Carlon A243F-CAR User manual

Type
User manual
Carlon
®
Electrical Nonmetallic
Tubing (ENT)
Application Handbook
NEW
per the
‘02 NEC
© Carlon 2002.
All rights reserved.
The cover and entire contents of this handbook
are fully protected and may not be reproduced
in any manner without the expressed written
consent of Carlon.
1
www.carlon.com
Introduction
This pocket handbook is intended to be used as a guide
for the installer of the Carlon brand of Electrical Nonmetallic
Tubing (ENT) to answer general questions relating to
installation procedures. For information on part numbers or
pricing, please refer to to the appropriate Carlon catalog.
Should the installer develop any unique installation or
support methods not shown in this manual, please
photograph the method with a 35mm camera only and
contact your local Carlon sales representative.
THIS POCKET HANDBOOK IS INTENDED AS A GUIDE
FOR GENERAL PURPOSES ONLY. CARLON ACCEPTS NO
LIABILITY FOR ANY DAMAGES OR LOSS WHICH MAY
RESULT FROM IMPROPER INSTALLATION OF ENT.
Table of Contents
Section Page
1. General Information and Questions about ENT . . . . . . 2
2. Embedded ENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3. Wood and Metal Stud Construction . . . . . . . . . . . . . 17
4. Masonry Construction . . . . . . . . . . . . . . . . . . . . . . . . 23
5. Exposed Construction . . . . . . . . . . . . . . . . . . . . . . . . 25
6. Above a Suspended Ceiling . . . . . . . . . . . . . . . . . . . . 28
7. Boxes and Supports . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8. Field Expediency and Tips . . . . . . . . . . . . . . . . . . . . . 35
9. Tables, Charts, etc. (Reference type of tables) . . . . . . 40
10. Article 362 and Associated Articles . . . . . . . . . . . . . . 46
11. Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
12. Flex-Plus
®
Blue
ENT . . . . . . . . . . . . . . . . . . . . . . . . 70
2
www.carlon.com
Section 1
General Information
and Questions about Carlon
®
Flex-Plus
®
Blue
ENT
Features:
• UL Listed
• CSA Certified
• Lightweight
• Nonconductive
• Color-coded
• Hand bendable (pliable), no sharp edges
• Clean
Available in long-length coils and reels to reduce scrap
• Available in
1
/2 inch through 2 inch sizes
Available with a complete line of fittings and accessories
that are compatible with PLUS 40
®
, PLUS 80
®
PVC
Conduit and Schedule 40 fittings
• Easy to work with, no special tools required
• Speeds installation time
A time saver when pulling wire
When this handbook refers to ENT, it is referenced as
Carlon Flex-Plus Blue ENT as published in Carlon
catalogs
Complete size range
1
/2" through 2"
3
www.carlon.com
Questions about ENT
1. WHAT IS ENT?
ENT is a pliable, nonmetallic raceway manufactured of
the same material (PVC) used for rigid nonmetallic
conduit.
2. IS ENT UL LISTED?
Yes. See UL Listing No. E73317 for
1
/2 inch through 2 inch
ENT
3. IS ENT RECOGNIZED BY THE NEC?
Yes. See Article 362 (Article 331 of the NEC) – Electrical
Nonmetallic Tubing (see Section 10 of this manual.)
4. ARE THERE ANY OTHER NATIONAL
ORGANIZATIONS THAT RECOGNIZE THE USE
OF ENT?
Yes. CABO – The Council of American Building Officials.
5. HOW LONG HAS ENT BEEN IN EXISTENCE?
Carlon introduced ENT in 1980 and is presently the
largest manufacturer of all PVC conduit, boxes and
fittings.
6. WHAT IS THE FIRE RATING OF ENT?
BOCA, SBCCI and ICBO recognize the use of ENT in a one
and two hour fire rated Wall Assembly and up to a three
hour rated Floor/Ceiling Assembly. (Reference ER-5644 or
NER-290).
7. IS THERE ANY CONCERN REGARDING THE
TOXICITY OF ENT DURING A FIRE?
a. PVC raceways have never caused death in a fire
situation, however, improperly grounded steel raceways
have ignited fires by arcing and sparking.
b. Smoke from ENT raceways is no more hazardous than
smoke from other materials commonly used in the
4
www.carlon.com
construction and contents of a building such as
furniture, wall coverings, carpeting, drapes, wood, and
paper. Wool carpeting and upholstery produce deadly
hydrogen cyanide gas. Wood produces carbon
monoxide, a primary cause of fire deaths. These
materials ignite at a much lower temperature than ENT.
c. Various tests conducted by combustion toxicologists,
third party certifying agencies, and testing laboratories
conclusively prove:
• PVC Raceways DO NOT generate HCI (Hydrogen
Chloride) in lethal concentrations.
• In an actual large scale fire test, PVC conduit
maintained the integrity of electrical circuits, even in
the case of flashover.
• In a fire situation, PVC conduit will protect the
integrity of conductors significantly longer than steel
conduit.
• PVC is a practical conduit material.
• Metallic conduit systems do not guard against fire
ignition (may promote arcing if not properly
grounded.)
• PVC conduit is superior to metallic conduit in most
applications.
• Since both metallic and nonmetallic raceways are
recognized by NEC, the buyer can decide which
product is best suited to the installation requirement.
A real concern for life safety in fires must be directed
toward eliminating fire ignition, providing better
control of burnables in the room and priding state-
of-the-art fire protection and sprinkler systems. These
are the goals of many recognized fire authorities.
8. HOW EASY IS ENT TO HANDLE ON THE JOB?
Let’s take a look:
1
/2 inch ENT weighs 11 pounds per 100 feet.
1
/2 inch EMT weighs 29 pounds per 100 feet
(or one bundle).
You can easily carry two coils of ENT (200 feet per coil)
weighing 44 pounds, compared to 4 bundles of EMT
(10 feet long per bundle) weighing 116 pounds.
5
www.carlon.com
Let’s look at the sizes:
A 200 foot coil of ENT is 22" 22" square 8
1
/2"
deep.
A 200 foot bundle of EMT is 10' long by approximately
20" in circumference.
Now how easy is it for one man to carry 200 feet of EMT
conduit and negotiate stairways and hallways? Try this
same experiment with Carlon ENT. It’s much easier isn’t it?
9. HOW EASY IS ENT TO INSTALL?
Very easy! All that is needed for installation is a Carlon
conduit cutter, an electrician’s knife or utility knife, tiewraps
or tiewire, and a pair of side cutter pliers. That’s all!
Contractors have said that Carlon ENT can be installed in
half the time of installing comparable EMT conduit.
10. WHAT DOES CARLON OFFER WHEN USING
ENT FOR COMMUNICATIONS AND FIRE
PROTECTION SYSTEMS?
Carlon also offers yellow and red ENT. All ENT must be
installed in accordance with NEC Article 362 (see Section
10 of this manual).
One Piece Quick Connect Fitting
Simple as 1-2-3 (Illustration 1-6-1)
1. Cut (No need to
ream or deburr)
2. Snap on Terminator
to ENT
2. Snap in Terminator
to Box
Done. Elapsed time: Less than 15 seconds
Tools: Carlon conduit cutter
ENT
tubing
Conduit
Cutter
One piece
connector
6
www.carlon.com
11. WHAT KIND OF ENT FITTINGS DOES CARLON
OFFER?
Carlon offers a complete line of one piece quick connect
fittings in sizes
1
/2 inch through 1 inch. For ENT sizes 1
1
/4
inch through 2 inch, the use of PVC Schedule 40 cemented
fittings is necessary. Carlon also offers PVC cemented
fittings for
1
/2 inch through 1 inch.
12. HOW EASY IS IT TO PULL WIRE THROUGH ENT?
Very easy! In fact, a field test showed that it required only
1.5 minutes for an electrician to push through 3-No. 12
wires through 40 feet of
1
/2 inch ENT with the equivalent
of four 90˚ bends. Remember, the corrugated construction
of ENT allows only one-half of the total length of installed
ENT to be in direct contact with the wire being installed
(for Wirefill sizes, see Section 9, Table 9-7 of this manual.)
13. HOW IS ENT PACKAGED?
ENT is packaged in:
a. Straight lengths
1
/2 inch ENT 20 10' pieces per bundle
3
/4 inch ENT 10 10' pieces per bundle
1 inch ENT 10 10' pieces per bundle
b. Coils
1
/2 inch ENT 200' per coil
3
/4 inch ENT 100' per coil
1 inch ENT 100' per coil
c. Reels
1
/2 inch ENT 1500' per reel
3
/4 inch ENT 1000' per reel
1 inch ENT 750' per reel
1
1
/4 inch ENT 750' per reel
1
1
/2 inch ENT 750' per reel
2 inch ENT 500' per reel
One Piece Quick
Connect fitting
Schedule 40 Male
Threaded Adapter
7
www.carlon.com
14. WHERE CAN I USE ENT?
ENT can be used in place of EMT, Rigid Galvanized
Steel, AC or MC/ cable and NM cable. Just refer to
Section 362.10 of NEC (see Section 10 of this manual.)
ENT can be used in residential, commercial, schools,
condominiums, apartments and industrial applications.
On Deck Installation – Commercial
Metal Stud Installation – School
Wood Stud Installation – Condominium
8
www.carlon.com
15. WHAT IF I HAVE ANY QUESTIONS THAT WERE
NOT COVERED IN THIS MANUAL?
Just call Carlon at (216) 766-6532
or 1-800-321-1970 (outside of Ohio) or contact
your local Carlon sales representative.
Visit our website at www.carlon.com.
On Deck Installation – Hospital
9
www.carlon.com
Section 2
Embedded ENT
REFERENCE NEC SECTION 362.10 USES PERMITTED:
The use of Carlon Electrical Nonmetallic Tubing and fittings
shall be permitted:
(6) Encased in poured concrete, or embedded in a concrete
slab on grade where ENT is placed on sand or approved
screenings, provided fittings identified for this purpose
are used for connections.
REFERENCE NEC SECTION 362.10 USES NOT PERMITTED:
Electrical nonmetallic tubing shall not be used:
(5) For direct earth burial.
1. Since ENT is manufactured in
1
/2 inch through 2 inch, it
can be installed quickly in most types of concrete floors,
either slab on grade or in multi-story building. PLEASE
CHECK YOUR JOB SPECIFICATIONS for any particular
requirements of concrete cover.
Multi-Story
Slab On Grade
10
www.carlon.com
2. Ideally, one continuous length of ENT should be installed
from box-to-box, but if the long lengths are not available,
the run can be made using shorter lengths coupled
together.
3. Carlon ENT is a pliable raceway that is not designed for
flexible use in final connections to motors, A.C. units or
other machinery where a flexible connection is necessary.
In such instances, use Carlon
®
Carflex
®
Liquidtight
Flexible Nonmetallic Conduit (ref. NEC Article 356)
(see Section 10 of this manual.)
4. Ease of installation of ENT enables you to meet to the
concrete pour schedule, and with ENT’s versatility and
pliability, installation rearrangements can be achieved just
prior to the pour.
5. The biggest advantage of ENT is its ability to resist
breaking, kinking, or crushing when installed and prior to
the pouring of concrete. This eliminates costly rework and
comebacks by the electrical contractor.
6. The installation of Carlon ENT isn’t any different than the
installation of comparable metallic conduit in a slab. ENT
is installed on the first layer of rebar. The ENT is tied to the
rebar every 3 feet with duct tape, tiewraps or tiewire. This
will prevent floating of the ENT and hold it in position
during the pouring of concrete.
Workers standing on ENT
11
www.carlon.com
Questions About ENT
1. WHAT ABOUT STUB UPS OF ENT?
First, read your job specifications for any particular
requirements. Then refer to Carlon suggested stub up
methods shown in this section.
2. WHAT FITTINGS DO I USE WHEN INSTALLING
1
/2 INCH THROUGH 1 INCH ENT IN CONCRETE?
Carlon offers a complete line of one piece quick connect
fittings. These fittings are suitable for damp locations and
are concrete-tight when used with Carlon ENT and a flat
sealing washer on the box connection end. Remember,
when using Carlon one piece quick connect fittings, NO
TAPING IS NEEDED.
3. WHAT FITTINGS DO I USE WHEN INSTALLING
LARGER CONDUIT 1
1
/4 INCH THROUGH 2 INCH
ENT TERMINATIONS?
All Schedule 40 fittings are compatible with ENT using
Carlon Blue ENT cement.
4. WHAT DO I USE FOR STUB DOWNS OF ENT?
For stub downs of ENT when installed in a deck, fabricate
a stub down (see illustration 2-1 in this section.)
REFERENCE NEC SECTION 362.10:
(7) For wet locations indoors as permitted in this section or
in a concrete slab on or below grade, with fittings listed
for the purpose.
This Section (7) permits the use of ENT in wet locations
providing fittings identified for this purpose are used. The
identified fittings are solvent cemented (glue-on) fittings
of the type used for Schedule 40 rigid PVC conduit.
Fabricated Stub Down
12
www.carlon.com
Stub Down into Box
Stub Down Using Carlon’s PV Mold
ENT in a Floor Slab prepared for
more form work to extend conduits in the
next pour.
ENT and Rigid PVC Conduit Stub Ups
prepared for the pour
13
www.carlon.com
ENT Stub Down
(Illustration 2-1)
1
/2" or
3
/4"
ENT
Form board
Foam sleeve
Foam bushing
Carlon ENT
ENT One-piece
coupling
Equipment Stub Up
(Illustration 2-2)
Carlon Carflex
®
flexible
extension for
equipment connection
Carlon
ENT
Finished
floor
Tie wrap ENT to rebar
Rebar
Prior to pouring plug coupling to
prevent entry of concrete
Carlon Sch 40 coupling flush with
finished floor
Carflex connector
Carlon FS or FD box
Box shall be securely
mounted to equipment
Carlon Sch 40 or Sch 80
conduit length
Glue Sch 40 coupling
to ENT using Carlon
ENT cement
Fabricated ENT deck stub down
After Stripping
Initial installation before form is Stripped
14
www.carlon.com
Stub Up in Walls
(Illustration 2-3)
Tape or tie-wrap
conduits together
Carlon ENT
Wood or steel base
plate is installed after
ENT is installed
Tie-wrap ENT to rebar to prevent floating
Wood stud
Steel stud
Stub Into Single Circuit Floor Box
(Illustration 2-4)
Carlon
ENT
Temporary cap
Metal deck
Plug and glue unused opening
Carlon E971FB
floor box
Stub Up into Control Cabinet or Switchgear
(Illustration 2-5)
1
/4" or
3
/8" plywood
Tape ENT to hold in template
Carlon ENT conduit
Caddy push nuts (2 per rod)
1
/4" or
3
/8" plain rods
drive into ground to
support template 3" - 4"
above top of pour
Rebar
15
www.carlon.com
Stub Up with ENT Sleeve
(Illustration 2-6)
1"
ENT
1
/2"
ENT
Metal deck
Rebar
Into
slab
Tape top of ENT sleeve prior
to pour to prevent entry of
concrete. Sleeve can be left
as long as needed or cut
flush with finished floor
Use a larger piece of ENT for a
sleeve. Push the smaller piece of
ENT through, bend and install
assembly
Finished floor
Stub Up with Refrigeration Tubing
(Illustration 2-7)
Carlon ENT tubing
Metal
deck
Rebar
After installation of sleeve and
ENT, space between ENT and the
sleeve can be troweled or foamed
with fireproofing compound.
