Mircom LT-6736-BB-4002R-and-BB-4006R Installation guide

  • Hello! I've reviewed the installation instructions for the MGC BB-4002R and BB-4006R Multi Module Enclosures. These enclosures are designed to house MIX-4000-M series modules, with different capacities. The document provides useful details on dimensions, wiring, and separation requirements between different types of wiring. I'm ready to answer any questions you have about these products.
  • What is the purpose of the BB-4002R enclosure?
    How many modules can the BB-4006R enclosure accommodate?
    Is there a requirement for separating different types of wiring?
LT-6736 Rev 0 April 2023 Page 1 of 5
BB-4002R and BB-4006R
Multi Module Enclosures
BB-4002R: Back Box and Red Door for 1 or 2 MIX-4000-M Series Modules
BB-4006R: Back Box and Red Door for up to 6 MIX-4000-M Series Modules
Refer to the module manual for mounting instructions.
BB-4002R Dimensions and Wiring
4 knockouts on top
4 knockouts on bottom
Knockouts
Front view
9”
9 31/32”
7 1/5”
12 3/4”
3 13/16”
Back view
Bottom view
LT-6736 Rev 0 April 2023 Page 2 of 5
BB-4006R Dimensions and Wiring
23”
12 1/2”
8 1/2” 5 19/32”
10 1/2”
20 1/4”
3 knockouts
on the side
3 knockouts
on the side
2 knockouts on top
2 knockouts
on bottom
Knockouts on back
Optional ground screw
(use either ground screw)
Ground screw
LT-6736 Rev 0 April 2023 Page 3 of 5
Cable Routing in BB-4002R Example #1
Cable Routing in BB-4002R Example #2
Maintain a separation of 1/4” (6.4 mm)
minimum between power-limited and
non-power-limited wiring at all times.
Right side of
box is reserved
for all power
limited wiring.
Gray area marks the
location for all
non-power-limited
wiring.
Green area marks the
location for all
power-limited wiring.
Maintain a separation of 1/4” (6.4 mm)
minimum between power-limited and
non-power-limited wiring at all times.
Gray area marks the
location for all
non-power-limited
wiring. Green area marks the
location for all
power-limited wiring.
Minimum
1/4”
Right side of
box is reserved
for all power
limited wiring.
Min. 1/4”
Minimum
1/4”
LT-6736 Rev 0 April 2023 Page 4 of 5
Cable Routing in BB-4006R Example #1
Maintain a separation of
1/4” (6.4 mm) minimum
between power-limited
and non-power-limited
wiring at all times.
Gray area marks the
location for all
non-power-limited
wiring.
Green area marks the
location for all
power-limited wiring.
Right side of
box is reserved
for all power
limited wiring.
Minimum 1/4”
Minimum 1/4”
LT-6736 Rev 0 April 2023 Page 5 of 5
Cable Routing in BB-4006R Example #2
Maintain a separation of
1/4” (6.4 mm) minimum
between power-limited
and non-power-limited
wiring at all times.
Gray area marks the
location for all
non-power-limited
wiring.
Green area marks the
location for all
power-limited wiring.
Right side of box is
reserved for all power
limited wiring.
Minimum 1/4”
Minimum 1/4”
Minimum 1/4”
Minimum 1/4”
Min.
1/4”
Minimum 1/4”
Min. 1/4”
Min.
1/4”
Min.
1/4”
Min. 1/4”
Min. 1/4”
/