Eldes ELAN-SNMP User manual

Type
User manual

This manual is also suitable for

ELAN3-SNMP
SNMP ETHERNET CONTROLLER
2
2 EN
ELAN3 SNMP Ethernet Controller
User Manual v1.0
SAFETY INSTRUCTIONS
Please read and follow these safety guidelines to safeguard yourself and others:
DO NOT use the device where it can cause potential danger and interfere with other devices – such as medical devices.
DO NOT use the device in hazardous environment.
DO NOT expose the device to high humidity, chemical environment or mechanical impact.
DO NOT attempt to repair the device yourself – any repairs must be carried out by fully qualied personnel only.
Please, use the 10-24V 50Hz ~ 210mA AC or 10-24V 210mA DC power supply unit that meets the EN 60950-1 standard.
Any additional device you connect to the device, such as a computer, must also be powered by an EN 60950-1 approved
supply. When connecting the power supply to the device, switching the polarity terminal places does not have any aect.
External power supply can be connected to AC mains only inside installation room
with automatic 2-pole circuit breaker capable of disconnecting circuit in the event
of short circuit or over-current condition. Open circuit breaker must have a gap
between connections of more than 3mm and the disconnection current 5A.
Phase
AC 230V
50 Hz/DC 24V
USB cable
Null
PE
ELAN3
AC/DC
Disconnect the mains power before installing. Never install or carry out maintenance during stormy weather. The electric
socket that powers the device must be easily accessible.
To switch the device o, unplug the external electric power supply or any other linked device that the device is powered from.
A blown fuse cannot be replaced by the user. The replacement fuse has to be of the kind indicated by the manufacturer (Fuse
F1 model – miniSMDC 0,5A).
The WEEE (Waste Electrical and Electronic Equipment) symbol on this product (see left) means it must not be disposed of in
household waste. To prevent possible harm to human health and/or the environment, you must dispose of this product in an
approved and environmentally safe recycling facility. For further information contact your system supplier, or your local waste
authority.
Copyright © “ELDES UAB”, 2014. All rights reserved
It is strictly forbidden to copy and distribute information in this document or pass to a third party without an advanced
written authorization from “ELDES UAB”. “ELDES UAB” reserves the right to update or modify this document and/or related
products without a warning. Hereby, “ELDES UAB” declares that the SNMP Ethernet Controller ELAN3-SNMP is in compli-
ance with the essential requirements and other relevant provisions of Directive 1999/5/EC. The declaration of conformity
may be consulted at www.eldes.lt.
3
3EN
ELAN3 SNMP Ethernet Controller
CONTENTS
1. GENERAL INFORMATION ...........................................................................................................................................................5
2. TECHNICAL SPECIFICATIONS ....................................................................................................................................................5
2.1. Electrical & Mechanical Characteristics ......................................................................................................................................................... 5
2.2. Main Unit, LED Indicator & Connector Functionality ................................................................................................................................... 6
2.3. Wiring Diagrams ................................................................................................................................................................................................ 7
3. INSTALLATION ...........................................................................................................................................................................8
4. GENERAL OPERATIONAL DESCRIPTION....................................................................................................................................9
5. CONFIGURATION, CONTROL AND MONITORING METHODS .....................................................................................................9
5.1. Web Browser ......................................................................................................................................................................................................9
The following section is intended for input conguration. ................................................................................................................................. 11
5.2. SNMP Manager.................................................................................................................................................................................................14
6. TECHNICAL SUPPORT .............................................................................................................................................................17
6.1. Troubleshooting .............................................................................................................................................................................................17
6.2. Restoring Default Parameters ......................................................................................................................................................................17
6.3. Updating the Firmware via USB Cable ........................................................................................................................................................17
4
4 EN
ELAN3 SNMP Ethernet Controller
Limited Liability
The buyer agrees that the device will reduce the risk of re, theft, burglary or other danger but that it does not guarantee against the
occurrence of such events.
“ELDES UAB” will not take any responsibility for the loss of personal eects, property or revenue whilst using the device. The liability of
“ELDES UAB” is limited to the value of the device purchased.
“ELDES UAB” is not aliated with any mobile/wireless/cellular provider and is therefore not responsible for the quality of such services.
Manufacturer Warranty
The device carries a 24-month manufacturer warranty from “ELDES UAB”.
The warranty begins the day the device is purchased by the user and the receipt must be retained as proof of purchase date. The warran-
ty remains valid only if the device is used as intended, following all guidelines outlined in this manual and in accordance with the operat-
ing conditions specied.
The warranty is void if the device has been exposed to mechanical impact, chemicals, high humidity, uids, corrosive and hazardous
environments or force majeure factors.
Dear Customer,
Thank you for choosing to purchase the SNMP Ethernet Controller ELAN3-SNMP. Your thoughtful decision will ensure reliable solution
for many years as all ELDES products are manufactured to meet the highest standards.
We are condent that you will be completely satised with your product. However, in the unlikely event that you do experience a prob-
lem, please contact the dealer from whom you made your purchase.
UAB ELDES
CONTENTS OF PACK
Item ................................................... Quantity
1. ELAN3-SNMP......................................................1
2. User manual........................................... 1
Not included:
Power supply unit - can be obtained from your local distributor.
Ethernet cable - can be obtained from your local distributor.
Temperature sensor - can be obtained from your local distributor.
miniUSB cable - can be obtained from your local distributor.
5
5EN
ELAN3 SNMP Ethernet Controller
1. GENERAL INFORMATION
ELAN3-SNMP is a micro-controller based device used to inform users about the state changes on digital or analog inputs and control up to
2 electrical appliances connected to the open-collector outputs. These functions can be congured via web-browser or SNMP Manager
software compatible with SNMP (Simple Network Management Protocol) v1.0.
Examples of using the device:
Any electrical appliance control: lighting, watering, heating etc.
Remote reboot of the “frozen” devices, such as computer network or a server.
Main features:
Supported Ethernet connectivity: 10/100 Mbit.
Supported SNMP protocol: v1.0
User name/password-protected web-based remote conguration, monitoring and control.
4 inputs and 1 open-collector output or 3 inputs and 2 open-collector outputs.
Inputs customizable as NC or NO.
Supported input modes: digital or analog.
1-Wire interface for up to 8 temperature sensor connection intended for temperature monitoring in dierent areas.
Up to 3 destination IP addresses for trap message delivery.
2. TECHNICAL SPECIFICATIONS
2.1. Electrical & Mechanical Characteristics
Power supply ..................................................................................10-24V 50Hz ~ 210mA max. / 10-24V 210mA max.
Number of inputs/outputs............................................................4 inputs & 1 output or 3 inputs & 2 outputs (congurable)
Input value range ......................................................................... .0... 10V; 30V max.
Input internal resistance..............................................................40 kΩ
Output circuit ................................................................................. Open collector output. Output
is pulled to COM when turned ON.
Maximum commuted output values............................................30V 50Hz ~ 200mA /
30 V 200 mA
Maximum supported number of temperature sensors............8
Supported temperature sensor model ......................................Maxim®/Dallas® DS18S20, DS18B20
Enclosure dimensions...................................................................87x107x29 mm
PCB dimensions..............................................................................63x82x17 mm
Operating temperature range......................................................-20…+55 °C
Humidity...........................................................................................0-90% RH @ 0... +40 °C (non-condensing)
6
6 EN
ELAN3 SNMP Ethernet Controller
2.2. Main Unit, LED Indicator & Connector Functionality
1
FRONT SIDE SIDE VIEW
USB
LAN
(green)
LAN
(yellow)
USB
RJ45
DEF
F1
AC/DC C1 COM Z2 Z1 +5V DATAZ3C2/
Z4
STATUS
RJ45
RJ45 10/100Base-T Ethernet port
USB Mini USB port for rmware update
DEF Pins for rmware update and restoring default parameters
STATUS Red light-emitting diode indicating micro-controller status
F1 miniSMDC 0,5A fuse
AC/DC Power supply terminals
C1 Open-collector output terminal
COM Common terminal
C2/Z4 Open-collector output | digital/analog input terminal
Z3, Z2, Z1 Digital/analog input terminal
+5V Temperature sensor power supply terminal
DATA Temperature sensor data terminal
LAN (green) Green light-emitting diode indicating Ethernet activity
LAN (yellow) Yellow light-emitting diode indicating Ethernet status
7
7EN
ELAN3 SNMP Ethernet Controller
2.3. Wiring Diagrams
General wiring
2
USB
RJ45
DEF
STATUS
+12V
0..+10V 0..+10V
AC/DC C1 COM Z2 Z1 +5V DATAZ3C2/
Z4
Temperature sensor wiring
+5V
+5V
DATA
DATA
GND
GND
FRONT
AC/DC C1 COM Z2 Z1 +5V DATAZ3C2/
Z4
3
Example of output wiring
4
Alarm system or other appliance
+12V
Electrical
appliance
AC/DC C1 COM Z2 Z1 +5V DATAZ3C2/
Z4
8
8 EN
ELAN3 SNMP Ethernet Controller
3. INSTALLATION
The device should be installed indoors, in stationary environment ONLY.
For the wiring of input/output terminals, use 0.50 mm
2
thread unshielded cable of up to 100 meters length.
For the wiring of temperature sensor, use 0.50 mm
2
thread unshielded cable of up to 30 meters length.
1. Mount the device in a designated installation area, such as server room.
2. Connect AC/DC terminals to 10-24V AC or DC power supply unit (see 2.1. Electrical & Mechanical Characteristics).
3. Connect ELAN3-SNMP to local area network router using the Ethernet cable (see Fig. No. 2)
ELAN3-SNMP
USB
RJ45
ETHERNET ROUTER
4. Power up ELAN3-SNMP and wait until indicator STATUS starts ashing indicating successful micro-controller operation (see Fig. No.
1).
5. Indicator LAN (green) will ash indicating Ethernet connection activity, while indicator LAN (yellow) will be steady ON indicating
successful Ethernet connection (see Fig. No. 1).
6. Once the device is up and running, it will automatically obtain a local IP address from the DHCP server, therefore manual conguration
of ELAN3-SNMP is necessary only if DHCP server is not supported by your network.
7. Open a web-browser and type in the following address: http://eldeselan/
8. Once prompted to enter the login details, please enter the following:
User name: 1234
Password: 1234
9. Proceed to further device conguration, control and monitoring (see 5. CONFIGURATION, CONTROL AND MONITORING METHODS).
10. If the web-browser fails to open the http://eldeselan address, please proceed as follows:
a. Power down ELAN3-SNMP.
b. Unplug the Ethernet cable from the RJ45 port of ELAN3-SNMP.
c. Power up ELAN3-SNMP and wait for 20 seconds or longer.
d. Plug in the Ethernet cable to the RJ45 port of ELAN3-SNMP.
e. Open a web-browser and type in the following address: http://192.168.3.155
f. Log in using the same details as mentioned in item #8.
g. Disable DHCP parameter (see 5.1.1. Network).
2
9
9EN
ELAN3 SNMP Ethernet Controller
4. GENERAL OPERATIONAL DESCRIPTION
ELAN3-SNMP SNMP Ethernet controller uses the Ethernet interface for connection to the Internet and event transmission by trap mes-
sage to up to 3 preset destination IP addresses.
The device has 4 inputs (customizable as digital or analog) for alarm system’s PGM output or detection device connection, such as
magnetic door contact. By connecting the device’s input to the output of the equipment, you will be able to receive a trap message to
the SNMP Manager software regarding equipment status and other events depending on equipment conguration. In addition to being
informed by trap message regarding input alarm and restore events as well as input voltage value (mV), the user can control up to two
electrical appliances by connecting them to the open-collector outputs. For example, users can turn ON or OFF the heating, lighting, lift
the gates, blinds etc.
ELAN3-SNMP can be equipped with up to 8 external temperature sensors for temperature monitoring in dierent areas.
5. CONFIGURATION, CONTROL AND MONITORING METHODS
5.1. Web Browser
The device comes equipped with remote access feature allowing to congure, control and monitor by logging in to the internal ELAN3-SN-
MP device’s web server, identied as ELAN Conguration Web Server, using any available web-browser.
NOTE: ELAN Conguration Web Server is username/password-protected. By default, the login details are the following: User name:
1234 | password: 1234
5.1.1. Network
This section is intended for network conguration. In order to avoid the IP address collision in your local area network, once the
ELAN3-SNMP device is powered up for the rst time it is mandatory to change the default LAN IP Address if DHCP server is not supported
by your network.
6
LAN IP Address – Local static IP address of the device. Default value is 192.168.3.155, if DHCP not in use.
LAN Net Mask – Sub-net mask of the device. Default value is 255.255.255.0, if DHCP not in use.
Default Gateway – Local IP address of gateway. Default value is 192.168.3.1, if DHCP not in use.
Primary DNS Server – Primary Domain-Name-device server IP address. Default value is 194.25.2.129, if DHCP not in use. This parameter
is mandatory if Web Server URL is used.
Secondary DNS Server – Secondary Domain-Name-device server IP address.. Default value is 0.0.0.0, if DHCP not in use.
Web Server URL – Hostname of the device. Default value is eldeselan.
MAC Address – Unique Media-Access-Control address of ELAN3-SNMP device.
Local Web Server Port – Local TCP port of ELAN3-SNMP device. Default value is 80.
DHCP – Dynamic-Host-Conguration-Protocol:
ON – DHCP enabled. Default parameter.
OFF – DHCP disabled.
Save button – Saves the changes made to the parameters in this page.
Undo button – Cancels the changes made to the parameters in this page.
NOTE: Some networks do not support DHCP. Please, contact your network administrator in order to nd out whether DHCP is supported.
10
10 EN
ELAN3 SNMP Ethernet Controller
5.1.2. Authentication
In this section the user can set up the details required for logging in to ELAN Conguration Web Server.
7
User name – User name required for authorization to log in to ELAN Conguration Web Server. Default user name is 1234.
Password for user – Password for authorization to log in to ELAN Conguration Web Server. Default password is 1234.
Retype password – Repeat the password for conrmation when changing it.
5.1.3. Statistics
This section provides the information regarding the established TCP connections.
8
Socket – Sequence number of the socket.
State – Socket state:
CONNECT – Successfully connected to remote IP address.
LISTEN – Ready for connection.
CLOSED – Connection is closed.
Rem IP – Remote IP address the device is connected to.
Rem Port – Remote port number the device is connected through.
Loc Port – Local port number of the device.
Timer – Connection uptime in seconds.
11
11EN
ELAN3 SNMP Ethernet Controller
5.1.4. SNMP
This section is intended for SNMP security authorization, device-related information, trap destination IP address and SNMP status (ena-
bled/disabled) conguration.
9
Get/set Community – Password for authorization to read and write SNMP parameters from/to the device. Default value is public.
sysDescriptor – General description of the device. Default value is Inputs monitoring via SNMP.
sysContact – The name of person or company whom user can contact if technical support is required. Default value is ELDES.
sysName – Several name of device. Default value is ELAN.
sysLocation – The name of location where ELAN3-SNMP device is installed. Default value is Vilnius.
Trap destination1 – IP address of the 1st trap message destination. Default value is 192.168.1.100.
Trap destination2 – IP address of the 2nd trap message destination. Default value is 0.0.0.0.
Trap destination3 – IP address of the 3rd trap message destination. Default value is 0.0.0.0.
SNMP – Simple-Network-Management-Protocol:
OFF – SNMP enabled. Default parameter.
ON – SNMP disabled.
ATTENTION: In order to send and receive the trap messages to/from the device, SNMP must be selected as ON.
NOTE: The device will accept a trap message from any IP address, if the trap message contains a valid Get/set Community value.
5.1.5. Inputs
The following section is intended for input conguration.
10
Mode
Digital – The device measures the input voltage resulting in input state (violated/restored) change in accordance with the Thresh-
old parameter and trap message delivery to the destination IP address (-es) of SNMP Manager softwaare.
Analog – The device measures the input voltage resulting in voltage value inclusion in the trap message. The value will be in-
cluded in the trap message delivered to the destination IP address (-es) of SNMP Manager software in case of voltage decrease or
increase in accordance with the Delta parameter.
O – Input disabled.
12
12 EN
ELAN3 SNMP Ethernet Controller
Type
No – Sets input type as normally-open. Connecting the circuit leads to input violation. Default parameter.
Nc – Sets input type as normally-closed. Disconnecting the circuit leads to input violation.
Threshold – Sets the voltage value (mV) for Digital input mode. The device considers the input violated/restored once this value is
exceeded. Value range is 0... 10000 mV. Default value is 5000 mV.
Delta – Sets the voltage value (mV) for Analog input mode. The device will indicate the voltage once it increases or decreases by this
value. Value range is 0... 10000 mV. Default value is 1000 mV.
Input name – Title of the input that will be included in the trap message.
State ON name – Title of the violated input state that will be included in the trap message.
State OFF name – Title of the restored input state that will be included in the trap message.
Priority – Priority level for setting a unique identication number for trap message related with a certain input. Value range is 1... 8.
ATTENTION: In order to receive the trap message regarding the voltage change on the inputs, SNMP must be enabled. For more details on
how to enable SNMP, please refer to 5.1.4. SNMP..
For more details on input wiring, please refer to general wiring diagram provided in 2.3. Wiring Diagrams.
5.1.6. Temperature Sensors
This section is intended for temperature sensor conguraiton.
The ELAN3-SNMP device may be equipped with up to 8 temperature sensors intended for temperature measurement in the surrounding
areas. This feature allows to monitor the temperature of up to 8 dierent areas in real-time in ELAN Conguration Web Server’s section
Monitoring (see 5.1.8. Monitoring) and receive a trap message to up to 3 trap destination IP addresses (see 5.1.4. SNMP) when the set
temperature thresholds, identied as Min Value and Max Value, are exceeded.
Adding, removing temperature sensors
To add a temperature sensor to the device, proceed as follows:
a) Power down ELAN3-SNMP.
b) Wire up the temperature sensor to the 1-Wire interface terminals (see 2.3. Wiring Diagrams).
c) If more than one temperature sensor is required, wire another sensor in parallel to the previous one.
d) Add as many temperature sensors as necessary – wire up one after another in parallel – until the number of 8 sensors is reached.
e) Power up ELAN3-SNMP.
To view the real-time temperature values measured by each temperature sensor, please refer to section Monitoring (see 5.1.8. Monitoring).
Temperature trap message
The device supports a trap message, which is automatically delivered to the preset destination IP adress (-es) if the minimum (Min Value)
(by default, 10 °C) or maximum (Max Value) (by default, 25 °C) temperature threshold of the temperature sensor is exceeded.
Optionally, a name for a temperature sensor can be set that will be included in the trap message when delivered to the destination IP
address (-es). This feature allows easier identication of the temperature sensor.
ATTENTION: In order to receive the trap message regarding the voltage change on the inputs, SNMP must be enabled. For more details on
how to enable SNMP, please refer to 5.1.4. SNMP..
NOTE: When multiple temperature sensors are connected, please touch and hold the sensor with your ngers and watch the temperature
value change to identify the number of the temperature sensor slot..
11
13
13EN
ELAN3 SNMP Ethernet Controller
Sensor no. - Sequence number of the temperature sensor.
Name – Temperature sensor name that might be included in temperature trap message.
Min Value – Minimum temperature level threshold resulting in temperature trap message delivery to the preset destination IP ad-
dress(-es) when exceeded. Value range is -55... 125 °C. Default value is 10 °C..
Max Value – Maximum temperature level threshold resulting in temperature trap message delivery to the preset destination IP ad-
dress(-es) when exceeded. Value range is -55... 125 °C. Default value is 25 °C..
5.1.7. Outputs
This section is intended for output C1 and C2 control.
The ELAN3-SNMP device comes equipped with 2 open collector outputs C1 and C2 designed for electricalal appliance connection. Nor-
mally, outputs can be used to open/close garage doors, activate lights, heating, watering and much more. When output turns ON, the
ELAN3-SNMP triggers any equipment or relay connected to it (see 2.3. Wiring Diagrams).
When input Z4 is operating in Digital or Analog mode, output C2 will not be available. In such case C2/Z4 terminal can not be used as
open-collector output. In order to use C2/Z4 terminal as open-collector output, disable input Z4. For more details on input conguraiton,
please refer to 5.1.5. Inputs.
NOTE: Output C2 and input Z4 DO NOT operate simultaneously..
12
The output can be turned ON or OFF by selecting a corresponding output status ON or OFF from the drop down list and clicking the Save
button afterwards. By default, output C1 and C2 are turned OFF.
14
14 EN
ELAN3 SNMP Ethernet Controller
5.1.8. Monitoring
In this section the user can monitor the input value and state as well as the temperature sensors. The page is automatically refreshed
every 5 seconds.
13
Input1... 4:
Status – State of the digital input. Value range: 0 – input restored; 1 – input violated; Na – not available.
Value – Voltage value (mV) provided to the analog input. Value range: 1... 10000 mV; Na – not available
Temp1... 8:
Value – Temperature value of the area surrounding the temperature sensor. Value range: -125... 55 °C; Na – not available
5.2. SNMP Manager
The congured via Simple Network Management Protocol (SNMP v1.0) is carried out by transmitting the SET/GET message from SNMP
Manager software to ELAN3-SNMP device. The tables provided in the following sections describe supported parameters, OIDs, actions
available for each parameter which can be congured via SNMP as well as value range and an example/comment. Please, note that the
tables reect the parameters described in the sub-sections of 5.1. Web Browser.
5.2.1. Network
Parameter name OID Access Value Example / comment
LAN IP Address 1.3.6.1.4.1.34093.1.2.10.1.0 get/set IP address e.g. 192.168.1.101
LAN Net Mask 1.3.6.1.4.1.34093.1.2.10.2.0 get/set subnet IP e.g. 255.255.255.0
Default Gateway 1.3.6.1.4.1.34093.1.2.10.3.0 get/set gateway IP e.g. 192.168.1.1
Local Web Server Port 1.3.6.1.4.1.34093.1.2.11.3.0 get/set number e.g. 80
Firmware version 1.3.6.1.4.1.34093.1.2.12.1.0 read number e.g. 80
DHCP 1.3.6.1.4.1.34093.1.2.11.5.0 get/set 0, 1
0 = disabled;
1 = enabled
5.2.2. Authentication
Parameter name OID Access Value Example / comment
Username 1.3.6.1.4.1.34093.1.2.11.1.0 get/set
text (16 chars
max.)
e.g. user
Password 1.3.6.1.4.1.34093.1.2.11.2.0 get/set
text (16 chars
max.)
e.g. psw1234
15
15EN
ELAN3 SNMP Ethernet Controller
5.2.3. SNMP
Parameter name OID Access Value Example / comment
SysDescription 1.3.6.1.2.1.1.1.0 get/set text (32 chars max.) e.g. Inputs monitoring SNMP device
SysObjectID 1.3.6.1.2.1.1.2.0 get 1.3.6.1.4.1.34093.1.2 constant
SysUpTime 1.3.6.1.2.1.1.3.0 get counter e.g. 10778 seconds
SysContact 1.3.6.1.2.1.1.4.0 get/set text (32 chars max.) e.g. ELDES, Tel. No. +370111111
SysName 1.3.6.1.2.1.1.5.0 get/set text (32 chars max.) e.g. ELAN3-SNMP device
SysLocation 1.3.6.1.2.1.1.6.0 get/set text (32 chars max.) e.g. Vilnius, Lithuania
Read/write community 1.3.6.1.4.1.34093.1.2.30.1.0 get/set text (16 chars max.) e.g. public
Trap Destination1 1.3.6.1.4.1.34093.1.2.31.1.0 get/set IP address e.g. 192.168.1.201
Trap Destination2 1.3.6.1.4.1.34093.1.2.31.2.0 get/set IP address e.g. 192.168.1.202
Trap Destination3 1.3.6.1.4.1.34093.1.2.31.3.0 get/set IP address e.g. 192.168.1.203
5.2.4. Inputs
Parameter name OID Access Value Example / comment
Input1 name 1.3.6.1.4.1.34093.1.2.60.1.0 get/set text e.g. Input-1
Input2 name 1.3.6.1.4.1.34093.1.2.60.2.0 get/set text e.g. Input-2
Input3 name 1.3.6.1.4.1.34093.1.2.60.3.0 get/set text e.g. Input-3
Input4 name 1.3.6.1.4.1.34093.1.2.60.4.0 get/set text e.g. Input-4
Input1 state ON name 1.3.6.1.4.1.34093.1.2.61.1.0 get/set text e.g. Input-1 is violated
Input2 state ON name 1.3.6.1.4.1.34093.1.2.61.2.0 get/set text e.g. Input-2 is violated
Input3 state ON name 1.3.6.1.4.1.34093.1.2.61.3.0 get/set text e.g. Input-3 is violated
Input4 state ON name 1.3.6.1.4.1.34093.1.2.61.4.0 get/set text e.g. Input-4 is violated
Input1 state OFF name 1.3.6.1.4.1.34093.1.2.62.1.0 get/set text e.g. Input-1 is restored
Input2 state OFF name 1.3.6.1.4.1.34093.1.2.62.2.0 get/set text e.g. Input-2 is restored
Input3 state OFF name 1.3.6.1.4.1.34093.1.2.62.3.0 get/set text e.g. Input-3 is restored
Input4 state OFF name 1.3.6.1.4.1.34093.1.2.62.4.0 get/set text e.g. Input-4 is restored
Input1 priority 1.3.6.1.4.1.34093.1.2.63.1.0 get/set 1... 8 e.g. 2
Input2 priority 1.3.6.1.4.1.34093.1.2.63 2.0 get/set 1... 8 e.g. 3
Input3 priority 1.3.6.1.4.1.34093.1.2.63.3.0 get/set 1... 8 e.g. 8
Input4 priority 1.3.6.1.4.1.34093.1.2.63.4.0 get/set 1... 8 e.g. 1
Input1 mode 1.3.6.1.4.1.34093.1.2.64.1.0 get/set D, A D = digital; A = analog
Input2 mode 1.3.6.1.4.1.34093.1.2.64.2.0 get/set D, A D = digital; A = analog
Input3 mode 1.3.6.1.4.1.34093.1.2.64.3.0 get/set D, A D = digital; A = analog
Input4 mode 1.3.6.1.4.1.34093.1.2.64.4.0 get/set D, A D = digital; A = analog
Digital Input1 type 1.3.6.1.4.1.34093.1.2.65.1.0 get/set Nc, No Nc = normally closed; No = normally open
Digital Input2 type 1.3.6.1.4.1.34093.1.2.65.2.0 get/set Nc, No Nc = normally closed; No = normally open
Digital Input3 type 1.3.6.1.4.1.34093.1.2.65.3.0 get/set Nc, No Nc = normally closed; No = normally open
Digital Input4 type 1.3.6.1.4.1.34093.1.2.65.4.0 get/set Nc, No Nc = normally closed; No = normally open
Digital Input1 - threshold 1.3.6.1.4.1.34093.1.2.66.1.0 get/set 1... 10000 e.g. 6000 mV
Digital Input2 - threshold 1.3.6.1.4.1.34093.1.2.66.2.0 get/set 1... 10000 e.g. 5000mV
Digital Input3 - threshold 1.3.6.1.4.1.34093.1.2.66.3.0 get/set 1... 10000 e.g. 2000mV
Digital Input4 - threshold 1.3.6.1.4.1.34093.1.2.66.4.0 get/set 1... 10000 e.g. 4000mV
Analolg Input1 - delta 1.3.6.1.4.1.34093.1.2.67.1.0 get/set 1... 10000 e.g. 200 mV
Analolg Input2 - delta 1.3.6.1.4.1.34093.1.2.67.2.0 get/set 1... 10000 e.g. 300 mV
Analolg Input3 - delta 1.3.6.1.4.1.34093.1.2.67.3.0 get/set 1... 10000 e.g. 250 mV
Analolg Input4 - delta 1.3.6.1.4.1.34093.1.2.67.4.0 get/set 1... 10000 e.g. 360 mV
16
16 EN
ELAN3 SNMP Ethernet Controller
5.2.5. Temperature Sensors
Parameter name OID Access Value Example / comment
Temp1 name 1.3.6.1.4.1.34093.1.2.410.1.0 get/set text (16 chars max.) e.g. Garage temp
Temp2 name 1.3.6.1.4.1.34093.1.2.411.1.0 get/set text (16 chars max.) e.g. Kitchen temp
Temp3 name 1.3.6.1.4.1.34093.1.2.412.1.0 get/set text (16 chars max.) e.g. Corridor temp
Temp4 name 1.3.6.1.4.1.34093.1.2.413.1.0 get/set text (16 chars max.) e.g. Attic temp
Temp5 name 1.3.6.1.4.1.34093.1.2.414.1.0 get/set text (16 chars max.) e.g. Basement temp
Temp6 name 1.3.6.1.4.1.34093.1.2.415.1.0 get/set text (16 chars max.) e.g. Dining room temp
Temp7 name 1.3.6.1.4.1.34093.1.2.416.1.0 get/set text (16 chars max.) e.g. Living room temp
Temp8 name 1.3.6.1.4.1.34093.1.2.417.1.0 get/set text (16 chars max.) e.g. Sleeping room
Temp5 Min value 1.3.6.1.4.1.34093.1.2.404.1.0 get/set -55... 125 e.g. 20 °C
Temp5 Max value 1.3.6.1.4.1.34093.1.2.404.2.0 get/set -55... 125 e.g. -30 °C
Temp6 Min value 1.3.6.1.4.1.34093.1.2.405.1.0 get/set -55... 125 e.g. -15 °C
Temp6 Max value 1.3.6.1.4.1.34093.1.2.405.2.0 get/set -55... 125 e.g. 18 °C
Temp7 Min value 1.3.6.1.4.1.34093.1.2.406.1.0 get/set -55... 125 e.g. 22 °C
Temp7 Max value 1.3.6.1.4.1.34093.1.2.406.2.0 get/set -55... 125 e.g. 10 °C
Temp8 Min value 1.3.6.1.4.1.34093.1.2.407.1.0 get/set -55... 125 e.g. 2 °C
Temp8 Max value 1.3.6.1.4.1.34093.1.2.407.2.0 get/set -55... 125 e.g. -4 °C
5.2.6. Outputs
Parameter name OID
Access
Value Example / comment
Output C1 control 1.3.6.1.4.1.34093.1.2.200.1.0 get/set 0, 1 0 = turn OFF output; 1 = turn ON output
Output C2 control 1.3.6.1.4.1.34093.1.2.200.2.0 get/set 0, 1 0 = turn OFF output; 1 = turn ON output
5.2.7. Monitoring
Parameter name OID
Access
Value Example / comment
Input1 status 1.3.6.1.4.1.34093.1.2.300.1.0 get/trap 0, 1, Na 0 = input is restored; 1 = input is violated; Na = not
available
Input2 status 1.3.6.1.4.1.34093.1.2.300.2.0 get/trap 0, 1, Na 0 = input is restored; 1 = input is violated; Na = not
available
Input3 status 1.3.6.1.4.1.34093.1.2.300.3.0 get/trap 0, 1, Na 0 = input is restored; 1 = input is violated; Na = not
available
Input4 status 1.3.6.1.4.1.34093.1.2.300.4.0 get/trap 0, 1, Na 0 = input is restored; 1 = input is violated; Na = not
available
Input1 value 1.3.6.1.4.1.34093.1.2.301.1.0 get/trap 1... 10000, Na e.g. 6000 mV; Na = not available
Input2 value 1.3.6.1.4.1.34093.1.2.301.2.0 get/trap 1... 10000, Na e.g. 6000 mV; Na = not available
Input3 value 1.3.6.1.4.1.34093.1.2.301.3.0 get/trap 1... 10000, Na e.g. 6000 mV; Na = not available
Input4 value 1.3.6.1.4.1.34093.1.2.301.4.0 get/trap 1... 10000, Na e.g. 6000 mV; Na = not available
Temp1 value 1.3.6.1.4.1.34093.1.2.400.3.0 get/trap -55... 125 e.g. 15 °C
Temp2 value 1.3.6.1.4.1.34093.1.2.401.3.0 get/trap -55... 125 e.g. 25 °C
Temp3 value 1.3.6.1.4.1.34093.1.2.402.3.0 get/trap -55... 125 e.g. -42 °C
Temp4 value 1.3.6.1.4.1.34093.1.2.403.3.0 get/trap -55... 125 e.g. 12 °C
Temp5 value 1.3.6.1.4.1.34093.1.2.404.3.0 get/trap -55... 125 e.g. 4 °C
Temp6 value 1.3.6.1.4.1.34093.1.2.405.3.0 get/trap -55... 125 e.g. 33 °C
Temp7 value 1.3.6.1.4.1.34093.1.2.406.3.0 get/trap -55... 125 e.g. 18 °C
Temp8 value 1.3.6.1.4.1.34093.1.2.407.3.0 get/trap -55... 125 e.g. -11 °C
17
17EN
ELAN3 SNMP Ethernet Controller
6. TECHNICAL SUPPORT
6.1. Troubleshooting
Indication Possible reason
Indicator STATUS is OFF · Power supply fault.
· No mains power.
· Micro-controller fault.
Indicators LAN(green) and LAN(yellow)
are OFF
· Bad Ethernet cable.
· Ethernet router is switched OFF.
All indicators are ON or ashing, but
unable to receive any trap message to
SNMP Manager software
· Wrong trap destination IP address / IP address not set.
· Wrong SNMP Manager software conguration.
· TCP/UDP port not forwarded on the router for ELAN3-SNMP device’s IP address and/or
your ISP is permanently blocking a certain TCP/UDP port (-s).
For product warranty repair service please , contact your local retail store where this product was purchased.
If your problem could not be xed by the self-guide above, please contact your local distributor. More up to date information about your
device and other products can be found at the manufacturer’s website www.eldes.lt
6.2. Restoring Default Parameters
1. Power down the device.
2. Short-circuit (connect) the DEF pins.
3. Power up the device for 7 seconds.
4. Power down the device.
5. Remove the short-circuit from DEF pins.
6. Parameters restored to default.
6.3. Updating the Firmware via USB Cable
1. Power down the device.
2. Short-circuit (connect) the DEF pins.
3. Connect the device via USB cable to the PC.
4. Power up the device.
5. The new window must pop-up where you will nd the .bin le. Otherwise open My Computer and look for Boot Disk drive.
6. Delete the .bin le found in the drive.
7. Copy the new rmware .bin le to the very same window.
8. Power down the device.
9. Unplug the USB cable.
10. Remove the short-circuit from DEF pins.
11. Power up the device.
12. Firmware updated.
NOTE: It is strongly recommended to restore default parameters after the rmware update.
Made in the European Union
www.eldes.lt
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Eldes ELAN-SNMP User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI