Fluorescent lamp
Ballast BallastAC Input
L
N
AC Input
L
N
Fluorescent lamp
Fluorescent lamp
Non-shunted lampholder
STOP!
DO NOT install this product in a xture that uses shunted lamp holders
(found in all xtures with instant start ballasts). Installing this product
with shunted lamp holders will cause a short circuit condition in the lamp
holder and create a re or shock hazard. Before continuing, determine if
the lamp holders currently installed in the xture are shunted or
non-shunted. If the current lamp holders are shunted, cut the wires away
from the lamp holders and install non-shunted lamp holders, making
new connections with the lead wires at terminals indicated here:
NOTE: If using existing non-shunted lamp holders, installer should not disconnect lead wires from
lamp holders and make new connections at terminals. Instead, cut lead wires away from lamp holders
and make new connections to lead wires using approved connectors.
INSTALLATION GUIDE
WARNING:
THIS PRODUCT MUCT BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PRESON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS
INVOLVED.
RISK OF SHOCK:
DISCONNECT POWER BEFORE INSTALLATION.
Risk of re/electric shock - The electrical rating of this product is 120-277V. Installer must determine whether
they have 120-277V at the xture before installation.
Risk of re/electric shock - T8 LED tube installation requires knowledge of uorescent lighting luminaires and
electrical systems. If not qualied, DO NOT attempt installation. Contact a qualied electrician.
Risk of re/electric shock - Install this kit only in the luminaires that have the construction features and
dimensions shown in the drawing and/or photographs.
Risk of re/electric shock - Do not use this kit in luminaires that emply shunted bi-pin lamp holders (found in
xtures that use instant start ballasts).
Do not make or alter any open holes in an enclosure of wiring or electrical components during installation.
This device complies with Part 15 of the FCC rules and has been tested and found to comply with the limits for
a Class B digital device. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequence to
radio communications. Any changes or modications not expressly approved by the manufacturer could void
the uner’s authority to operate the equipment.
Removing uorescent lamp system
NOTE: Westinghouse TL LED tube is suitable for be installed in T8 or T12 standard luminaries.
1. Disconnect power from xture.
2. Remove uorescent bulb.
3. Remove wiring compartment cover.
4. Cut all wires which are connected to ballast and remove it.