ATSUMI ELECTRICS Atsumi TriWatcher SIR10SA Outdoor PIR Detector Technical Manual

Type
Technical Manual
1
English
4-2-2 Shin-Miyakoda,Kitaku,Hamamatsu,Shizuoka 431 2103 Japan
Phone:(81)53-428-4116 Fax:(81)53-428-4119
Thank you for using this Atsumi Intrusion Alarm System:
Intelligent Outdoor Detector. Be sure to carefully read this
installation manual before the installation to ensure correct
installation. Then, keep this manual in a safe location for
reference when needed.
<Disclaimer>
This detector is a component device for detecting illegal
intrusion, and it is not a theft-prevention device. This
product should be used effectively as a part of a full
security system by the customer.
Atsumi is not liable for any damages arising due to theft or
other causes.
Intrusion Alarm System
Automatic Monitoring System
Intelligent Outdoor Detector
SIR10SA
Tri Watcher
®
Installation Manual
1. PRODUCT COMPONENTS
The product components are shown in the table below. Check that all the components are included before starting the
installation.
Component Quantity
Main device 1
Main device installation screws (nominal diameter 4 x 30) 2
Lens 1 masking tape 2
Lock screw (Nominal diameter M3x8) 1
Installation manual (this manual) 1
Lens 2 masking tape 1
2
English
2. NAMES OF PARTS AND THEIR OPERATIONS
a
Lens 1
This lens is for collecting the heat in the detection
area.
b
Lens 2
This lens is for collecting the heat in the detection
area.
c
Lens 1’
This lens is for collecting the heat in the detection
area.
d
Alarm LED 1
This LED lights or flashes red to indicate the
operating status of the device.
e
Alarm LED 2
This LED lights or flashes red to indicate the
operating status of the device.
f
Cover
This is the front cover of the device.
g
Lower cover
This is the bottom cover of the device.
h
Small cover
This is the cover of the setting switches.
i
Cover screw
These screws are used when removing the cover.
j
Knockout
Break this knockout for wiring on the wall.
k
Sensitivity volume
This adjusts the detection sensitivity.
l
Dip switch
The dip switches are used to set the various
functions of the device.
m
Alarm mode index
This index indicates the alarm mode.
Wide mode Pet Alley mode
n
Board fi x screw
This is a screw for fi xing the board in place.
o
Relay cable
This is a cable for connecting the main device
and mounting base.
p
Terminals
These are terminals for the cable connection to
other equipment.
q
Relay cable connector
This is a connector for connecting the relay cable
from the main device.
r
Tamper switch
This is a switch that detects opening and closing
of the lower cover.
s
Mounting base
This is used when mounting this device on a wall
or other object.
Main device front Main device rear
Main device rear Mounting base
f
a
d
b
e
c
g
i
i
i
i
h
i
i
g
j
k
l
o
m
n
s
q
p
r
3
English
3. NAMES OF TERMINALS AND THEIR OPERATIONS
Terminals of Mounting base
bcdaefgh
E+ E- COM NC TP1
TP2 AM1 AM2
Terminal symbol/Name Operation
Power supply input
(
a
:E+,
b
:E-)
A power supply of 9.0 V to 28.0 V DC is input. It has the
polarity.
Alarm output
(
c
:COM,
d
:NC)
This is the 1b non-voltage output.
The allowable contact capacity is 30 V DC/0.3 A
(resistor load).
* When power is not supplied,the output opens.
Tamper output
(
e
:TP1,
f
:TP2)
This is the 1b contact component non-voltage output.
The allowable contact capacity is 30 V DC/0.1 A
(resistor load).
Anti-Masking output
(
g
:AM1,
h
:AM2)
This is the 1b non-voltage output.
The allowable contact capacity is 30 V DC/0.3 A
(resistor load).
* When power is not supplied,the output opens.
4. WIRING MATERIALS AND WIRING METHODS
CAUTION
Do not wire near equipment that is a strong source of noise.
Do not wire in parallel to commercial power supplies or power lines.
Do not use aerial wiring. All of these installation could result in a malfunction.
Power line wiring
For the wiring materials of power input wires, use wires that have a resistance lower than the maximum allowable
resistance found using the formula below.
To simplify the calculation method in this example, the calculation method is described for the condition where the all
detectors are installed farthest from the power supply device (so that the allowable resistance is minimized).
Single wire (mm)
ø
0
.
50
ø
0
.
65
ø
0
.
80
ø
0
.
90
ø
1
.
00
ø
1
.
20
Single wire (AWG)
24 22 20 19 18 16
Twisted wire (mm
2
)
0
.
20 0
.
40 0
.
50 0
.
75 0
.
90 1
.
30
Resistance (
Ω
/km)
89 56 37 29 24 16
*Use a wire material that ranges from AWG24 to AWG16.
Wire Table
Calculation method for wire length in one
direction from power supply unit to this detector
Vc - Vs
Maximum allowable resistance
value for wire material R [
Ω
/km]
=
1.2 × (2×L) × i
Vc: Output voltage of power supply unit [V]
Vs: Minimum operating voltage of this device = 9 V
L : The wire length from this device to power supply unit (km)
i : Current consumption of this device = 0.035 A
Wire examples
E+ E- 1 C T1 T2 A1 A2
Power supply
output
Sensor
input
Error
input
Error
input
E+ E- 1 C T1 T2 A1 A2
Power supply
output
Sensor
input
Error
input
Error
input
E+ E- COM NC TP1 TP2 AM1 AM2
Power supply
input
Detection
output
Tamper
output
Anti-Masking
output
E+ E- COM NC TP1 TP2 AM1 AM2
Power supply
input
Detection
output
Tamper
output
Anti-Masking
output
Security receiver Detector 1 Detector 2
Security receiver
E+ E- COM NC TP1 TP2 AM1 AM2
Power supply
input
Detection
output
Tamper
output
Anti-Masking
output
Detector
a
One channel, single-detector example (1b contact)
b
One channel, two-sensor example (1b contact)
SIR10SA wiring examples
4
English
5. INSTALLATION PROCEDURE
1
Remove the lower cover, and rotate the main device
by 90 degrees.
Main device
Lower cover
2
Loosen the two screws.
3
Remove main device from the mounting base.
Main device
Mounting base
4
Use the device mounting screws to secure the
mounting base and back sponge to the wall surface
and connect the wiring.
Device mounting
screws
Mounting base
Device mounting
screws
Wall surface
Back sponge
(Back sponge
is affi xed to the
mounting base by
an adhesive tape.)
CAUTION
Be sure to install the main device so that it is parallel
to the ground surface or floor. If it is installed at a tilt, a
malfunction or breakdown could result.
5
Connect the relay cable of the main device to the
connector of the mounting base.
Relay cable connector
Mounting base
Relay cable
6
Fit the main device.
Main device
Mounting base
Hang the
hook of the
main device
rear side.
7
Tighten the screws.
8
About how to use lock screw.
* A locking mechanism of the rotary prevention
becomes stronger by using an attached lock
screw when the detection area of the detector was
decided.
Lock screw M3 × 8
5
English
9
Align the alarm direction, and tighten the screw of the
lower cover.
* Check the alarm direction index to make sure the
direction.
Main device
Lower cover
Alarm direction
index
NOTES
If Anti-Masking output remains even in the state where
masking is not performed after the warmup function has
ended, the Anti-Masking function may not have been
initialized normally. In this case, turn the power off and
then turn it back on.
Anti-Masking LED may be turned on while the warmup
function is running, which does not indicate a failure.
6. USING AS A PET ALLEY MODE
(The device is set to the wide mode in default)
1
Loosen the lower cover screw by about 5 mm, and
rotate the main device by 180 degrees.
Main device
Lower cover
2
Loosen the two screws, and take off the small cover.
Small cover
3
Loosen the board fix screw, and slide all the way
in the direction of the arrow. Check that the alarm
selection index is in the "P" position, and tighten the
board fi x screw.
Alarm selection index
Board fi x screw
4
Loosen the six cover screws.
5
Rotate the main device by 180 degrees so that it is
facing forward.
Main device
6
Remove the front cover.
Cover
Lens 1
Lens 2
Lens 1’
6
English
7
Remove Lens 1, 1’ and affix masking tape to the
inside of Lens 1, 1’.
The masking locations are "H" to "P" on Lens 1, 1’.
Lens 1
confi guration
Lens 2 confi guration
A
B
CD
E
F
G
H
I
J
K
L
M
N
O
P
a
b
c
d
e
f
g
n
m
l
k
j
i
h
o
Lens 1’
confi guration
A
B
CD
E
F
G
H
I
J
K
L
M
N
O
P
Lens 1 Lens 2
Lens 1’
CAUTION
The shape of the projections on lens 1, 1’ and lens 2
are different. When mounting the lens, be careful not
to mistake them. This could cause a malfunction or
breakdown.
After the lens is removed, do not touch the main
device internal parts. This could cause a malfunction or
breakdown.
8
Mount the front cover.
Cover
9
Rotate the main device by 180 degrees, and tighten
the six cover screws.
10
Set back the small cover, and tighten the two screws.
* The small cover can be mounted in either direction.
Small cover
11
Rotate the main device, align the alarm direction,
and then tighten the lower cover screws to secure in
place.
Main device
Rotation is possible 180
degrees in the left
direction.
Rotation is possible
135 degrees in the
right direction.
7
English
7. SETTING SWITCHES
Make the switch settings after removing the small cover from the main device.
Setting volume 1 ..................Sensitivity
Setting switches 1 and 2 ......Pulse count (Default: OFF, ON)
Setting switch 3 ...................LED indicator (Default: ON)
Setting switch 4 ................... LED precaution and Anti-Masking LED
indicator (Default: OFF)
1 2 3 4
ON OFF
Vol.1
1. Detection sensitivity selection function
(Sensitivity volume)
The detection sensitivity of the detector can be adjusted.
Range: 50% - 100% - 150%
The default detection sensitivity is 100%.
Operation :
When set to 100%, the detection sensitivity when
walking at 1 m/s in a 35°C environment is 1.5°C.
2. Pulse count function
(Setting switches 1 and 2)
Detection operation is performed by a preset number of
signal inputs.
Function selection : Set the setting switches to select one
of the four types below.
(Default
setting)
Switch 1 Switch 2 No. of signals
On On 1
Off On 2
On Off 3
Off Off 4
Operation
:
The number of signal inputs within 10 seconds
are countered, and if they reach to a preset
count, the detection operation is performed.
When 10 seconds elapses from the last signal
input, the count value is reset.
Normally, when a person passes through a zone,
one or two signal inputs are obtained, but if the
temperature difference is small between the
person and the background of the floor or wall,
only one signal is obtained. Therefore, keep this
point in mind when making the setting.
3. LED indicator selection function
(Setting switch 3)
On : Alarm LEDs 1 and 2 (red) are normally off, and turn
on at detection. (Default setting)
Off : Alarm LEDs 1 and 2 (red) are normally off, and do
not turn on at detection.
4. LED precaution and Anti-Masking LED
indicator
(Setting switch 4)
In normal conditions, the alarm LEDs 1 and 2 are
alternately turned on. (once every 2.5 seconds)
Upon detection of Anti-Masking, the alarm LEDs 1 and 2
start fl ashing simultaneously. (5 times a second)
The alarm LEDs fl ash at different intervals between when
operation is in normal conditions and when Anti-Masking
is detected.
On : The LED alarm is used. This function can be used
even though LED indicator selection is off.
Off : The LED alarm is not used. (Default setting)
8
English
Removing
1
Loosen the lower cover screw by about 5 mm, and
rotate the main device by 180 degrees.
Main device
2
Loosen the two screws, and take off the small cover.
Small cover
8. AUXILIARY FUNCTIONS
1. Detection system selection function
Wide mode
:
Install at a height from 2 to 3.0 m. In the default
setting, the Wide mode is set.
Pet alley mode: Install at a height from 0.8 to 1.2 m.
This is used when large pets may be falsely
detected by the Wide mode.
2. Warmup function
Function selection: This function is always enabled
regardless of the switch setting.
Operation
:
To stabilize the detection function of the detector,
the detection operation is not performed for
about 50 seconds after the power is on. During
the warmup operation, alarm LEDs 1 and 2 (red)
ash once a second.
3. Self-diagnostic function
This detects errors in the detector itself.
Function selection: This function is always enabled
regardless of the switch setting.
Operation
:
When an error occurs in the element or signal
amplifi cation unit, alarm LEDs 1 and 2 (red) fl ash
once a second, and continue to send the alarm
output until the power is turned off. In this case,
the device must be replaced.
The detector and the Anti-Masking function do not work
while the self-diagnostic function is running.
4. Tamper function
This detects opening and closing of the lower cover.
Function selection: This function is always enabled
regardless of the switch setting.
Operation
: While the lower cover is opened, the tamper
output is sent.
5. Masking function
If causes of false alarm are in the detection area (such
as trees and outdoor air-conditioning units) and causing
malfunctions, mask the lens to disable that detection sector.
Affi x the masking tape by referring to the zone diagram
shown in "12. Detection Area".
Lens 1
confi guration
Lens 2 confi guration
A
ag
B
b
C
c
D
d
E
e
F
f
G
Hh
I
i
J
j
K
k
L
l
M
m
N
n
OP
o
Lens 1’
confi guration
A
B
C
D
E
F
G
H
I
J
K
L
M
N
OP
Mounting
1
Fit the small cover, and tighten and secure the two screws.
* The small cover can be mounted with the top and
bottom in either direction.
Small cover
2
Rotate the main device, align the alarm direction, and
then tighten the lower cover screws to secure in place.
Mounting and removing the small cover
9
English
9. OPERATION CHECK ~ WALK TEST
(1) The warmup function runs for 50 seconds after the power is turned on, and the detection operation is not performed.
(The alarm LED fl ashes during this time.)
(2) Once the warmup is completed, walk through the detection area along the potential route of an intruder.
If the alarm LED does not turn on, set the detection area, sensitivity, and pulse count again, and repeat the operation
check.
10. TROUBLESHOOTING
If this detector does not work correctly, be sure to check the supply voltage and polarity. If the detector is still not
working correctly even though power is being supplied properly, fi nd the cause and remedy of the problem by referring
to the table below.
Symptom Cause Remedy
The detector does not work at all.
(The alarm LED (red) does not turn on.)
Sometimes, the detector does not work.
Glass, screen, or other obstacle is blocking
the detection zone.
Move the obstacle, or readjust the
detection area.
The relay cable is not connected. Connect the relay cable.
The intruder does not pass through the
detection zone.
Readjust the detector direction so that the
intruder will pass through the detection
zone.
The detector is activated even though there
is no intruder.
(The alarm LED (red) turns on.)
The detector is near a source of electrical
noise, or the wiring is near a power source
or power line.
Change the installation location.
Change the wiring location.
A sudden change in temperature has
occurred.
Move the heat source or mask the
correspond zone of the lens.
Readjust the detection area.
Sunlight, a car's headlights, or other light
source has entered the background of the
detector or detection area.
Readjust the detection area or mask the
correspond zone of the lens.
Trees, laundry, or other moving objects are
within the detection area.
Remove the moving object from the
detection area or mask the correspond
zone of the lens.
Readjust the detection area.
Change the installation location.
Anti-Masking out remains even when
masking is not performed.
The Anti-Masking function has not been
initialized normally.
Turn the power off and then turn it back on.
The alarm LED (red) turns on, but the
receiver alarm is not output.
The receiver is not in the alarm status. Set the receiver to the alarm status.
The alarm LED (red) flashes (once a
second) continuously.
The self-diagnostic function is activated
due to the detector error. The detector and
the Anti-Masking function do not work while
the self-diagnostic function is running.
Replace the detector unit.
6. Anti-Masking function
This function detects masking performed for this device.
Function selection:This function is always enabled
regardless of the switch setting.
Operation
: When masking is performed for one minute or
more, Anti-Masking is output from AM1 or AM2
on the terminal block.
If the setting switch 4 is ON, the alarm LEDs 1
and 2 fl ash fi ve times a second when masking
is performed for three seconds or more.
10
English
11. DETECTION AREA
Lens 1,1’ zone confi guration diagram Lens 2 zone confi guration diagram
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
O, P
12 (m)
12 (m)
0
2.5 (m)
1.0 (m)
0
5 (m) 10 (m) 12 (m)
H
~
N
A
~
G
Side View
Top View
P
a
b
c
d
e
f
g
h
i
j
k
l
m
n
o
o
12 (m)
12 (m)
0
2.5 (m)
1.0 (m)
0
5 (m) 10 (m) 12 (m)
h
~
n
a
~
g
Side View
Top View
Wide Alarm Area Diagram Pet Alley Alarm Area Diagram
12 (m)
12 (m)
0
2.5 (m)
1.0 (m)
0
5 (m) 10 (m) 12 (m)
Side View
Top View
1 (m)
12 (m)
12 (m)
0
2.5 (m)
1.0 (m)
0
5 (m) 10 (m) 12 (m)
Side View
Top View
1 (m)
When the board is slid to the top (opposite direction from pet alley)
2.5 (m)
1.0 (m)
0
5 (m) 10 (m) 12 (m)
Side View
(The maximum alarm distance is 9 m.)
Set the detector mounting height to 2.0 m to 3.0 m above the fl oor or ground for the wide mode and 0.8 m to 1.2 m
above the fl oor or ground for the pet alley mode.
The detection area can be adjusted ±45° horizontally, and the vertical direction can be adjusted by sliding the board.
The detection zone consists of Lens1,1
and Lens2 zone confi gurations.
11
English
12. DIMENSIONS
Knockout
Knockout
Knockout
Wire hole position
Knockout
Mounting base
82.3
99
ø78
282.7
3024
233
83.5
74.5
4.5
9.5
9.5
9.5
4.5
40
40
(R)
(R)
(R)
(R)
ø9
13. SPECIFICATIONS
Product name Intelligent outdoor detector
Model
SIR10SA
Power
9 – 28 V DC
Current draw
35 mA (maximum)
Operating temperature and
humidity range
-25 ~ +50°C RH 95% or less
Storage temperature and
humidity range
-30 ~ +60°C RH 95% or less
Alarm method
Wide mode Pet alley mode
Installation height
2m ~ 3.0m 0.8m ~ 1.2m
Detection area
12m, 84°
Detection zone (sector)
47 pairs(94 sectors) 29 pairs(58 sectors)
Detection method
Passive infrared system
Indicator lights
Alarm LED 1=Red, Alarm LED 2=Red
Self-diagnostic function : Alarm LEDs 1, 2 fl ashing (once a second)
Warmup function : Alarm LEDs 1, 2 fl ashing (once a second)
At detection : Alarm LEDs 1, 2 fully light
Anti-Masking : Alarm LEDs 1, 2 fl ashing (5 times a second)
LED precaution : Alarm LEDs 1, 2 turn on alternately
High
Priority
Low
Detection output
Non-voltage contact (1b)
Contact operation : One-shot (3 seconds)
Contact capacity : 30 V DC 0.3 A (resistance load)
Output resistance when closed
: 3
Ω
or less
Tamper output
Non-voltage contact (1b)
Contact operation : When the lower cover is removed or opened
Contact capacity : 30 V DC 0.1 A (resistance load)
Output resistance when closed
: 3
Ω
or less
Anti-Masking output
Non-voltage contact (1b)
Contact operation : When masking is performed for one minute or more
Contact capacity : 30 V DC 0.3 A (resistance load)
Output resistance when closed
: 3
Ω
or less
Detection speed
0.3 ~ 2.0 m/sec
Detection sensitivity
1.5°C (temperature difference with background)
Walk speed : 1 m/sec
Environment temperature : +35°C
Sensitivity setting : 100%
Main device movable range
Horizontal direction ±45°
Installation location
indoor/outdoor (IP55)
Weight
800g
Color
White DIC G-21
12
14. OPTIONAL COMPONENTS
The optional components shown in the table right are available for this
detector. Purchase them separately if needed.
The specifications of the optional components are subject to
change without notice for improvements
15. MAINTENANCE
Daily inspection
If the detector is dirty, wipe it off using a soft cloth with a small amount of soap solution. Never use thinner or
alcohols.
Perform an operation check on a regular basis about once a week. Also, check operation if storage box/house or
walls/screens to block the detection zones.
Regular inspection
Perform an operation check that includes that system about once a year. Be sure to also check the items below.

Is the supply voltage suitable?

Is the Alarm output working correctly (is the output resistance correct)?

Is the Tamper output working correctly (is the output resistance correct)?

Is the Anti-Masking output working correctly (is the output resistance correct)?
Product number Product name
PMK1 Pole mount kit
AE1257
4-2-2 Shin-Miyakoda,kitaku,Hamamatsu,Shizuoka 431 2103 Japan
Phone:(81)53-428-4116 Fax:(81)53-428-4119
The specifi cations and design are subject to change without notice for incorporating improvements.
Atsumi guarantees the quality of our products for a period of one year based on provisions of the warranty. If any
defects should occur in this product, please contact the dealer where you made the purchase.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

ATSUMI ELECTRICS Atsumi TriWatcher SIR10SA Outdoor PIR Detector Technical Manual

Type
Technical Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI