Mircom LT-6736-BB-4002R-and-BB-4006R Installation guide

  • Hello! I have reviewed the installation instructions for the MGC BB-4002R and BB-4006R multi module enclosures. This document provides detailed information on the dimensions, wiring, and cable routing for these enclosures, ensuring safe installations with MIX-4000-M Series Modules. I'm ready to answer any questions you might have about these enclosures.
  • What is the minimum separation required between power-limited and non-power-limited wiring?
    What modules are these enclosures compatible with?
    How many modules can the BB-4002R enclosure house?
    How many modules can the BB-4006R enclosure house?
LT-6736 Rev 0 June 2023 Page 1 of 5
BB-4002R and BB-4006R
Multi Module Enclosures
BB-4002R: Back Box and Red Door for 1 or 2 MIX-4000-M Series Modules
BB-4006R: Back Box and Red Door for up to 6 MIX-4000-M Series Modules
Refer to the module manual for mounting instructions.
BB-4002R Dimensions and Wiring
4 knockouts on top
4 knockouts on bottom
Knockouts
Front view
9”
9 31/32”
7 1/5”
12 3/4”
3 13/16”
Back view
Bottom view
LT-6736 Rev 0 June 2023 Page 2 of 5
BB-4006R Dimensions and Wiring
23”
12 1/2”
8 1/2” 5 19/32”
10 1/2”
20 1/4”
3 knockouts
on the side
3 knockouts
on the side
2 knockouts on top
2 knockouts
on bottom
Knockouts on back
Optional ground screw
(use either ground screw)
Ground screw
LT-6736 Rev 0 June 2023 Page 3 of 5
Cable Routing in BB-4002R Example #1
Cable Routing in BB-4002R Example #2
Maintain a separation of 1/4” (6.4 mm)
minimum between power-limited and
non-power-limited wiring at all times.
Right side of
box is reserved
for all power
limited wiring.
Gray area (solid
outline) marks the
location for all
non-power-limited
wiring.
Green area (dotted
outline) marks the
location for all
power-limited wiring.
Maintain a separation of 1/4” (6.4 mm)
minimum between power-limited and
non-power-limited wiring at all times.
Gray area (solid
outline) marks the
location for all
non-power-limited
wiring.
Green area (dotted
outline) marks the
location for all
power-limited wiring.
Minimum
1/4”
Right side of
box is reserved
for all power
limited wiring.
Min. 1/4”
Minimum
1/4”
LT-6736 Rev 0 June 2023 Page 4 of 5
Cable Routing in BB-4006R Example #1
Maintain a separation of
1/4” (6.4 mm) minimum
between power-limited
and non-power-limited
wiring at all times.
Gray area (solid outline)
marks the location for
all non-power-limited
wiring.
Green area (dotted
outline) marks the
location for all
power-limited wiring.
Right side of
box is reserved
for all power
limited wiring.
Minimum 1/4”
Minimum 1/4”
LT-6736 Rev 0 June 2023 Page 5 of 5
Cable Routing in BB-4006R Example #2
Maintain a separation of
1/4” (6.4 mm) minimum
between power-limited
and non-power-limited
wiring at all times.
Gray area (solid outline)
marks the location for
all non-power-limited
wiring.
Green area (dotted
outline) marks the
location for all
power-limited wiring.
Right side of box is
reserved for all power
limited wiring.
Minimum 1/4”
Minimum 1/4”
Minimum 1/4”
Minimum 1/4”
Min.
1/4”
Minimum 1/4”
Min. 1/4”
Min.
1/4”
Min.
1/4”
Min. 1/4”
Min. 1/4”
/