(Follow manufacturer’s
recommendations)
Refrigeration tubing
Finished
floor
Stub Up using Sch 40 Elbow
(Illustration 2-8)
Carlon ENT
Scrap steel or EMT conduit
for support of stub up
PVC Sch 40 coupling See gluing
instructions – Section 11
Rebar
Rebar
PVC Sch 40 90º Elbow stub-size
as required by job specifications
Tie-wrap or tie-wire
Finished floor
Tie wrap
16
www.carlon.com
ENT in Wet Conditions
(Illustration 2-9)
Grade
ENT permitted in wet
locations, including
concrete below grade,
provided fittings identified
for the purpose are used.
17
www.carlon.com
Section 3
Wood and Metal Stud Construction
Reference NEC Section 362.10 Uses Permitted: The use of
electrical nonmetallic tubing and fittings shall be permitted:
(2)
In any building exceeding three floors above grade, ENT
shall be concealed within walls, floors, and ceilings where
the walls, floors, and ceilings provide a thermal barrier of
material that has at least a 15 minute finish rating as
identified in listings of fire-rated assemblies. (see Section 3,
Table 3-1 in this manual.) The 15-minute-finish-rated ther-
mal barrier shall be permitted to be used for combustible
or noncombustible walls, floors, and ceilings.
Exception: Where a fire sprinkler system(s) is installed in
accordance with NFPA 13-1999, Standard for the Installation
of Sprinkler Systems, on all floors, ENT is permitted to be
used within walls, floors, and ceilings, exposed or concealed,
in buildings exceeding three floors above grade.
Reference NEC Section 300.4 Protection Against Physical
Damage: Where subject to physical damage, conductors
shall be adequately protected.
(a) Cables and Raceways Through Wood Members.
Bored Holes. In both existing and concealed locations,
where a cable or raceway-type wiring method is installed
through bored holes in joists, rafters, or wood members,
holes shall be bored so that the edge of the hole is not
less than 1
1
/4 inch (31.8 mm) from the nearest edge of
the wood member. Where this distance cannot be main-
tained, the cable or raceway shall be protected from pene-
tration by screws or nails by a steel plate or bushing, at
least
1
/16 inch (1.59 mm) thick, and of appropriate length
and width installed to cover the area of the wiring.
Exception: Steel plates shall not be required to protect rigid
metal conduit, intermediate metal conduit, rigid nonmetal-
lic conduit, or electrical metallic tubing.
18
www.carlon.com
Questions about ENT
1. WHAT IS THE FINISH RATING WHERE ENT IS
INSTALLED?
As previously stated in this manual, when ENT is run
through studs and the wall, construction provides at least
a 15 minute finish rating by using materials shown in the
following chart.
2. WHAT HOLE SIZES DO I NEED FOR ENT RUNS
THROUGH STUDS OR JOISTS?
The absolute minimum size of holes needed are as
follows:
ENT (trade size) Hole (inches)
1
/2 1*
3
/4 1
1
/8
11
1
/2
1
1
/4 1
3
/4
1
1
/2 2
22
1
/2
*This is the only size ENT that can be drilled in the center of
a standard 2
4 inch wood stud and maintain 1
1
/4 inch
from each edge.
3. HOW DO I INSTALL
3
/4 INCH ENT AND OTHER
LARGER SIZES OF ENT IN STUDS OR JOISTS?
For
3
/4 inch ENT, start your 1
1
/8 inch hole 1
1
/4 inch from
the edge and cover the other side of the stud with a
1
/16
inch thick steel plate moved over the hole where it is less
than 1
1
/4 inch from the other end of the stud (see Section
300.4(A)(1), Section 10 of this manual.)
FINISH RATINGS OF WALLS
Finish
Rating
Material Min.
Fireboard,
1
/2" thick with
1
/2" 112,112
Gypsum sand plaster 15
Gypsum wallboard,
1
/2" thick 15
Gypsum wallboard,
5
/8" thick 20
Laminated wallboard,
3
/8",
1
/2" and
5
/8
" thick 28-60
From National Bureau of Standards, BMS-92
Table 3-1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82

Carlon A243F-CAR User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI