Symbols, Contents
PROFIBUS Networks
1
Topologies of SIMATIC NET PROFIBUS
Networks
2
Configuring Networks
3
Passive Components of RS–485 Networks
4
Active Components of RS–485 Networks
5
Passive Components for PROFIBUS–PA
6
Passive Components for Electrical Networks
7
Active Components for Optical Networks
8
Active Components for Wireless Networks
9
Testing PROFIBUS
A
Lightning and Surge Voltage Protection for
LAN Cables Between Buildings
B
Installing LAN Cables
C
Installing Instructions for SIAMTIC NET
PROFIBUS Plastic Fiber Optic with Simplex
Connenctors or BFOC Connectors and Pul-
ling Loop for the FO Standard Cable
D
Installing Network Components in Cubicles
E
Dimension Drawings
F
Operating Instructions ILM / OLM / OBT
G
General Information
H
References
I
SIMATIC NET – Support and Training
J
Glossary, Index
Manual
05/2000
6GK1970–5CA20–0AA1
Release 2
SIMATIC NET
PROFIBUS Networks
!
Danger
indicates that death, severe personal injury or substantial property damage will result if proper precau-
tions are not taken.
!
Warning
indicates that death, severe personal injury or substantial property damage can result if proper precau-
tions are not taken.
!
Caution
indicates that minor personal injury or property damage can result if proper precautions are not taken.
Note
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.
Qualified Personnel
Only qualified personnel should be allowed to install and work on this equipment Qualified persons are
defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and sy-
stems in accordance with established safety practices and standards.
Correct Usage
Note the following:
!
Warning
This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers which
have been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed cor-
rectly, and operated and maintained as recommended.
Trademarks
SIMATICR, SIMATIC HMIR and SIMATIC NETR are registered trademarks of SIEMENS AG.
HCS is a registered trademark of EnsignBickford Optics Company.
Third parties using for their own purposes any other names in this document which refer to trademarks
might infringe upon the rights of the trademark owners.
Safety Guidelines
We have checked the contents of this manual for agreement with the hard-
ware and software described. Since deviations cannot be precluded entirely,
we cannot guarantee full agreement. However, the data in this manual are
reviewed regularly and any necessary corrections included in subsequent
editions. Suggestions for improvement are welcomed.
Disclaimer of LiabilityCopyright Siemens AG 1999 All rights reserved
The reproduction, transmission or use of this document or its contents is not
permitted without express written authority. Offenders will be liable for
damages. All rights, including rights created by patent grant or registration of
a utility model or design, are reserved.
Siemens AG
Bereich Automatisierungs und Antriebstechnik
Geschäftsgebiet Industrielle Kommunikation
Postfach 4848, D-90327 Nürnberg
E Siemens AG 1999
Subject to technical change.
Siemens Aktiengesellschaft Order no. 6GK 19705AC200AA1
i
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Symbols
PROFIBUS 830–1 T connecting cable
PROFIBUS 830-2 connecting cable
LAN cable (twisted-pair)
Duplex FO cable
Wireless transmission (infrared)
Bus connector
S7–300
S7–400
ET200S
OP25
ET 200M (with IM 153–2 FO)
PG/PC/OP
AS-i branch
Symbols
ii
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Optical link module (OLM)
Optical bus terminal (OBT)
Infrared link module (ILM)
Repeater
Contents
iii
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Contents
1 PROFIBUS NETWORKS 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Local Area Networks in Manufacturing and Process Automation 1-2. . . . . . .
1.1.1 General Introduction 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.2 Overview of the SIMATIC NET System 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Basics of the PROFIBUS Network 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 Standards 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Access Techniques 1-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3 Transmission Techniques 1-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.4 Transmission Techniques According to EIA Standard RS-485 1-10. . . . . . . . .
1.2.5 Transmission Techniques for Optical Components 1-12. . . . . . . . . . . . . . . . . . .
1.2.6 Transmission Technique for Wireless Infrared Technology 1-14. . . . . . . . . . . . .
1.2.7 Transmission Technique for PROFIBUS-PA 1-15. . . . . . . . . . . . . . . . . . . . . . . . .
2 Topologies of SIMATIC NET PROFIBUS Networks 2-1. . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Topologies of RS-485 Networks 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1 Components for Transmission Rates up to 1.5 Mbps 2-3. . . . . . . . . . . . . . . .
2.1.2 Components for Transmission Rates up to
12 Mbps 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Topologies of Optical Networks 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Topology with Integrated Optical Interfaces 2-6. . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2 Topologies with OLMs 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.3 Combination of Integrated Optical Interfaces and OLMs 2-13. . . . . . . . . . . . . .
2.3 Topologies of Wireless Networks 2-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Topologies with PROFIBUS-PA 2-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 Connectivity Devices 2-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.1 DP/DP Coupler 2-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.2 Connecting to PROFIBUS-PA 2-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.3 DP/PA Coupler 2-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.4 DP/PA Link 2-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.5 Connecting PROFIBUS-DP to RS-232C 2-28. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.6 Connecting with the DP/AS-Interface Link 65 2-30. . . . . . . . . . . . . . . . . . . . . . .
2.5.7 Connecting with the DP/AS-Interface Link 20 2-33. . . . . . . . . . . . . . . . . . . . . . . .
2.5.8 Connecting PROFIBUS-DP to instabus EIB 2-36. . . . . . . . . . . . . . . . . . . . . . . . .
3 Configuring Networks 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Configuring Electrical Networks 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Segments for Transmission Rates up to a Maximum of 500 Kbps 3-3. . . . . .
3.1.2 Segments for a Transmission Rate of 1.5 Mbps 3-4. . . . . . . . . . . . . . . . . . . . .
3.1.3 Segments for Transmission Rates up to a Maximum of
12 Mbps 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.4 Configuring Electrical Networks with RS-485 Repeaters 3-9. . . . . . . . . . . . . .
3.2 Configuring Optical Networks 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 How a Fiber-Optic Cable Transmission System Works 3-12. . . . . . . . . . . . . . .
3.2.2 Optical Power Budget of a Fiber-Optic Transmission System 3-14. . . . . . . . . .
3.2.3 Cable Lengths for Plastic and PCF FO Paths 3-17. . . . . . . . . . . . . . . . . . . . . . .
3.2.4 Calculating the Power Budget of Glass Fiber Optical Links with OLMs 3-18. .
Contents
iv
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3.3 Transmission Delay Time 3-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Configuring Optical Buses and
Star Topologies with OLMs 3-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2 Configuring Redundant Optical Rings with OLMs 3-27. . . . . . . . . . . . . . . . . . . .
3.3.3 Example of Configuring the Bus Parameters in STEP 7 3-31. . . . . . . . . . . . . . .
4 Passive Components for RS-485 Networks 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 SIMATIC NET PROFIBUS Cables 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 FC Standard Cable 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 FC-FRNC Cable (LAN cable with halogen-free outer sheath) 4-8. . . . . . . . . .
4.1.3 FC Food Cable 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.4 FC Robust Cable 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.5 PROFIBUS Flexible Cable 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.6 FC Underground Cable 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.7 FC Trailing Cable 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.8 PROFIBUS Festoon Cable 4-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.9 SIENOPYR-FR Marine Cable 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 FastConnect Bus Connector 4-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1 The FastConnect System 4-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2 Area of Application and Technical Specifications of the FastConnect Bus
Connector 4-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.3 Using the FastConnect Stripping Tool for Preparing FC Cables 4-30. . . . . . . .
4.3 Bus Connectors 4-32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.1 Area of Application and Technical Specifications of the Bus Connector 4-33. .
4.4 Attaching the LAN Cable to the Bus Connector 4-37. . . . . . . . . . . . . . . . . . . . . .
4.4.1 Attaching the LAN Cable to Bus Connector (6ES7 972-0B.11..) 4-37. . . . . . . .
4.4.2 Connecting the LAN Cable to Bus Connector (6ES7 972-0BA30-0XA0) 4-40.
4.4.3 Connecting the LAN Cable to Bus Connector (6ES7 972-0B.40) 4-42. . . . . . .
4.5 Installing the Bus Connector with Axial Cable Outlet 4-44. . . . . . . . . . . . . . . . . .
4.6 Plugging the Bus Connector into the Module 4-46. . . . . . . . . . . . . . . . . . . . . . . .
4.7 Bus Terminals for RS-485 Networks 4-48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.1 Versions 4-48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.2 Design and Functions of the RS-485 Bus Terminal 4-49. . . . . . . . . . . . . . . . . . .
4.7.3 Design and Functions of the 12M Bus Terminal 4-52. . . . . . . . . . . . . . . . . . . . . .
4.7.4 Mounting/Attaching the LAN Cables 4-55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.5 Grounding 4-58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.6 Technical Data of the RS-485 Bus Terminal 4-60. . . . . . . . . . . . . . . . . . . . . . . . .
4.7.7 Technical Data of the 12M Bus Terminal 4-61. . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8 Cable Connections 4-63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8.1 Cable Connections to Network Components 4-63. . . . . . . . . . . . . . . . . . . . . . . .
4.8.2 Cable Connection without Bus Connection Elements 4-63. . . . . . . . . . . . . . . . .
4.9 Preassembled Connecting Cables 4-65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.9.1 830-1T Connecting Cable 4-65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.9.2 830-2 Connecting Cable 4-67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Active Components for RS-485 Networks 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 RS-485 Repeater 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Possible Configurations with the RS-485 Repeater 5-6. . . . . . . . . . . . . . . . . . .
Contents
v
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
5.3 Installing and Uninstalling the RS-485 Repeater 5-9. . . . . . . . . . . . . . . . . . . . .
5.4 Ungrounded Operation of the RS-485 Repeater 5-12. . . . . . . . . . . . . . . . . . . . .
5.5 Connecting the Power Supply 5-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6 Connecting the LAN Cable 5-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7 PROFIBUS Terminator 5-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Passive Components for PROFIBUS-PA 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 FC Process Cable 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 SpliTConnect Tap 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Passive Components for Electrical Networks 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 Fiber-Optic Cables 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Plastic Fiber-Optic Cables 7-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.1 Plastic Fiber Optic, Duplex Cord 7-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.2 Plastic Fiber-Optic, Standard Cables 7-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.3 PCF Fiber-Optic Cables 7-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 Glass Fiber-Optic Cables 7-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.1 Fiber-Optic Standard Cable 7-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.2 INDOOR Fiber-Optic Cable 7-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.3 Flexible Fiber-Optic Trailing Cable 7-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.4 SIENOPYR Duplex Fiber-Optic Marine Cable 7-22. . . . . . . . . . . . . . . . . . . . . . .
7.3.5 Special Cables 7-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4 Fiber-Optic Connectors 7-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.1 Connectors for Plastic Fiber-Optic Cables 7-26. . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.2 Simplex Connector and Adapter for Devices with Integrated Optical Interfaces .
7-26
7.4.3 BFOC Connectors for OLMs 7-30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.4 Connectors for Glass Fiber Cables 7-30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Active Components for Optical Networks 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1 Optical Bus Terminal OBT 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 Optical Link Module OLM 8-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 Active Components for Wireless Networks 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1 Infrared Link Module ILM 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A Testing PROFIBUS A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Hardware Test Device BT200 for PROFIBUS-DP A-2. . . . . . . . . . . . . . . . . . . .
A.1.1 Possible Uses A-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1.2 Area of Application A-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1.3 Logging Functions A-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1.4 Design A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1.5 Functions A-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1.6 How the Unit Functions A-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Testing FO Transmission Paths A-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2.1 Necessity of a Final Test A-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2.2 Optical Power Source and Meter A-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2.3 Optical Time Domain Reflectometer (OTDR) A-9. . . . . . . . . . . . . . . . . . . . . . . .
Contents
vi
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
A.2.4 Checking the Optical Signal Quality with PROFIBUS OLM V3 A-12. . . . . . . . .
B Lightning and Surge Voltage Protection for LAN Cables Between Buildings B-1
B.1 Why Protect Your Automation System From Overvoltage? B-2. . . . . . . . . . . .
B.2 Protecting LAN Cables from Lightning B-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.2.1 Instructions for Installing Coarse Protection B-5. . . . . . . . . . . . . . . . . . . . . . . . .
B.2.2 Instructions for Installing Fine Protection B-6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.2.3 General Information on the Lightning Protection Equipment from the Firm of
Dehn & Söhne B-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C Installing LAN Cables C-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.1 LAN Cables in Automation Systems C-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.2 Electrical Safety C-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.3 Mechanical Protection of LAN Cables C-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.4 Electromagnetic Compatibility of LAN Cables C-7. . . . . . . . . . . . . . . . . . . . . . .
C.4.1 Measures to Counter Interference Voltages C-7. . . . . . . . . . . . . . . . . . . . . . . . .
C.4.2 Installation and Grounding of Inactive Metal Parts C-8. . . . . . . . . . . . . . . . . . .
C.4.3 Using the Shields of Electrical LAN Cables C-8. . . . . . . . . . . . . . . . . . . . . . . . . .
C.4.4 Equipotential Bonding C-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.5 Routing Electrical LAN Cables C-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.5.1 Cable Categories and Clearances C-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.5.2 Cabling within Closets C-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.5.3 Cabling within Buildings C-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.5.4 Cabling outside Buildings C-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.5.5 Special Noise Suppression Measures C-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.6 Electromagnetic Compatibility of Fiber-Optic Cables C-20. . . . . . . . . . . . . . . . .
C.7 Installing LAN Cables C-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.7.1 Instructions for Installing Electrical and Optical LAN cables C-21. . . . . . . . . . . .
C.8 Additional Instructions on Installing Fiber-Optic Cables C-24. . . . . . . . . . . . . . .
D Installation Instructions for SIMATIC NET PROFIBUS Plastic Fiber-Optic with
Simplex Connectors or BFOC Connectors and Pulling Loop for the FO Standard
Cable D-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E Installing Network Components in Cubicles E-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E.1 IP Degrees of Protection E-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E.2 SIMATIC NET Components E-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F Dimension Drawings F-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F.1 Dimension Drawings of the Bus Connectors F-2. . . . . . . . . . . . . . . . . . . . . . . . .
F.2 Dimension Drawings of the RS-485 Repeater F-5. . . . . . . . . . . . . . . . . . . . . . .
F.3 Dimension Drawing of the PROFIBUS Terminator F-6. . . . . . . . . . . . . . . . . . .
F.4 Dimension Drawings of the RS-485 Bus Terminal F-7. . . . . . . . . . . . . . . . . . . .
F.5 Dimension Drawings of the BT12M Bus Terminal F-8. . . . . . . . . . . . . . . . . . . .
F.6 Dimension Drawings of the Optical Bus Terminal OBT F-9. . . . . . . . . . . . . . . .
Contents
vii
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
F.7 Dimension Drawings Infrared Link Module ILM F-11. . . . . . . . . . . . . . . . . . . . . .
F.8 Dimension Drawings Optical Link Module OLM F-12. . . . . . . . . . . . . . . . . . . . . .
G Operating Instructions ILM / OLM / OBT G-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H General Information H-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H.1 Abbreviations/Acronyms H-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I References I-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
J SIMATIC NET – Support and Training J-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary Glossary-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index Index-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
viii
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
PROFIBUS NETWORKS
1
PROFIBUS NETWORKS
1-2
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.1 Local Area Networks in Manufacturing and Process Automation
1.1.1 General Introduction
Communication Systems
The performance of control systems is no longer simply determined by the
programmable logic controllers, but also to a great extent by the environment in
which they are located. Apart from plant visualization, operating and monitoring,
this also means a high-performance communication system.
Distributed Systems
Distributed automation systems are being used increasingly in manufacturing and
process automation. This means that a complex control task is divided into smaller
“handier” subtasks with distributed control systems. As a result, efficient
communication between the distributed systems is an absolute necessity. Such
structures have, for example, the following advantages:
S Independent and simultaneous startup of individual sections of plant/system
S Smaller, clearer programs
S Parallel processing by distributed automation systems
This results in the following:
Shorter reaction times
Reduced load on the individual processing units
S System-wide structures for handling additional diagnostic and logging functions
S Increased plant/system availability since the rest of the system can continue to
operate if a substation fails.
A comprehensive, high-performance communication system is a must for a
distributed system structure.
PROFIBUS NETWORKS
1-3
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
SIMATIC NET
With SIMATIC NET, Siemens provides an open, heterogeneous communication
system for various levels of process automation in an industrial environment. The
SIMATIC NET communication systems are based on national and international
standards according to the ISO/OSI reference model.
The basis of such communication systems are local area networks (LANs) which
can be implemented in one of the following ways:
S Electrically
S Optically
S Wireless
S Combined electrical/optical/wireless
S Electrically, intrinsically safe
1.1.2 Overview of the SIMATIC NET System
SIMATIC NET is the name of the communication networks connecting SIEMENS
programmable controllers, host computers, work stations and personal computers.
SIMATIC NET includes the following:
S The communication network consisting of transmission media, network
attachment and transmission components and the corresponding transmission
techniques
S Protocols and services used to transfer data between the devices listed above
S The modules of the programmable controller or computer that provide the
connection to the LAN (communications processors “CPs” or “interface
modules”).
To handle a variety of tasks in automation engineering, SIMATIC NET provides
different communication networks to suit the particular situation.
The topology of rooms, buildings, factories, and complete company complexes and
the prevalent environmental conditions mean different requirements. The
networked automation components also make different demands on the
communication system.
To meet these various requirements, SIMATIC NET provides the following
communication networks complying with national and international standards:
PROFIBUS NETWORKS
1-4
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Industrial Ethernet/Fast Ethernet
A communication network for the LAN and cell area using baseband technology
complying with IEEE 802.3 and using the CSMA/CD medium access technique
(Carrier Sense Multiple Access/Collision Detection). The network is operated on
S 50 triaxial cable
S 100 Twisted pair cables
S Glass fiber-optic cable
AS-Interface
The actuator sensor interface (AS-i) is a communication network for automation at
the lowest level for connecting binary actuators and sensors to programmable logic
controllers via the AS-i bus cable.
PROFIBUS
A communication network for the cell and field area complying with EN 50170-1-2
with the hybrid medium access technique token bus and master slave. Networking
is on twisted pair, fiber-optic cable or wireless.
PROFIBUS-PA
PROFIBUS-PA is the PROFIBUS for process automation (PA). It connects the
PROFIBUS-DP communication protocol with the IEC 61158-2 transmission
technique.
PROFIBUS NETWORKS
1-5
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2 Basics of the PROFIBUS Network
EN 50170
SIMATIC NET PROFIBUS products and the networks they make up comply with
the PROFIBUS standard EN 50170 (1996). The SIMATIC NET PROFIBUS
components can also be used with SIMATIC S7 to create a SIMATIC MPI subnet
(MPI = Multipoint Interface).
Attachable Systems
The following systems can be connected:
S SIMATIC S5/S7/M7/C7 programmable controllers
S ET 200 distributed I/O system
S SIMATIC programming devices/PCs
S SIMATIC operator control and monitoring devices or systems
S SICOMP IPCs
S SINUMERIK CNC numerical controls
S SIMODRIVE sensors
S SIMOVERT master drives
S SIMADYN D digital control system
S SIMOREG
S Micro-/Midimasters
S SIPOS reversing power controllers/actuators
S SIPART industry/process controllers
S MOBY identification systems
S SIMOCODE low-voltage switchgear
S Circuit breakers
S SICLIMAT COMPAS compact automation stations
S TELEPERM M process control system
S Devices from other manufacturers with a PROFIBUS-compliant interface
PROFIBUS NETWORKS
1-6
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Transmission Media
PROFIBUS networks can be implemented with the following:
S Shielded, twisted pair cables (characteristic impedance 150 )
S Shielded, twisted pair cables, intrinsically safe (with PROFIBUS-PA)
S Fiber-optic cables
S Wireless (infrared technology)
The various communication networks can be used independently or if required can
also be combined with each other.
PROFIBUS NETWORKS
1-7
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2.1 Standards
SIMATIC NET PROFIBUS is based on the following standards and directives:
IEC 61158–2 to 6: 1993/2000
Digital data communications for measurement and control
Fieldbus for use in industrial control systems
EN 50170-1-2: 1996
General purpose field communication system
Volume 2 : Physical Layer Specification and Service Definition
PROFIBUS User Organization Guidelines:
PROFIBUS Implementation Guide to DIN 19245
Part 3 (Draft)
Version 1.0 dated 14.12.1995
Fiber Optic Data Transfer for PROFIBUS
Version 2.1 dated 12.98
EIA RS-485: 1983
Standard for Electrical Characteristics of Generators and
Receivers for Use in Balanced Digital Multipoint Systems
SIMATIC NET PROFIBUS-PA is based on the following standards and directives:
EN 50170-1-2: 1996
General Purpose Field Communication System
Volume 2 : Physical Layer Specification and Service Definition
IEC 61158-2: 1993
Fieldbus standard for use in industrial control systems
Part 2 : Physical layer specification and service definition
EN 61158-2: 1994
Fieldbus standard for use in industrial control systems
Part 2 : Physical layer specification and service definition
PTB-Bericht W-53: 1993
Untersuchungen zur Eigensicherheit bei Feldbussystemen
Braunschweig, March 1993
PNO-Richtlinie: 1996
PROFIBUS-PA Inbetriebnahmeleitfaden (Hinweise zur Nutzung
der IEC 61158-2-Technik für PROFIBUS, Art.-Nr. 2.091)
PROFIBUS NETWORKS
1-8
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2.2 Access Techniques
TOKEN BUS/Master-Slave Method
Network access on PROFIBUS corresponds to the method specified in EN 50170,
Volume 2 Token Bus for active and “Master-Slave” for passive stations.
Slave
Master
Token rotation
(logical ring)
Slave = passive node
Logical token ring
Master-slave relationship
Master
Master
Master
Master
Master = active node
Slave
Slave
Slave
Slave
Figure 1-1 Principle of the PROFIBUS Medium Access Technique
PROFIBUS NETWORKS
1-9
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Active and Passive Nodes
The access technique is not dependent on the transmission medium. Figure 1-1
Principle of the PROFIBUS Medium Access Technique shows the hybrid
technique with active and passive nodes. This is explained briefly below:
S All active nodes (masters) form the logical token ring in a fixed order and each
active node knows the other active nodes and their order in the logical ring (the
order does not depend on the topological arrangement of the active nodes on
the bus).
S The right to access the medium, the “Token”, is passed from active node to
active node in the order of the logical ring.
S If a node has received the token (addressed to it), it can send frames. The time
in which it is allowed to send frames is specified by the token holding time.
Once this has expired, the node is only allowed to send one high priority
message. If the node does not have a message to send, it passes the token
directly to the next node in the logical ring. The token timers from which the
maximum token holding time is calculated are configured for all active nodes.
S If an active node has the token and if it has connections configured to passive
nodes (master-slave connections), the passive nodes are polled (for example
values read out) or data is sent to the slaves (for example setpoints).
S Passive nodes never receive the token.
This access technique allows nodes to enter or leave the ring during operation.
1.2.3 Transmission Techniques
The physical transmission techniques used depend on the SIMATIC NET
PROFIBUS transmission medium:
S RS-485 for electrical networks on shielded, twisted pair cables
S Optical techniques according to the PROFIBUS User Organization guideline /3/
on fiber-optic cables
S Wireless techniques based on infrared radiation
S IEC 61158-2 technique for intrinsically safe and non-intrinsically safe electrical
networks in process control (PROFIBUS-PA) based on shielded, twisted pair
cables.
PROFIBUS NETWORKS
1-10
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2.4 Transmission Techniques According to EIA Standard RS-485
EIA Standard RS-485
The RS-485 transmission technique corresponds to balanced data transmission as
specified in the EIA Standard RS-485 /4/. This transmission technique is
mandatory in the PROFIBUS standard EN 50170 for data transmission on twisted
pair cables.
The medium is a shielded, twisted pair cable.
The bus cable is terminated at both ends with the characteristic impedance. Such
a terminated bus cable is known as a segment.
The attachment of the node to the bus is via a bus terminal with a tap line or a bus
connector (maximum 32 nodes per segment). The individual segments are
interconnected by repeaters.
The maximum length of a segment depends on the following:
S The transmission rate
S The type of cable being used
Advantages:
S Flexible bus or tree structure with repeaters, bus terminals, and bus connectors
for attaching PROFIBUS nodes
S Purely passive passing on of signals allows nodes to be deactivated without
affecting the network (except for the nodes that supply power to the terminating
resistors)
S Simple installation of the bus cable without specialized experience.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350
  • Page 351 351
  • Page 352 352
  • Page 353 353
  • Page 354 354
  • Page 355 355
  • Page 356 356
  • Page 357 357
  • Page 358 358
  • Page 359 359
  • Page 360 360
  • Page 361 361
  • Page 362 362
  • Page 363 363
  • Page 364 364
  • Page 365 365
  • Page 366 366
  • Page 367 367
  • Page 368 368
  • Page 369 369
  • Page 370 370
  • Page 371 371
  • Page 372 372
  • Page 373 373
  • Page 374 374
  • Page 375 375
  • Page 376 376
  • Page 377 377
  • Page 378 378
  • Page 379 379
  • Page 380 380
  • Page 381 381
  • Page 382 382
  • Page 383 383
  • Page 384 384
  • Page 385 385
  • Page 386 386
  • Page 387 387
  • Page 388 388
  • Page 389 389
  • Page 390 390
  • Page 391 391
  • Page 392 392
  • Page 393 393
  • Page 394 394
  • Page 395 395
  • Page 396 396
  • Page 397 397
  • Page 398 398
  • Page 399 399
  • Page 400 400
  • Page 401 401
  • Page 402 402
  • Page 403 403
  • Page 404 404
  • Page 405 405
  • Page 406 406
  • Page 407 407
  • Page 408 408
  • Page 409 409
  • Page 410 410
  • Page 411 411
  • Page 412 412
  • Page 413 413
  • Page 414 414
  • Page 415 415
  • Page 416 416
  • Page 417 417
  • Page 418 418
  • Page 419 419
  • Page 420 420
  • Page 421 421
  • Page 422 422
  • Page 423 423
  • Page 424 424
  • Page 425 425
  • Page 426 426
  • Page 427 427
  • Page 428 428
  • Page 429 429
  • Page 430 430
  • Page 431 431
  • Page 432 432
  • Page 433 433
  • Page 434 434
  • Page 435 435
  • Page 436 436
  • Page 437 437
  • Page 438 438
  • Page 439 439
  • Page 440 440
  • Page 441 441
  • Page 442 442
  • Page 443 443
  • Page 444 444
  • Page 445 445
  • Page 446 446
  • Page 447 447
  • Page 448 448
  • Page 449 449
  • Page 450 450
  • Page 451 451
  • Page 452 452
  • Page 453 453
  • Page 454 454
  • Page 455 455
  • Page 456 456
  • Page 457 457
  • Page 458 458
  • Page 459 459
  • Page 460 460
  • Page 461 461
  • Page 462 462
  • Page 463 463
  • Page 464 464
  • Page 465 465
  • Page 466 466
  • Page 467 467
  • Page 468 468
  • Page 469 469
  • Page 470 470
  • Page 471 471
  • Page 472 472
  • Page 473 473
  • Page 474 474
  • Page 475 475
  • Page 476 476
  • Page 477 477
  • Page 478 478
  • Page 479 479
  • Page 480 480
  • Page 481 481
  • Page 482 482
  • Page 483 483
  • Page 484 484
  • Page 485 485
  • Page 486 486
  • Page 487 487
  • Page 488 488
  • Page 489 489
  • Page 490 490

Siemens SIMATIC NET PROFIBUS Operating instructions

Category
Networking
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI