stilling well that
extends below the lowest level to be measured in the tank.
Refer to Section 3.2, Measurement Range Calculations, for
more information.
 
Closed tanks that contain chemicals or other liquids that
create vapors may severely reduce the maximum measuring
range. Refer to the Section 3.2, Measurement Range Cal-
culations for more information.
 
Strong air flow or wind in the vicinity of the ultrasonic
beam should be avoided. A strong wind may prevent the
return echo from being received by the transducer.
 
For the best accuracy, mount the transducer as close as possi-
ble above the expected maximum water level (Head) in the
flume or weir (usually 12 to 18 inches (300 to 450 mm)
higher than the maximum head in the flume or weir).
Install the Model 355 on the inflow side of the flume throat
or weir crest in the location defined by the manufacturer of
the primary measuring device. The unit should also be
aligned with the longitudinal axis of the flume or weir.
Diameter
Length
 
2" (50 mm)
Not Recommended
3" (75 mm) 9" (225 mm)
4" (100 mm) 12" (300 mm)
5" (125 mm) 15" (375 mm)
6" (150 mm) 18" (450 mm)
8" (200 mm) 20" (500 mm)
Model 355
Flow
Parshall
Flume



45°
8
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
2.4 Wiring
 The Echotel Model 355 transmitter operates at voltages of
1
6 to 36 VDC (GP), 16 to 28.6 VDC (IS) and 16 to 36 VDC
(XP). Higher voltage will damage the transmitter.
 The Lexan
®
housing should only be used as “end of line”,
with one conduit entry plugged. If cable glands are used
with the Lexan housing, they should be non-metallic.
Wiring between the power supply and the Echotel Model 355
transmitter should be made using 18–22 AWG shielded
twisted pair instrument cable. Wiring must be suitable for
temperatures up to at least +185° F (+85° C). Within the
transmitter enclosure, connections are made to the terminal
strip and the ground connections. The directions for wiring
the Echotel Model 355 transmitter depend on the applica-
tion:
General Purpose or Non-incendive (Cl I, Div. 2)
Intrinsically Safe
Explosion Proof
 
This equipment is suitable for installation in Class I, Divi-
sion 2, Groups A, B, C, and D hazardous or
non-hazardous locations.
WARNING 

A general purpose installation does not have flammable
media present. Areas rated non-incendive (Cl I, Div. 2)
have flammable media present only under abnormal
conditions. No special electrical connections are required.
 If flammable media is contained in the vessel, the
transmitter must be installed per Cl I, Div. 1 standards of
area classification.
To install General Purpose or Non-Incendive wiring:
1. Remove the cover of the transmitter. Install the conduit
plug in the unused opening. Use PTFE tape/sealant to en-
sure a liquid-tight connection.
2. Install a conduit fitting and pull the supply wires.
3. Connect shield to an earth ground at power supply.
4. Connect an earth ground wire to the green ground screw.
Use a minimum 18 AWG wire rated up to +185 °F (+85 °C).
5. Connect the positive supply wire to the (+) terminal and
the negative supply wire to the (-) terminal.
6. Replace the cover of the transmitter.

Ground
(+)
(
-)
Black Wire (-)
Red Wire (+)
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
9
 
An intrinsically safe (IS) installation potentially has flam-
mable media present. An approved IS barrier must be in-
stalled in the non-hazardous (safe) area. See Agency
Drawing, Section 3.5.1.
To install Intrinsically Safe wiring:
1. Make sure the IS barrier is properly installed in the safe
area (refer to local plant or facility procedures). Complete
the wiring from the barrier to the Echotel 355 transmitter.
2. Remove the cover of the transmitter. Install the conduit
plug in the unused opening. Use PTFE tape/sealant to en-
sure a liquid-tight connection.
3. Install a conduit fitting and pull the supply wires.
4. Connect shield to an earth ground at power supply.
5. Connect an earth ground wire to the green ground screw.
Use a minimum 18 AWG wire rated up to +185 °F +(85 °C).
6. Connect the positive supply wire to the (+) terminal and
the negative supply wire to the (-) terminal.
7. Replace the cover of the transmitter.
 
WARNING Explosion hazard. Do not disconnect equipment unless
power has been switched off or the area is known to be
non-hazardous.
Explosion Proof (XP) is a method of designing equipment
for installation in hazardous areas. A hazardous location is
an area in which flammable gases or vapors are, or may be,
present in the air in quantities sufficient to produce explo-
sive or ignitable mixtures. The wiring for the transmitter
must be contained in Explosion Proof conduit extending
into the safe area. See Agency Approvals, Section 3.5.
To install Explosion Proof wiring:
1. Install Explosion Proof conduit from the safe area to the
conduit connection of the Echotel Model 355 transmitter
(refer to local plant or facility procedures).
2. Remove the cover of the transmitter.
3. Connect shield to an earth ground at the power supply.
4. Connect an Earth ground wire to the green ground screw
per local electrical code. Use a minimum 18 AWG wire
rated up to +185 °F (+85 °C).
5. Connect the positive supply wire to the (+) terminal and
the negative supply wire to the (-) terminal.
6. The cover must be completely installed before power may
be applied.
10
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
2.5 Configuring the Transmitter
Echotel Model 355 Ultrasonic Transmitters do not need to
be calibrated since they operate purely as time-of-flight
units based on the speed-of-sound. Configuring the
Model 355 for a specific level, volume, or open channel
flow application can be completed in minutes. Configura-
tion is easily performed at the vessel, or on a bench prior to
being installed in the field.

The following operating parameters are used in configuring
the Model 355 ultrasonic transmitter:
Range: Distance from the face of the transducer to the
bottom of the vessel/channel.
Blocking Distance: Minimum distance of 10" (250 mm)
in front of the transducer that is a “blind spacewhere the
transmitter cannot make any measurements.
Level Offset: If any obstructions (heating coils, mixing
blades, angled bottoms, etc.) exist at the bottom of the tank,
a Level Offset can be set to ignore reflections from these ob-
jects.
Distance: This is measured by the transmitter independent
of any of the configuration data. It is distance from the face
of the transducer to the target.
Level: Computed by the transmitter as the configured
Range minus the measured Distance.

The Model 355 can be configured at a test bench by con-
necting a 24 VDC power supply directly to the transmitter
terminals. Section 2.4 shows the wiring connections. When
using a HART communicator for configuration, a mini-
mum 250 Ω line load resistance is required. See the HART
communicator manual for more information.
To verify basic operation the 355 can be pointed at a stable
target at an appropriate distance and held steady. This can
be accomplished by holding the unit 2 to 4 feet (610 to
1220 mm) from the floor and observing the display for 1–
2 minutes.

When power is first applied to the unit, the transmitter
goes through an initialization period. During this period
the unit will show “Initializing.” After approximately 30
seconds the Model 355 will either begin to display meas-
ured values such as “Level” and “Distance,” or display an-
other status screen if a diagnostic condition is present.
Range
Blocking
Distance
Distance (measure
Level
(range - distance)
Level Offset

51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
11

The 355 transmitter has a local user interface consisting of a
2-line × 16-character liquid crystal display (LCD) and 4-
push-button keypad. All transmitter measurement data and
configuration information is shown in the LCD.
While configuring the unit with the local user interface the
transmitter cover is off and all 16 characters can be displayed
by the LCD. During normal operation the cover obscures
part of the LCD and only 12 characters are shown. For this
reason, the Measured Values and Diagnostic data are shown
as 12 characters per line so that they can be completely seen
through the cover window.
Model 355 is configured via atreetype menu structure,
where it is easy to access branches of the tree to configure the
various transmitter parameters. The four push buttons have
different functions for various operating modes within the
menu structure.
2.5.4.1 Menu Traversal Mode
When going from one branch of the menu to another the
push buttons operate as follows:
2.5.4.2 Character Data Entry Mode
This mode is most commonly used when entering a new
local tag into the 355 transmitter. The local tag as shipped
from the factory is “Model 355” but can be changed to
have the actual tag number of the vessel or primary ele-
ment. When entering data in the Character Data Entry
Mode, the leftmost character on the lower line of the LCD
will be a cursor. Data is entered at the cursor by using the
push buttons as follows:
Push button Keystroke Action
Up Moves to the previous item in the menu branch
Down Moves to the next item in the menu branch
Back Moves back one level to the previous higher branch item
Enter Enters into the lower level branch or switches to the entry mode
Push button Keystroke Action
Up
Moves to the previous character (Z,Y,X,W). If held down the
characters scroll until the push button is released.
Down
Moves to the next item character (A,B,C,D). If held down the
characters scroll until the push button is released.
Back
Moves the cursor back to the left. If the cursor is already at the
leftmost position, then the screen is exited without changing the
original tag characters.
Enter
Moves the cursor forward to the right. If the cursor is at the
rightmost position, then the new tag is saved.
12
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
2.5.4.3 Numeric Digit Entry Mode
The Numeric Digit Entry Mode is used to enter most of
the numeric values in the System and I/O Configuration
screens. This mode is accessed when the Enter key is
pressed on a menu item that presents a saved numeric value
such as the Range setting. Data is entered at the cursor by
using the push buttons as follows:
NOTE: All numeric values are left-justified, and new values are en-
tered from left to right. A decimal point can be entered after
the first digit is entered, such that .9 is entered as 0.9.
NOTE: A few configuration items can have a negative value. In
this case, the leftmost position is reserved for the sign (ei-
ther “-“ for a negative value, or+” for a positive value)
2.5.4.4 Increment/Decrement Digit Entry Mode
The Increment/Decrement Digit Entry Mode is used to
trim or revise some numeric values. An example is the Trim
Level screen in System Configuration which has a default
value of 0.0. When the Enter key is pushed in the Trim
Level screen, a double headed arrow (
) is shown as the
rightmost character of the LCD lower line. When the (
) is
present, the value can be revised by using the push buttons
as follows:
Push button Keystroke Action
Up
Moves up to the next highest digit (0,1,2,3,....,9). If held down
the digits scroll until the push button is released.
Down
Moves down to the next lowest digit (9,8,7,6,….,0). If held down
the digits scroll until the push button is released.
Back
Moves the cursor to the left and deletes a digit. If the cursor is
already at the leftmost position, then the screen is exited
without changing the previously saved value.
Enter
Moves the cursor to the right. If the cursor is located at a blank
character position, the new value is saved.
Push button Keystroke Action
Up
Increments the displayed value. If held down the digits scroll
until the push button is released. Depending on which screen is
being revised, the increment amount may increase by a factor of
10 after the value has been incremented 10 times.
Down
Decrements the displayed value. If held down the digits scroll
until the push button is released. Depending on which screen is
being revised, the decrement amount may increase by a factor
of 10 after the value has been decremented 10 times.
Back
Returns to the previous menu without changing the original
value, which is immediately redisplayed.
Enter Accepts the displayed value and returns to the previous menu.
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
13

The 355 transmitter can be password protected to restrict
access to certain portions of the menu structure that affect
the operation of the system. The default user password in-
stalled in the 355 transmitter at the factory is 0, which ef-
fectively disables the user password feature. This allows a
complete configuration to be done without entering a pass-
word.
If desired, a new user password can be entered in Advanced
Configuration in the New Password screen. The password
can be changed to any numerical value up to 255. If the pass-
word is changed from the factory default value of 0, then the
new password will be required whenever any configuration
values are changed.
NOTE: If the password is not known, the menu item New Password in
Advanced Configuration displays an encrypted value repre-
senting the present password. Contact the factory with this en-
crypted value to determine the actual password.

Configuration of the Model 355 is performed by use of a tree-
like menu structure. The figure on the next page shows an
overview of the top level menu items.

The Measured Values Menu (see page 15) contains all the
possible measured or calculated values that the 355 trans-
mitter can display for level, volume, and open channel flow
applications. For simple level applications there are many
screens (such as Volume, Flow, Head, and the totalizers)
that are not applicable and will show values of zero.
The Measured Values Menu is also used to add or remove pa-
rameters from the Home Menu. The Home Menu appears on
the LCD after the 355 is powered up and has gone through
the 30 second initialization period. Home Menu parameters
are shown as 12-characters or less, and have asterisks on either
side of the top line of the LCD. The Home Menu parameters
rotate at a 2-second interval on the LCD.
From the factory, the Home Menu will show the Level
value. To add or remove parameters from the Home Menu,
push the Enter key. Use the Up or Down keys
to remove them (Off Main Disp) or add them (On Main
Disp) from the rotating Home Menu display. To exit the
Measured Values screen push the Back key.
Any of the Measured Values screens can be left on the LCD
without returning to the rotating Home Menu. To return to
the rotating Home Menu, simply push the Back key
twice.
14
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter

Measured Values
See Page 15
Volume Setup
See Page 18
Flow Setup
See Page 23
4-20 mA Config
See Page 30
Totalizers
See Page 32
Echo Profile
See Page 38
Diagnostics
See Page 41
Factory Config
See Page 45
Vessel Dims
See Page 18
Gen Eqn Factors
See Page 26
System Config
See Page 18
I/O Config
See Page 30
Advanced Config
See Page 34
This Configuration Menu Overview shows the top level of the
Model 355 firmware. See the referenced pages for further infor-
mation on each branch of the tree-like menu structure.
Run Mode
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
15

Level
nnnn units
U
P / DN
Volume
nnnn units
UP / DN
D
EL
Flow
nnnn units
UP / DN
D
EL
Head
nnnn units
UP / DN
D
EL
Distance
nnnn units
UP / DN
DEL
% Output
nnn%
UP / DN
DEL
Loop Current
nn.nn mA
UP / DN
DEL
Local Tag
Model 355
UP / DN
DEL
Temperature
nn.n units
UP / DN
DEL
Totalizer R
nnnn units
UP / DN
DEL
Totalizer NR
nnnn units
UP / DN
DEL
Custom Unit
nnnn units
DEL
U
P / DN
M
easured Values
to select
UP / DN
System Config
to select
U
P / DN
IO Config
to select
UP / DN
Advanced Config
to select
UP / DN
Diagnostics
to select
UP / DN
Factory Config
to select
UP / DN
Run Mode
to select
UP / DN
Status
[Fault or Warning]
*[Label]*
[String or Value]
Model 355 HT
Ver 1.0 A
START
R
otating Screens
O
nly shown if fault or warning
S
hown for
2 Seconds
E
NT
E
NT
ENT
E
NT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
DEL
DEL
DEL
DEL
DEL
DEL
UP/DN
E
NT
D
EL
On Main Disp
Off Main Disp
E
NT
D
EL
16
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
 
The System Configuration Menu shown below contains all the parameters that are needed to configure the
355 for level applications. This menu is also used for Volume & Level and Flow & Level configurations:
L
anguage
[selection]
E
NT
DEL

Francais
D
eutsch
E
spanol
U
P / DN
Measure Type
[selection]
E
NT
DEL
D
EL

V
olume & Level
Flow & Level
U
P / DN
Level Units
[selection]
E
NT
DEL
DEL

Feet
Centimeters
Meters
UP / DN
Range
[entered value]
ENT
DEL
DEL
decimal entry
in selected units
U
P / DN
Blocking Dist
[entered value]
ENT
DEL
DEL

3.6 mA
22 mA
Latch 3.6 mA
Latch 22 mA
UP / DN
Safe Zone Fault
[selection]
ENT
DEL
DEL
decimal entry
in selected units
UP / DN
Safe Zone Height
[entered value]
ENT
DEL
DEL
decimal entry
in selected units
UP / DN
Level Offset
[entered value]
ENT
DEL
DEL
decimal entry
in selected units
UP / DN
Trim Level
[entered value]
UP / DN
ENT
DEL
DEL
[inc/dec]
in selected units
UP / DN
E
NT
DEL
S
ystem Config
to select
U
P / DN
U
P / DN
D
EL
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
17
2.5.8.1 System Configuration Menu –
Level Applications
The System Configuration Menu on the opposite
page contains all the parameters that are needed to
configure the 355 for level applications. Additional
System Configuration parameters are used for vol-
ume (page 18) or open channel flow applications
(page 23). The following table provides an explana-
tion of each of the System Configuration parame-
ters for level applications.
 
Language The 355 can be configured in  (default value), ,  or .
Measure Type The 355 can be configured as a (default value), , or Open
Channel  transmitter.
Level Units A selection of (default value), , , or  is provided.
Should some other units of level be desired, the Custom Unit feature can be used in
the Advanced Configuration Menu.
Range
Range is defined as the distance from the face of the transducer to the bottom of the
tank for level applications. This distance needs to be measured accurately for proper
level indication. Factory default value is 240.0 inches.
Blocking Dist
The Blocking Distance is a “blind space” or “dead zone” immediately in front of the
transducer where level measurement cannot be made. The 355 defaults to a mini-
mum Blocking Distance of 10" (250 mm). If needed, a larger value can be entered to
help ignore potential false echoes originating from the bottom rim of a nozzle, or other
objects close to the transducer.
Safe Zone Fault
Ultrasonic transmitters cannot reliably measure level if the liquid enters the Blocking
Distance. For this reason, a Safe Zone (see drawing above) can be configured in a user-
defined area just below the Blocking Distance. If desired, a Safe Zone Fault can be set
to ensure safe, reliable high-level readings in critical applications. Choices are 
(default value), , , , or . If  or
 is chosen, the loop current will remain in alarm until it is manually cleared
with the Safe Zone Alarm Reset located in the Diagnostics Menu.
Safe Zone Height
Safe Zone Height is entered as the distance just below the Blocking Distance that es-
tablishes a Safe Zone. If the liquid level enters this zone the 355 will report the chosen
Safe Zone Fault. Factory default value is 2.0 inches.
Level Offset
A Level Offset (see drawing above) can be established at the bottom of the tank if any
obstructions (heating coils, mixing blades, angled bottoms, etc.) exist that have the
potential to create false level reflections. It is the distance from the bottom of the tank
to the lowest valid level reading. The 355 will not display any levels (on the LCD or the
mA loop) lower than the Level Offset value. Factory default value is 0.0".
Trim Level
Trim Level is an offset value (maximum of ± 10" or 25.4 cm) that can be used to force the
output the exact level. This should only be used after all parameters have been entered cor-
rectly, and it has been confirmed that the transmitter is tracking the correct level target.
18
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
2.5.8.2 System Configuration Menu –
Volume Applications
The level System Configuration parameters on pages 16 &
17 need to be entered before the volume configuration can
be done. Enter these parameters prior to starting the
volume configuration shown below.
Conical Height
[entered value]
UP / DN
ENT
DEL
DEL
Width
[entered value]
ENT
DEL
Length
[entered value]
ENT
DEL
DEL
decimal entry
in selected units
UP / DN
Ellipse End
[entered value]
ENT
DEL
DEL
UP / DN
Previous Menu
to select
UP / DN
UP / DN
ENT
DEL
Ellipse Height
[entered value]
ENT
DEL
DEL
UP / DN
Radius
[entered value]
ENT
DEL
UP / DN
E
NT
DEL
Vessel Dims
to select
UP / DN
UP / DN
U
P / DN
Vessel Type
[selection]
E
NT
DEL
Volume Units
[selection]
U
P / DN
E
NT
DEL
E
NT
DEL
Volume Setup
to select
UP / DN
D
EL
DEL
DEL
U
P / DN
Rectangular
Horizontal/Flat
Horiz./Ellip.
Horiz./Sphere.
Spherical

Vertical/Ellip.
Vertical/Sphere
Vertical/Conical
Custom Table
C
ubic Feet
C
ubic Inches

M
illiliters
Liters
decimal entry
in selected units
decimal entry
in selected units
decimal entry
in selected units
decimal entry
in selected units
d
ecimal entry
i
n selected units
Verti/Ellip
only
Verti/Conical
only
Rectangular
only
Rectangular &
Horizontal only
Horiz/Ellipse
only
DEL
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter
19
2
.5.8.2 System Configuration Menu –
Volume Applications (cont.)
The following table provides an explanation of each of the
System Configuration parameters for volume applications
that use one of the nine Vessel Types. See below and page
20 for dimensional information on all nine Vessel Types.
 
Volume Units A selection of  (factory default Volume Unit), , , ,
or , is provided. Should some other units of volume be desired, the
Custom Unit feature can be used in the Advanced Configuration Menu.
Vessel Type Select either  (factory default Vessel Type)


Note: Vessel Dims is the next screen only if a specific Vessel Type was selected. If Custom Table was selected, turn
to page 21 & 22 to select the Cust Table Type and Cust Table Vals.
Vessel Dims
Depending on which Vessel Type was selected, the next few screens will allow
entry of the vessel dimensions. See the vessel drawings below and on page 20 for
proper dimensions.
 is used for all Vessel Types with the exception of Rectangular vessels.
 is only used for Vertical/Ellip vessels.
 is only used for Vertical/Conical vessels.
 is only used for Rectangular vessels.
 is only used for Rectangular and the three Horizontal vessels.
 is only used for Horiz/Ellip vessels.
Previous Menu exits the Vessel Dims menu.





Vessel Types

20
51-661 Echotel Model 355 Two-Wire Ultrasonic Transmitter













Vessel Types













  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Magnetrol Echotel 355 Operating instructions

Category
Measuring, testing & control
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI