LT-6736 Rev 0 April 2023 Page 3 of 5
Cable Routing in BB-4002R Example #1
Cable Routing in BB-4002R Example #2
Maintain a separation of 1/4” (6.4 mm)
minimum between power-limited and
non-power-limited wiring at all times.
Right side of
box is reserved
for all power
limited wiring.
Gray area marks the
location for all
non-power-limited
wiring.
Green area marks the
location for all
power-limited wiring.
Maintain a separation of 1/4” (6.4 mm)
minimum between power-limited and
non-power-limited wiring at all times.
Gray area marks the
location for all
non-power-limited
wiring. Green area marks the
location for all
power-limited wiring.
Minimum
1/4”
Right side of
box is reserved
for all power
limited wiring.
Min. 1/4”
Minimum
1/4”