17
www.carlon.com
Section 3
Wood and Metal Stud Construction
Reference NEC Section 362.10 Uses Permitted: The use of
electrical nonmetallic tubing and fittings shall be permitted:
(2)
In any building exceeding three floors above grade, ENT
shall be concealed within walls, floors, and ceilings where
the walls, floors, and ceilings provide a thermal barrier of
material that has at least a 15 minute finish rating as
identified in listings of fire-rated assemblies. (see Section 3,
Table 3-1 in this manual.) The 15-minute-finish-rated ther-
mal barrier shall be permitted to be used for combustible
or noncombustible walls, floors, and ceilings.
Exception: Where a fire sprinkler system(s) is installed in
accordance with NFPA 13-1999, Standard for the Installation
of Sprinkler Systems, on all floors, ENT is permitted to be
used within walls, floors, and ceilings, exposed or concealed,
in buildings exceeding three floors above grade.
Reference NEC Section 300.4 Protection Against Physical
Damage: Where subject to physical damage, conductors
shall be adequately protected.
(a) Cables and Raceways Through Wood Members.
Bored Holes. In both existing and concealed locations,
where a cable or raceway-type wiring method is installed
through bored holes in joists, rafters, or wood members,
holes shall be bored so that the edge of the hole is not
less than 1
1
/4 inch (31.8 mm) from the nearest edge of
the wood member. Where this distance cannot be main-
tained, the cable or raceway shall be protected from pene-
tration by screws or nails by a steel plate or bushing, at
least
1
/16 inch (1.59 mm) thick, and of appropriate length
and width installed to cover the area of the wiring.
Exception: Steel plates shall not be required to protect rigid
metal conduit, intermediate metal conduit, rigid nonmetal-
lic conduit, or electrical metallic tubing.