Fire-Lite ACC-25 User manual

Category
Grass trimmers
Type
User manual
E1
P/N 51889:E1 ECN 10-278
Document 51889
6/8/2010 Rev:
Voice Evacuation Control Panels
AUDIO•COMMAND•CENTER•25/50
AUDIO•COMMAND•CENTER•25/50ZS
AUDIO•COMMAND•CENTER•25/50ZST
Instruction Manual
2 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a develop-
ing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the National Fire Protection Association
Standard 72 (NFPA 72), manufacturer's recommendations,
State and local codes, and the recommendations contained in
the Guides for Proper Use of System Smoke Detectors, which
are made available at no charge to all installing dealers.
These documents can be found at http://www.systemsen-
sor.com/html/applicat.html. A study by the Federal Emer-
gency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm sys-
tem may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-
floor or basement fire.
Particles of combustion or “smoke from a developing fire
may not reach the sensing chambers of smoke detectors
because:
Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
Smoke particles may be blown away from detectors by air
outlets.
Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsi-
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control panel. It is essential to use only equip-
ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A main-
tenance agreement should be arranged through the local man-
ufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Limit-C1-2-2007
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsof and Windows® are registered
trademarks of the Microsoft Corporation.
©Tuesday, August 14, 2012 9:40 am by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
4 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.T[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 5
Table of Contents
Section 1: Product Description ............................................................................................. 13
1.1: Product Features ..........................................................................................................................................14
1.2: Specifications...............................................................................................................................................19
1.3: Controls and Indicators................................................................................................................................23
1.3.1: Single Zone Operation (ACC-25/50, ACC-25/50ZS, ACC-25/50ZST) ...........................................23
1.3.2: Dual Zone Operation (ACC-25/50 Only)..........................................................................................23
1.3.3: RECORD/PLAYBACK ....................................................................................................................24
1.3.4: TROUBLE SILENCE .......................................................................................................................24
1.3.5: LEDs (visible with panel door closed): .............................................................................................24
1.3.6: ACC-ZPMK Zone Page Module (ACC-25/50ZS and ACC-25/50ZST Panels only) .......................24
1.3.7: ACC-FFT Fire Fighter Telephone Module (ACC-25/50ZST only) ...................................................25
1.3.8: ACC-EPM External Page Module.....................................................................................................25
1.3.9: Other System LEDs (located on main circuit board and modules) ...................................................25
1.4: Circuits.........................................................................................................................................................26
1.5: Components .................................................................................................................................................27
1.6: Optional Modules .......................................................................................................................................29
1.7: Getting Started .............................................................................................................................................30
1.7.1: ACC-25/50, Requiring up to 50 Watts of Audio Power....................................................................30
1.7.2: ACC-25/50 With ACC-25/50DA(s), Requiring Greater Than 50 Watts of Audio Power................30
1.7.3: ACC-25/50ZS & ACC-25/50ZST, Requiring up to 50 Watts of Audio Power................................30
1.7.4: ACC-25/50ZS & ACC-25/50ZST, Requiring Greater Than 50 Watts But Less Than 150 Watts....31
Section 2: Field Programming...............................................................................................32
2.1: S1 DIP Switch Settings on ACC-25/50 Series Motherboard (ACC-MCB) ................................................36
2.2: S5 DIP Switch Settings on ACC-25/50 Series Motherboard (ACC-MCB) ................................................37
2.3: S3 DIP Switch Settings on ACC-25/50 Motherboard (ACC-MCB) ...........................................................37
2.4: S2 - Record Bypass Switch on ACC-25/50 Series Motherboard (ACC-MCB) ..........................................38
2.5: S4 - Battery Charger Switch on ACC-25/50 Series Motherboard...............................................................39
2.6: SW1 - Remote Microphone Installed Switch on ACC-FFT........................................................................39
2.7: SW2 - 2 Wire/4 Wire Connection on Telephone Loop................................................................................39
2.8: ACC-ZPMK Zone Page Module (ACC-25/50ZS & ACC-25/50ZST) .......................................................39
2.8.1: S1 DIP Switch Settings on ACC-ZPMK...........................................................................................40
2.8.2: S2 and S3 Addressing Rotary Switches ............................................................................................41
2.9: ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST) ......................................................41
Section 3: Installation............................................................................................................. 42
3.1: Mounting Options........................................................................................................................................42
3.2: Backbox Installation ....................................................................................................................................42
3.2.1: Transformer Installation ....................................................................................................................45
3.3: Operating Power ..........................................................................................................................................46
3.4: Auxiliary DC Power Output Connections ...................................................................................................48
3.5: Input/Initiating Circuits ...............................................................................................................................48
3.6: Output Circuits.............................................................................................................................................49
3.6.1: Master Command Bus Output ...........................................................................................................49
3.6.2: Trouble Relay - TB1..........................................................................................................................51
3.6.3: AC Power Loss Relay - TB7 .............................................................................................................51
3.6.4: Notification Appliance Circuit (Speakers) ........................................................................................51
3.6.5: ACC-ZPMK Zone Page Module - ACS Link (ACC-25/50ZS & ACC-25/50ZST) .........................52
3.6.6: ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST) ............................................54
3.6.7: ACC-FFT Fire Fighter Telephone Module (ACC-25/50ZST Only) ..................................................55
3.7: UL Power-limited Wiring Requirements.....................................................................................................56
3.8: Installation of Option Modules ....................................................................................................................57
3.8.1: Audio Amplifier Module (ACC-AAM25) ........................................................................................57
3.8.2: 70.7 V
RMS
Transformer Module (FC-XRM70) ................................................................................58
3.8.3: Local Playback Speaker Module (FC-LPS) ......................................................................................59
Table of Contents
6 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
3.8.4: ACC-EPM External Page Module.....................................................................................................60
Section 4: Operating Instructions ......................................................................................... 63
4.1: Switch Functions..........................................................................................................................................63
4.1.1: Single Zone Operation (ACC-25/50, ACC-25/50ZS, ACC-25/50ZST) ...........................................63
4.1.2: Dual Zone Operation (ACC-25/50 Only) ..........................................................................................63
4.1.3: RECORD/PLAYBACK ....................................................................................................................64
4.1.4: TROUBLE SILENCE .......................................................................................................................64
4.1.5: Record/Playback Button - Record Customized Messages.................................................................64
Recording Instructions..........................................................................................................................64
4.1.6: Record/Playback Button - Review Stored Message(s) ......................................................................65
4.1.7: Main Control Panel Keypad Labels...................................................................................................66
4.2: ACC-ZPMK Switch Functions (ACC-25/50ZS & ACC-25/50ZST) ..........................................................66
4.3: ACC-FFT Answer Call Push-Button (ACC-25/50ZST)..............................................................................67
4.4: LED Indicators.............................................................................................................................................67
4.4.1: LEDs Visible with Backbox Door Closed (Figure 4.1 on page 63) ..................................................67
4.4.2: ACC-ZMPK LEDs Visible with Backbox Door Closed (Figure 4.4 on page 66) ............................68
4.4.3: ACC-FFT LEDs Visible with Backbox Door Closed (Figure 3.15 on page 55)...............................69
4.4.4: LEDs Visible with Door Open and Optional Dress Panel Removed (Figure 1.1 & Figure 1.2).......69
4.5: Operation......................................................................................................................................................70
4.5.1: Fire Alarm..........................................................................................................................................70
4.5.2: Fire Alarm Restoral ...........................................................................................................................70
4.5.3: Manual Evacuation/Alert...................................................................................................................70
4.5.4: Manual Evacuation/Alert Restoral ....................................................................................................71
4.5.5: Audio On/Off: ACC-25/50 Single Zone and ACC-25/50ZS/T.........................................................71
4.5.6: All Call: ACC-25/50, Single Zone Configuration .............................................................................71
All-Call General Page Using Local Microphone..................................................................................72
All-Call General Page Using Optional Remote Microphone ...............................................................72
All-Call Emergency Page Using Local Microphone ............................................................................72
All-Call Emergency Page Using Optional Remote Microphone..........................................................72
All-Call During FACP Activated Alarm ..............................................................................................72
All-Call During Manual Evacuation/Alert ...........................................................................................72
All-Call With Distributed Audio Panels...............................................................................................72
4.5.7: All-Call: ACC-25/50ZS & ACC-25/50ZST......................................................................................72
All-Call General Page Using Local/Integral Microphone ....................................................................72
All-Call General Page Using Optional Remote Microphone ...............................................................73
All-Call General Page Using Optional RPJ-F Remote Keyswitch via the Optional Fire Fighter Tele-
phone Module:......................................................................................................................................73
All-Call Emergency Page Using Local/Integral Microphone ..............................................................73
All-Call Emergency Page Using Optional Remote Microphone..........................................................73
All-Call Emergency Page Using Optional RPJ-F Remote Keyswitch via the Fire Fighter Telephone
Module..................................................................................................................................................73
All-Call During FACP Activated Alarm ..............................................................................................73
All-Call During Manual Evacuation/Alert ...........................................................................................73
4.5.8: Paging: ACC-25/50 Single Zone .......................................................................................................73
General Page Using Local/Integral Microphone ..................................................................................73
General Page Using Optional Remote Microphone .............................................................................73
Emergency Page Using Local/Integral Microphone.............................................................................74
Emergency Page Using Optional Remote Microphone........................................................................74
4.5.9: Paging: ACC-25/50 Dual Zone .........................................................................................................74
General Page Using Local/Integral Microphone ..................................................................................74
General Page Using Optional Remote Microphone .............................................................................74
Emergency Page Using Local/Integral Microphone.............................................................................74
Emergency Page Using Optional Remote Microphone........................................................................74
4.5.10: Paging: ACC-25/50ZS & ACC-25/50ZST ......................................................................................74
General Page Using Local/Integral Microphone ..................................................................................74
General Page Using Optional Remote Microphone .............................................................................75
Table of Contents
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 7
General Page Using the Optional RPJ-F Remote Keyswitch via the Optional Fire Fighter Telephone
Module..................................................................................................................................................75
Emergency Page Using Local/Integral Microphone ............................................................................75
Emergency Page Using Optional Remote Microphone........................................................................75
Emergency Page Using Optional RPJ-F Remote Keyswitch via the Optional Fire Fighter Telephone
Module..................................................................................................................................................75
4.5.11: Fire Fighter Telephone: ACC-25/50ZST Only ...............................................................................75
Communication on the Telephone Loop ..............................................................................................75
Annunciation of Remote Telephone Locations (MS-9600 or MS-9200UDLS only) ..........................76
4.5.12: Trouble Condition Response ...........................................................................................................76
4.5.13: Trouble Condition Restoral .............................................................................................................78
Section 5: Application Examples .......................................................................................... 80
5.1: One Speaker Circuit on ACC-25/50 ............................................................................................................80
5.2: One Speaker Circuit With Backup on ACC-25/50 ......................................................................................81
5.3: Two Speaker Circuits on ACC-25/50 ..........................................................................................................83
5.4: Two Speaker Circuits on ACC-25/50 ..........................................................................................................85
5.5: ACC-25/50ZS & ACC-25/50ZST Zone Splitting Applications..................................................................87
5.5.1: 25 Watt Zone Splitting - Eight Speaker Circuits, Style Y (Class B).................................................87
5.5.2: 25 Watt Zone Splitting - Four Speaker Circuits, Style Z (Class A) ..................................................89
5.5.3: 50 Watt Zone Splitting - Eight Speaker Circuits...............................................................................91
5.6: ACC-25/50 and ACC-25/50DA Installation ..............................................................................................93
5.7: 16 Theater Cineplex Utilizing ACC-25/50ZS With ACC-25/50DAZS ......................................................95
5.8: Audio Command Center 24 Zone System ...................................................................................................96
Section 6: Power Supply Calculations.................................................................................. 98
6.1: Overview......................................................................................................................................................98
6.2: Calculating the AC Branch Circuit..............................................................................................................98
6.3: Calculating the System Current Draw .........................................................................................................98
6.3.1: Overview ...........................................................................................................................................98
6.3.2: How to use Table 6.2 to calculate system current draws..................................................................99
6.4: Calculating the Battery Size ......................................................................................................................100
6.4.1: NFPA Battery Requirements ...........................................................................................................100
6.4.2: Selecting and Locating Batteries .....................................................................................................100
Appendix A: Digital Voice Messages..................................................................................102
Appendix B: Addressable Module Connections................................................................103
Appendix C: Wiring Requirements...................................................................................... 104
Appendix D: Programmed Activation by FACP ................................................................. 105
D.1: MS-9600, MS-9200UDLS and MS-9200UD ...........................................................................................106
D.1.1: Overview.........................................................................................................................................106
D.1.2: Basic MS-9600/MS-9200UD/MS-9200UDLS & ACC-25/50ZS/T Step-By-Step Install/Setup...106
D.1.3: Wiring From ACC-25/50ZS or ACC-25/50ZST to FACP.............................................................107
D.1.4: ACC-25/50ZS and ACC-25/50ZST Switch Settings .....................................................................108
D.1.5: FACP Programming .......................................................................................................................109
Programming Tips for MS-9600, MS-9600LD, MS-9200UDLS, and MS-9200UD.........................110
Message Assignment - Speaker Specific............................................................................................110
Message Assignment - Zone Specific ................................................................................................112
Fire Fighter Telephone SLC Point Assignment .................................................................................115
D.2: MS-5210UD..............................................................................................................................................118
D.2.1: Overview.........................................................................................................................................118
D.2.2: MS-5210UD Individual Zone Control With One or Two Messages..............................................118
ACC-25/50ZS/T DIP Switch Settings................................................................................................119
MS-5210UD Programming ................................................................................................................120
D.2.3: MS-5210UD All Zone Activation With One to Five Messages.....................................................120
ACC-25/50ZS and ACC-25/50ZST Switch Settings .........................................................................121
Table of Contents
8 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
ACM-8RF Programming....................................................................................................................121
MS-5210UD Programming ................................................................................................................121
D.3: MS-9200(E) ..............................................................................................................................................122
D.3.1: Overview.........................................................................................................................................122
D.3.2: Basic MS-9200 & ACC-25/50ZS/T Step-By-Step Install/Setup....................................................122
D.3.3: Wiring From ACC-25/50ZS or ACC-25/50ZST to MS-9200(E)...................................................124
ACC-25/50ZS & ACC-25/50ZST Switch Settings ............................................................................125
D.3.4: FACP Programming .......................................................................................................................125
D.4: MS-5UD-3/7 and MS-10UD-3/7 ..............................................................................................................127
D.4.1: Overview.........................................................................................................................................127
D.4.2: Basic ANN-BUS Step-By-Step Install/Setup .................................................................................127
D.4.3: ACC-ZPMK DIP Switch 1 Settings on ACC-25/50ZS and ACC-25/50ZST ................................128
D.4.4: Wiring From ACC-25/50ZS or ACC-25/50ZST to FACP.............................................................129
D.4.5: FACP Programming .......................................................................................................................130
Index ...................................................................................................................................... 138
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 9
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
Underwriters Laboratories Standard UL 864
NFPA 72 National Fire Alarm Code
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code
Note: Audible signal appliances used in public mode applications, are required to have
minimum sound levels of 75 dBA at 10 feet (3 meters) and a maximum level of 120 dBA
at the minimum hearing distance from the audible appliance.
To ensure that the appliance is clearly heard, the audible appliance sound level must be at
least 15 dBA above the average ambient sound level or 5 dBA above the maximum sound
level with a duration of at least 60 seconds, depending on which level is greater, with the
sound level being measured 5 feet (1.5 meters) above the floor.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1711 Amplifiers for Fire Protective Signaling Systems
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384
MS-5UD/10UD Series Technical Manual Document #52626
FCPS-24F(E) Field Charger/Power Supply Document #50079
FCPS-2404 Field Charger/Power Supply Document #51486
FCPS-24FS6/8 Field Charger/Power Supply Document #51883
MS-9200(C/E) Technical Manual Document #51003
MS-9200UD Technical Manual Document #51906
MS-9200UDLS Technical Manual Document #52750
MS-9600 Technical Manual Document #51335
MS-5210UD Technical Manual Document #50193
ACC-25/50DA Technical Manual Document #52265
SLC Wiring Manual Document #51309
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
Before proceeding, the installer should be familiar with the following documents.
10 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Audio Riser
25W Speaker Circuit
25W Speaker Circuit
Master Command Bus
FACP Control
ACC-25/50
FACP Control
Master Command Bus
Audio Riser
To Additional ACC-25/50DA Panels
25W Speaker Circuit
25W Speaker Circuit
25W Speaker Circuit
25W Speaker Circuit
ACC-25/50DA
ACC-25/50DA
ACC-25/50 System
Audio Command Center System Diagram
The FireVoice (ACC-25/50) can be used for systems
requiring up to 50 watts of audio power. Compatible
FACPs can be used for automatic control.
The Distributed Audio Panel (ACC-25/50DA) can
be used to increase audio power above 50 watts.
1. The FACP contorls the audio system via the CMD
inputs on the ACC-25/50 and ACC-25/50DA.
2. The Audio Riser connects the audio output of the
ACC-25/50 to each of the ACC-25/50DA(s).
3. The Master Command Bus provides an All-Call trigger
from the ACC-25/50 to the ACC-25/50DA(s).
accdadistsys.wmf
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 11
Audio Command Center Zone System
Up to 24 Zones @ 150W (max.)
Speaker Circuit #16
1. The FACP controls the audio system via the ACS Link or CMD
inputs on the ACC-25/50ZS
2. The Audio Riser connects the audio output of the ACC-25/50ZS to
each of the ACC-25/50DAZS(s) to distribute alarm or paging
audio.
3. The ACC-25/50ZS uses the Control Serial Link to control the
routing of the alarm or paging audio.
4. Riser conductors must be installed in accordance with the
survivability from attack by fire requirements in National Fire
Alarm Code, NFPA 72.
Speaker Circuit #9
Speaker Circuit #17
Speaker Circuit #24
ACC Control Serial Link (RS-485)
Audio Riser
Speaker Circuit #1
Speaker Circuit #8
ACC Control Serial Link (RS-485)
Automatic Control via the
ACS Link or CMD Input
ACC-25/50DAZS
ACC-25/50ZS
ACC-25/50DAZS
ACCDAZSDISTSYS2.wmf
Audio Riser
12 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Speaker Circuit #16
1. The FACP controls the audio system via the ACS Link or CMD
inputs on the ACC-25/50ZST.
2. The Audio Riser connects the audio output of the ACC-25/50ZST to
each of the ACC-25/50DAZS(s) to distribute alarm or paging audio.
3. The ACC-25/50ZST uses the Control Serial Link to control the
routing of the alarm or paging audio.
4. Riser conductors must be installed in accordance with the
survivability from attack by fire requirements in National Fire Alarm
Code, NFPA 72.
Speaker Circuit #9
Speaker Circuit #17
Speaker Circuit #24
ACC Control Serial Link (RS-485)
Audio Riser
Speaker Circuit #1
Speaker Circuit #8
ACC Control Serial Link (RS-485)
Automatic Control via the
ACS Link or CMD Input
ACC-25/50DAZS
ACC-25/50ZST
ACC-25/50DAZS
CDR
Audio Riser
RPJ-F
FPJ-F
up to 24 remote
FireFighter
Telephones
Audio Command Center Zone System With FireFighter Telephone
Up to 24 Zones @ 150W (max.)
ACCDAZSDISTSYS3.wmf
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 13
Section 1: Product Description
The ACC-25/50 Series consists of the AUDIO•COMMAND•CENTER•25/50 (ACC-25/50), the
AUDIO•COMMAND•CENTER•25/50 Zone System (ACC-25/50ZS), and the AUDIO•COM-
MAND•CENTER•25/50 Zone System with Telephone (ACC-25/50ZST) which are single channel,
25 watt, 25 VRMS, emergency voice evacuation panels. The ACC-25/50 provides up to two
speaker circuits while the ACC-25/50ZS and ACC-25/50ZST support up to eight speaker circuits.
Each panel provides the ability to record five field programmable messages (up to 60 seconds total
message duration) with an integral microphone or from an external audio source. An integral
power supply with battery charger supplies operational power. An ACC-AAM25 audio amplifier is
provided standard with each base unit. An optional second ACC-AAM25 amplifier is also avail-
able for backup purposes or to provide an additional channel of 25 watts. Optional 70 VRMS con-
version modules are also available for installations where 70 VRMS speakers are to be installed or
already exist. An optional External Page Module (ACC-EPM) is available for interfacing to nonfire
paging systems. The modular design allows for ease-of-serviceability.
Automatic activation of the ACC-25/50 by an FACP is possible via the five Command Input Cir-
cuits (CMD). The ACC-25/50ZS and ACC-25/50ZST can be automatically activated by the CMD
inputs or via the ACS serial communications link from the MS-9600, MS-9200UDLS, MS-
9200UD, MS-9200(E) and MS-5210UD FACPs.
Two Command Input Circuits can be independently field programmed for activation by an FACP
Notification Appliance Circuit reverse polarity or by closure of a supervised normally open contact
and three Command Input Circuits activate on contact closure. CMD 1 and CMD 2 provide termi-
nals for NAC input and output to allow installation of the audio panel anywhere along the NAC cir-
cuit being used to activate it. Options via the Command Inputs allow one 60 second message, two
30 second messages, three 20 second messages, four 15 second messages or five 12 second mes-
sages.
The ACC-25/50ZS and ACC-25/50ZST include an ACC-ZPMK Zone Page Module with keypad
and an ACC-ZSM Zone Splitter Module. These modules provide up to eight speaker circuits that
may be manually or automatically activated.
The ACC-25/50ZST includes an ACC-FFT Fire Fighter Telephone Module with keypad which
provides indications of phone activation, remote page activation, remote microphone activation and
corresponding trouble conditions. Additionally, up to 24 telephone circuits can be annunciated at
the ACC-FFT by connecting addressable monitor modules to the optional FPJ-F or RPJ-F Remote
Page Jacks.
Significant technological enhancements set the ACC-25/50 Series apart from other voice panels.
These enhancements include full supervision in both active (alarm or music) and standby condi-
tions. Supervision is provided for:
amplifier outputs
field wiring (shorts and opens)
message generator
all tone generators
microphone
telephones (optional)
If the message generator fails, the system automatically reverts to the primary tone generator. If the
primary tone generator fails, one of three backups become enabled.
Power is fed independently
to each amplifier so that a short circuit in one amplifier will not shut
down the other. Full output power of 25 watts per amplifier is generated while in a low battery con-
dition. Power is not diminished when the optional 70 V
RMS
transformer module is installed. Audio
is amplified utilizing modern integrated circuits as opposed to transformer technology. This pro-
vides for very low signal distortion for crystal clear audio.
14 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Product Description Product Features
Primary applications for the audio panels include structures such as restaurants, schools, auditori-
ums, places of worship, buildings with occupancies over 50, etc. The ACC-25/50 Series is
designed to interface directly to addressable or conventional fire alarm control panels or can be
used with the Audio Command Center Distributed Audio (ACC-25/50DA) panel to distribute audio
in systems that require more than 50 watts.
1.1 Product Features
25 watts of 25 V
RMS
audio power (expandable to 50 watts) per panel
Optional 70.7 V
RMS
conversion module available for each amplifier (note that speaker wiring
continues to be supervised in standby, alarm and when background music is playing with this
option module installed)
Modular design for maximum system flexibility
Unobstructed module access and removable terminal blocks for ease of servicing and module
replacement
Designed to allow easy system expansion
Five Command Input Circuits:
CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification
Appliance Circuits (reverse polarity) or contact closures
CMD3, CMD4, and CMD5 are activated by contact closures
Speaker Circuits
single Style Y or Z speaker circuit (one ACC-AAM25 Audio Amplifier provided with base
unit)
two Style Y or Style Z speaker circuits (with optional second ACC-AAM25 Audio
Amplifier installed)
eight Style Y or four Style Z speaker circuits (only on ACC-25/50ZS or ACC-25/50ZST
Panel with ACC-ZSM Zone Splitter Module)
ACC-25/50ZS and ACC-25/50ZST can be controlled by an FACP via the ACS (EIA-485) link
to the ACC-ZPMK. ACS compatible FACPs include the MS-9600, MS-9200(E), MS-
9200UD, MS-9200UDLS and MS-5210UD.
Integral supervised microphone
Microphone time-out feature which reverts back to prerecorded message if emergency page
exceeds three minutes
Standard, prerecorded message:
“May I have your attention please. May I have your attention please. The signal you
have just heard indicates a report of a fire in this building. Please proceed to the nearest
exit and leave the building. Do not re-enter the building unless directed to do so by the
proper authorities.”
Field-selectable message and custom message field recording capability using local
microphone or two compatible audio input jacks
Two External Audio Inputs for recording custom message from compatible source or playing
music over the system with prior approval of the local Authority Having Jurisdiction (AHJ)
Multiple duration message capability: one 60 second, two 30 second, three 20 second, four 15
second or five 12 second custom messages
Integral tone generators field selectable for steady, slow-whoop, high-low or chime tones
Higher wattage capability available by using the Audio Command Center Distributed Audio
(ACC-25/50DA) panel
Powered by integral AC power supply or batteries during AC fail
Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss
Piezo sounder for local trouble
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 15
Product Features Product Description
Two Form-C trouble relays:
System Trouble Relay - TB1
AC Power Loss Relay - TB7
35 mA Special Application (auxiliary power) output for addressable modules when interfaced
with the Fire•Lite MS-9200(E) or MS-9600 FACP or equivalent and End-of-Line power
supervision relays
Integral Dress Panel
Optional ACC-TR semi-flush trim ring
ACC-FFT Fire Fighter Telephone module for control and annunciation of up to 24 remote
telephone jacks (installation in ACC-25/50ZST only)
Fire Fighter Handset (FHS-F) used to communicate over the telephone circuit connected to the
ACC-FFT (ACC-25/50ZST only)
Fire Fighter Phone Jack FPJ-F provides plug-in location for the FHS-F (ACC-25/50ZST only)
Remote Page Jack RPJ-F provides plug-in location for the FHS-F and All-Call paging
capability (ACC-25/50ZST only)
Fire Fighter Handset Cabinet FHSC-RF (recess mount) or FHSC-SF (surface mount) is used to
store five Fire Fighter Handsets (FHS-F) (ACC-25/50ZST only)
Optional FC-RM Remote Microphone (includes cabinet and FC-MIM Microphone Interface
Module). Refer to the FC-RM Product Installation Document #51247 for additional
information
Optional ACC-EPM External Page Module for interfacing to non-fire paging systems
Optional local playback speaker (FC-LPS)
System Status LEDs (refer to “Controls and Indicators” on page 23)
Master Command Bus output for All-Call paging control of Distributed Audio panels in non-
zone split systems
16 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Product Description Product Features
AUX
POWER
CMD1
CMD2
CMD3
CMD4
CMD5
MASTER
CMD OUT
AC LOSS
TB4
TB2 TB5
TB8
TB9
TB10
TB6
TB7
P1
TB1
NC NO C
C NO NC
1 2
1 2 3
1 2 3 4 1 2 3 4 1 2 3 4
Form-C AC
Loss Relay
nonsupervised
Programmable
Output Trigger -
(supervised, power-
limited) activation by
Emergency and
Nonemergency
paging - active
polarity shown
4.7K ELR ½ watt
P/N: 27072
+ + - -
+ -
Special
Application
Power 35 mA
(nonsupervised,
power-limited)
- + + -
CMD1 Input
Trigger by contact
closure or NAC
reverse polarity
(ELR required) -
alarm polarity
shown
OUT IN
CMD2 Input
Trigger by contact
closure or NAC
reverse polarity
(ELR required) -
alarm polarity
shown
OUT IN
Form-C Trouble
Relay
(nonsupervised)
Connector P5
FC-MIM or
ACC-FFT
Local Speaker
Connector
RCA Jack
Local Microphone
Connector
HOT
NEUTRAL
EARTH
Connector for
Transformer
ac25mnt1.wmfR
AC Power Only (supervised,
nonpower-limited)
Refer to AC Power in Section
“Specifications” on page 19
Personal
Computer
Source
- + + -
+ -
+ -
+ -
CMD3, CMD4 & CMD5 Input
Trigger by contact closure
alarm polarity shown (inputs only)
ACC-ZSM
All CMD inputs are supervised, power-limited. When contact closure is
employed, a 4.7K ELR, P/N: 27072 is required.
(supervised,
nonpower-limited)
Figure 1.1 Audio Command Center Board
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 17
Product Features Product Description
!
CAUTION: OBSERVE PROPER POLARITY
MATCH PROPER POLARITY CONNECTIONS TO FIELD WIRING AND SPEAKERS. POLARITY
SHOWN IS IN THE STANDBY AND ALARM CONDITIONS.
J1
TB1 TB2
P1
SW1
BACK-UP ON
CKT TBL
AMP SUPV
J1
TB1 TB2
P1
SW1
BACK-UP ON
CKT TBL
AMP SUPV
J1
TB2
TB2
TB1 TB1
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4
1 2 3 4
S2
S1
BACK-UP ON
+ - + -
+ - + -
S4
AC25MNT2.wmf
+ - + -
+ - + -
Speaker Circuits are supervised
and power-limited
ELR Resistor required only for
Style Y (Class B) circuits.
4.75 K, 1 watt P/N: 75470
Figure 1.2 Command Board With Amplifiers
Backup Audio
In Out
Backup Audio
In Out
Optional 2nd or
Backup Amplifier
ACC-AAM25
Field
Programmable
Option Switches
S3, S5, and S1
Controls and
System Status
Indicators
(Switch S1 of 2nd amplifier
shown in Backup ‘OFF’ condition
FC-XRM70
Optional 70.7 VRMS Plug-in
Conversion Module
(available for each amplifier)
Battery Charger
Disable Switch
(switch shown for
charger enabled)
LEDs on each amplifer
Amp
Supervision
Circuit
Trouble
Standard
Main Amplifier #1
ACC-AAM25
18 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Product Description Product Features
ACC-25/50ZS Modules
TB1 TB2
P1
SW1
BACK-UP ON
CKT TBL
AMP SUPV
J1
TB1 TB2
P1
SW1
BACK-UP ON
CKT TBL
AMP SUPV
J1
TB1
J1
1 2 3 4 5 6 7 8
ON
S1
ON
S3
0
5
4
3
2
1
9
8
7
6
0
5
4
3
2
1
9
8
7
6
S2
TENS
ONES
AAM
1 & 2
AAM1
JP1
TB1
TB9
TB4
SW2
SW1
TB5
TB6
CLASS A
CLASS B
1 2 3 4 5 6 7 8
ON
S1
S3
0
5
4
3
2
1
9
8
7
6
0
5
4
3
2
1
9
8
7
6
S2
AAM
1 & 2
AAM1
SW2
SW1
TB1
TB9
TB4
TB5
TB6
+ -
+ -
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
TB1
TB2
TB1
TB4
TB5
TB6
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
-
Figure 1.3 ACC-25/50ZS Main Board With Modules
AC25ZSMNTa.wmf
1 2 3 4 1 2 3 4
Circuits are power-limited and
supervised and require ELRs
4.75K P/N: 27589
1 2 3 4
1 2 3 4
1 2 3 4
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
Speaker Circuits are
supervised, power-limited
supervised
(nonsupervised)
Style Y (Class B)
To Speakers
To Speakers
To Speakers
To Speakers
To Speakers
To Speakers
To Speakers
shield
shield
shield
shield
Dummy Load all
unused circuits with
4.75 K resistor
Style Z (Class A)
To Speakers
shield
Speaker Return
Page
Active
LED
To Speakers
shield
Speaker Return
To Speakers
shield
Speaker Return
To Speakers
shield
Speaker Return
Jumper all unused circuits:
+ to + and - to -
Field Programmable
Option Switches for
Speaker Circuits
ACS Addressing
Switches for EIA-485
Communications with
FACP
ON
TENS ONES
ACC-ZPMK
Zone Page Module
ACS (EIA-485)
Link to FACP
to ACS devices down-stream
ACC-EPM
External Page Module
Class A
Class B
from external page
system audio
(600, 700 mV
RMS
)
contact closure
from external
page system
Select 4 Class
A or 8 Class B
Speaker
Circuits
(shown for 8
Class B
Speaker
Circuits)
To Amplifier #1
To Amplifier #2
Select Single
or Split
Amplifier
Configuration
(shown set for
Split Amplifier
configuration)
ACC-ZSM
Zone Splitter
Module
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 1
Zone 2
Zone 3
Zone 4
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 19
Specifications Product Description
ACC-25/50ZST with ACC-FFT Module
1.2 Specifications
AC Power - TB3
ACC-25/50, ACC-25/50ZS, ACC-25/50ZST: 120 VAC, 60 Hz, 1.5 amp.
Wire size: minimum #14 AWGb with 600 V insulation.
AC Loss Relay - TB7
Operation: normally energized fail-safe relay transfers on AC power loss for independent monitor-
ing by DACT. AC Loss Relay can be programmed to be the only indication of an AC loss condi-
tion (see Table 2.3 on page 34).
AC Loss relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.6 amps @ 30 VAC (resistive)
TB1 TB2
P1
SW1
BACK-UP ON
CKT TBL
AMP SUPV
J1
TB1 TB2
P1
SW1
BACK-UP ON
CKT TBL
AMP SUPV
J1
1 2 3 4 5 6 7 8
ON
S1
ON
S3
0
5
4
3
2
1
9
8
7
6
0
5
4
3
2
1
9
8
7
6
S2
TENS
ONES
AAM
1 & 2
AAM1
JP1
TB1
TB9
TB4
SW2
SW1
TB5
TB6
CLASS A
CLASS B
SW1
J1
TB1
TB2
TB3
FFT 1
FFT 2
FFT 3
FFT 4
FFT 5
FFT 6
FFT 7
FFT 8
FFT 9
FFT 10
FFT 11
FFT 12
FFT 13
FFT 14
FFT 15
FFT 16
FFT 17
FFT 18
FFT 19
FFT 20
FFT 21
FFT 22
FFT 23
FFT 24
SW1
TB1
TB2
TB3
J3
J2
J1
1 2 3 4 5 6
1 2 3 4 5 6
1 2
SW2
Figure 1.4 ACC-25/50ZST Main Board with ACC-FFT Module
AC25ZSTMNTa.wmf
Dark stripe on
ribbon cable must
be positioned to
left as shown!!
Remote
Microphone
Wiring
Power
Grnd
+ Audio
- Audio
Earth
Remote Page
Jack Keyswitch
used for All-Call
Phone Paging
(4.7K ELR
required after
last RPJ
Keyswitch or at
TB2 if
Keyswitch is
not used)
Class A Class B
Return Out
+ shld - + shld -
Audio Wiring to
Remote Page
Jack (4.7K ELR
required after last
RPJ for Class B
wiring only)
switch position
shown for
2-wire Class B
telephone
connection
2-wire
4-wire
(ribbon cable is required when
annunciating remote Fire Fighter
Telephone locations)
to P5
on
main
board
Panel FFT
Handset
Connector
(side view)
Fire Fighter
Telephone Module
REMOTE MIC INSTALLED
switch position shown
for remote
microphone installed
Zone Page Module
Ribbon
Cable from
J3 on back
of
to P4 on
back of
20 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Product Description Specifications
Battery (lead acid only) - P10
Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.800 amp
Maximum Charger Capacity: 18 Amp Hour battery. (Audio Command Center Series cabinet holds
max. 18 Amp Hour Battery.
Command Input Circuits (alarm polarities shown)
CMD1 - TB2 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output
terminals which provide feed through of the NAC circuits to NAC devices down stream
CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output
terminals which provide feed through of the NAC circuits to NAC devices down stream
CMD3 - TB8 Terminals 1(+) & 2(-) are input terminals for contact closure only
CMD4 - TB9 Terminals 1(+) & 2(-) are input terminals for contact closure only
CMD5 - TB10 Terminals 1(+) & 2(-) are input terminals for contact closure only
Operation: CMD1 & CMD2 circuits are independently field programmable to activate amplifiers
on NAC polarity reversal or contact-closure. IMPORTANT! When CMD1 and CMD2 are config-
ured for reverse polarity, the NAC cannot
be Coded.
CMD3, CMD4 and CMD5 are fixed to activate on contact closure only. End-of-Line resistors must
be connected in all configurations.
Power-limited and supervised circuitry
Normal Operating Voltage Range: 10.5 VDC - 29 VDC; Maximum Voltage: 29 VDC
NAC Reverse Polarity Current (requires End-of-Line Resistor from NAC): 1.6 mA maximum.
Contact Closure Operation Current (requires 4.7K, ½ watt End-of-Line Resistor P/N 27072): 6.6
mA maximum
Maximum Wiring Impedance CMD1 - CMD5 (Contact Closure Operation): 200
Maximum Input Impedance:
CMD1 & CMD2 (Reverse Polarity Operation): 20K
CMD1 - CMD5 (Contact Closure Operation): 3.4K
Audio Amplifier Module
Standard ACC-AAM25 Amplifier plugs into P4 of main circuit board, optional ACC-AAM25
Amplifier plugs into P3 of main circuit board
Backup Audio - TB2 [In Terminals 1(+) & 2(-), Out Terminals 3(+) & 4(-)] on Amplifier Module
Operation: When TB2 is wired between the two amplifiers of a panel, the optional amplifier pro-
vides backup to the standard amplifier. Switch S1 on the backup amplifier must be 'ON' and jump-
ers placed from backup amplifier TB2 Terminal 3 to standard amplifier TB2 Terminal 1 and from
backup amplifier TB2 Terminal 4 to standard amplifier TB2 Terminal 2. Refer to Section “One
Speaker Circuit With Backup on ACC-25/50” on page 81, for additional information.
Speaker Circuit - TB1 Terminals 3(+) & 4(-) Style Y, 5(+) & 6(-) Style Z, 1 & 2 Shield (Standby
and Alarm Polarity Shown) on Amplifier Module
Power-limited circuitry
Operation: Circuit can be wired Style Y or Style Z
Normal Operating Voltage: 25 V
RMS
@ 1 amp max. and maximum Load Impedance of 25
(70.7 V
RMS
@ 350 mA max. with maximum Load Impedance of 200operation possible by plug-
ging optional FC-XRM70 conversion module into P1 of audio amplifier).
Circuit wiring is supervised during standby, alarm and when background music is playing
Output Power: 25 watts (20 watts when background music is employed);
Frequency Range: 800Hz - 2,800Hz
Maximum total capacitance for each speaker circuit: 250 µF.
End-of-Line Resistor required for Style Y circuit: 4.75 K, 1 watt (P/N: 75470)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144

Fire-Lite ACC-25 User manual

Category
Grass trimmers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI