Siemens MM0404L1400RLM is a surface mount enclosure suitable for both overhead and underground service. It has a Type 3R enclosure rating, meaning it is designed to be weather-resistant and can be used outdoors. The device has a maximum amperage rating of 400 amps and can be used with either 120/240 V or 208Y/120 V single-phase, three-wire electrical systems. It comes with a 4-jaw meter socket that has a lever-operated bypass with jaw tension release. The terminal tightening torques range from 250 to 500 lb.-in. depending on the wire size.

Siemens MM0404L1400RLM is a surface mount enclosure suitable for both overhead and underground service. It has a Type 3R enclosure rating, meaning it is designed to be weather-resistant and can be used outdoors. The device has a maximum amperage rating of 400 amps and can be used with either 120/240 V or 208Y/120 V single-phase, three-wire electrical systems. It comes with a 4-jaw meter socket that has a lever-operated bypass with jaw tension release. The terminal tightening torques range from 250 to 500 lb.-in. depending on the wire size.

4099823 Rev.B
CATALOG NUMBER:
MM0404L1400RLM
FOR OVERHEAD AND UNDERGROUND
SERVICE SURFACE MOUNT
: CIRCUIT MAY BE LIVE WITH
METER REMOVED.
DEVICE RATING:
400 AMPS MAXIMUM; 120/240 V ~(4 JAW) OR
208Y/120 V ~ (5 JAW); SINGLE PHASE, THREE
WIRE.
METER SOCKET: 4 JAW; LEVER OPERATED
BYPASS WITH JAW TENSION RELEASE.
RATING: 400 AMPS (320 AMPS CONTINUOUS)
SUITABLE ONLY FOR USE AS SERVICE
EQUIPMENT.
CAUTION
Outdoor Combination Metering
ENCLOSURE
TYPE 3R
S
TERMINAL TIGHTENING TORQUES LB.-IN.:
kcmil OR AWG
WIRE SIZE
600 - 500 kcmil 500 _ _ _
500 - 350 kcmil 500 _ _ 450
350kcmil-3/0 500 250 _ 450
2/0 _ 250 50 _
1/0-#6 _ 250 50 _
TERMINAL RANGES, kcmil OR AWG:
= LIMITED TO (1)600kcmil-#4
OR (2)350kcmil-1/0
= (1)#250kcmil-6
= (1)2/0-#12
= LIMITED TO (1) 500kcmil-3/0
OR (2) 250kcmil-3/0
HARDWARE TIGHTENING TORQUES:
3/8 NUTS ........ 250-350 IN.-LBS.
ACCESSORIES
FILLER PLATE QF3
5TH JAW SHIELD S35815-2
FOR HUB, ORDER FROM “HD”
SERIES
COVERPLATE HD000
3” HUB HD300
3 ½”HUB HD350
4”HUB Hd400
EQUIPMENT
GROUND
NEUTRAL
(BONDED)
NEUTRAL
BARRIER
THIS DEVICE HAS A MAXIMUM SHORT CIRCUIT CURRENT RATING OF 65,000 AMPS
RMS SYMMETRICAL, 120/240 V ~. WATTHOUR METER IS NOT INCLUDED IN
SHORT CIRCUIT CURRENT RATING. THE ACTUAL RATING IS EQUAL TO THE
LOWEST INTERRUPTING RATING OF ANY INSTALLED CIRCUIT BREAKERS. USE
ONLY SIEMENS TYPE QP, QPH, HQP, QN, QNH, HQN, QNR, QNHR, OR HQNR
CIRCUIT BREAKERS. ANY CIRCUIT BREAKER INSTALLED, REPLACED, OR ADDED
IN THIS PANELBOARD MUST BE ONE OF THESE TYPES .
: THIS DEVICE HAS BEEN DESIGNED FOR USE ONLY WITH THOSE
CIRCUIT BREAKERS AS LISTED ABOVE. THE USE OF OTHER CIRCUIT BREAKERS
COULD RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY.
ALL OPENINGS MUST BE FILLED WITH BREAKERS OR FILLER PLATES.
FOR BREAKERS WITH TRIPPED POSITION IN CENTER, RESET BREAKER BY
MOVING HANDLE TO "OFF" AND THEN TO "ON". DEVICE SUITABLE FOR USE WITH
BREAKERS MARKED 60/75 C.
FOR INSTALLATION IN ACCORDANCE WITH ALL LOCAL ELECTRICAL CODES
AND/OR THE NATIONAL ELECTRICAL CODE.
.
WARNING
O
®
TERMINALS SUITABLE FOR USE WITH 60/75 C, INSULATED WIRE.
PAINTS, PLASTER, HYDROCARBON BASED SPRAYS, LUBRICANTS
OR SOLVENTS CAN DAMAGE THIS EQUIPMENT. DO NOT ALLOW THESE OR
OTHER CONTAMINANTS TO CONTACT INTERIOR COMPONENTS.
THE NATIONAL ELECTRICAL CODE IS A REGISTERED TRADEMARK OF THE
NATIONAL FIRE PROTECTION ASSOCIATION.
O
AL/CU
CAUTION:
®
4099824 Rev.A
SIEMENS ENERGY & AUTOMATION, INC.
ALPHARETTA, GEORGIA U.S.A
D
LEFT TWISTOUTS USED
WITH TYPE QN, QNH, HQN,
QNR, QNHR, & HQNR
BREAKERS ONLY
RIGHT TWISTOUTS
USED WITH TYPES QP,
QPH, OR HQP
BREAKERS
DEADFRONT VIEW
  • Page 1 1
  • Page 2 2

Siemens MM0404L1400RLM Installation guide

Type
Installation guide

Siemens MM0404L1400RLM is a surface mount enclosure suitable for both overhead and underground service. It has a Type 3R enclosure rating, meaning it is designed to be weather-resistant and can be used outdoors. The device has a maximum amperage rating of 400 amps and can be used with either 120/240 V or 208Y/120 V single-phase, three-wire electrical systems. It comes with a 4-jaw meter socket that has a lever-operated bypass with jaw tension release. The terminal tightening torques range from 250 to 500 lb.-in. depending on the wire size.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI