TheapplicationA266.2isveryflexible.Thesearethebasic
principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’
or‘Saving’mode(twovaluesforthedesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperaturedoesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Thecirculationpump,P2,isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.Furthermorethe
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.WhentheA266.2isusedinanECLComfort310theflow/
energysignalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
DHW(circuit2):
TheDHWtemperatureatS4ismaintainedat‘Comfort’levelata
DHWdraw-off(DHWtapping)(theflowswitch(S8)isactivated).
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
TheDHWtemperaturecontrolisinrelationtoactualsupply
temperature(S6).Inordertocompensateforthereactiontime,the
motorizedcontrolvalvecanbepre-activatedatthestartofaDHW
draw-off(DHWtapping).Anidletemperaturecanbemaintainedat
eitherS6orS4whenthereisnodraw-off(DHWtapping).
Thereturntemperature(S5)canbelimitedtoafixedvalue.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’
or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
TypicalA266.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S4
DHWflowtemperaturesensor,circuit2
S5
(Optional)Returntemperaturesensor,circuit1,circuit
2orbothcircuits
S6
(Optional)Supplytemperaturesensor,circuit2
S7
(Optional)Flow/energymeter(pulsesignal)
S8
Flowswitch,DHWdraw-off,circuit2
P1
Circulationpump,DHW,circuit2
P2
Circulationpump,heating,circuit1
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV
A1
Alarm
8|©Danfoss|2018.01
VI.KT.X4.02
OperatingGuideECLComfort210/296/310,applicationA266