Greenheck 474111 Smoke Detector Hochiki Operating instructions

Type
Operating instructions
Ductmate
Connection
1.5 in. x 1.5 in.
Retaining Angle
Ductmate
Connection
5.75 in.
14 in.
21 in.
6 in. wall
maximum
Document Number 474111
Installation Instruction Supplement for
SMD, SMDR & SSSMD Series
Smoke Dampers and
FSD, FSD-3xxV and SSFSD Series
Combination Fire Smoke Dampers and
CFSD Series
Corridor Ceiling Dampers
Refer to:
'Installation Instructions for SMD, SMDR, and SSSMD
Series Leakage Rated Smoke Dampers' (Part # 461338)
or
'Installation Instructions for CFSD Series Corridor Ceiling
Dampers' (Part # 461335)
or
'Installation Instructions for FSD-xxx, DFD-xxx, and
SSFSD-xxx Series Combination Fire Smoke Dampers'
(Part # 481318) for additional details.
"UL CLASSIFIED (see complete marking on
product)"
"UL CLASSIFIED to Canadian safety standards (see
complete marking on product)"
Standard 555 (Listing #R13317)
Standard 555S (Listing #R13447)
Notes
1. Minimum air velocity for smoke detector operation is 300
fpm (1.5 m/s). Maximum is 4000 fpm (20.3 m/s).
2. Since the smoke detector is not rated for use at velocities
below 300 fpm (1.5 m/s), local code may require an
alternate means of damper closure such as zone detection
or automated damper closure when the system fan is
shut down. The local authority having jurisdiction should
be consulted prior to the in installation of the damper and
smoke detector.
3. Holes on sampling tube must face into the airstream.
4. Smoke detector specifications are:
Operating temperature range: 32°F to 100°F
(0°C to 38°C)
Operating humidity range: 10% to 85% R.H.
Operation voltage: 24 VAC/DC or 120 VAC
5. Refer to Hochiki Duct Smoke Detector installation
instructions.
6. Hochiki America Corporation
7051 Village Drive Suite 100
Buena Park, CA 90621-2268
Phone: 714-522-2246
Fax: 714-522-2268
Technical Support: 1-800-845-6692 or
Website: http://www.hochikiamerica.com
Figure 1: Smoke detector mounting orientation for
dampers less than 25 inches (635mm) in height.
DH-98-P Duct Smoke DetectorWiring Diagrams
Ductmate
Connection
1.5 in. x 1.5 in.
Retaining Angle
10.125 in.
21 in.
6 in.wall
maximum
Figure 2: Smoke detector mounting
orientation for dampers equal to or greater
than 25 inches (635mm) in height.
DH-98-P Duct Smoke DetectorWiring Diagrams
DH-98-P Duct Smoke DetectorWiring Diagrams
DH-98-P Duct Smoke DetectorWiring Diagrams
DH-98-P Duct Smoke DetectorWiring Diagrams
TOR 24 VAC/VDC
Figure 3: Label applied to dampers with factory mounted Hochiki duct smoke detectors.
Copyright © 2016 Greenheck Fan Corporation
474111 Hochiki Smoke Detector IOM Rev 3 April 2016
Smoke detector r equir es 300 fpm minimum
air velocity in duct. For damper activation
r equir ements when system velocity is less
than 300 fpm, the local authority having
jurisdiction should be consulted.
Refer to smoke detector installation
instructions and Gr eenheck IOM - Hochiki
SmokeDetector Supplement for dampers with
factory mounted duct smoke detectors.
DH-98-P Duct Smoke DetectorWiring Diagrams
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8