Kromschroder FCU 500 Warn Operating instructions

  • Hello! I've reviewed the instructions for the Protective system control FCU 500. This document highlights an error in the initial connection diagram and emphasizes the 24V DC requirement for the fan's binary signal. It also details how to customize the function of terminal 51. I am ready to answer you questions.
  • What is the voltage required for the binary signal at terminal 44?
    Where can the correct connection diagram be found?
    How is the function of Terminal 51 determined?
www.docuthek.com
D GB
© 2012 Elster GmbH
Edition 07.12
D/GB-1
07.12 Fx/IVD 100
Hinweis Anschlussplan
Originalhinweis
D
GB
F
NL
I
E
Hinweis
Ofenschutzsystem-Steuerung
FCU 500
VORSICHT
Fehler im Anschlussplan in der Betriebsan-
leitung Ofenschutzsystem-Steuerung FCU 500
(Edition 03.12, Seite D-5).
Klemme 44: Das Binärsignal für die Betriebs-
bereitschaft des Gebläses, das an die Ofen-
steuerung FCU 500 übertragen wird, muss
24V= betragen.
Klemme 51: In Abhängigkeit des Parameters69
kann die Funktion der Anschlussklemme be-
stimmt werden, z. B. Abfrage von Auf-Position
des Stellantriebes IC 40 oder von High-Position
eines RBW-Stellantriebes.
Korrekter Anschlussplan siehe Seite D/GB-2.
Weitere Informationen siehe Betriebsanleitung
Ofenschutzsystem-Steuerung FCU 500.
Note on connection diagram
Translation from the German
D
GB
F
NL
I
E
Note
Protective system control
FCU 500
CAUTION
Error in connection diagram in the protective
system control FCU 500 operating instructions
(Edition 03.12, page GB-5).
Terminal 44: the binary signal which is trans-
ferred to the furnace control unit FCU500 to
show that the fan is ready for operation must
be 24VDC.
Terminal 51: the function of this connection ter-
minal can be determined depending on parame-
ter69, e.g. query of the Open position of actuator
IC40 or of the High position of an RBWactuator.
Correct connection diagram, see page D/GB-2.
Further information can be found in the protective
system control FCU 500 operating instructions.
D/GB-2
STW/STB
STM/STL
D
GB
Luft
Luftmin
Air
Airmin
61 62
FCU 500 3,15AT
5AT
FS
A
L1
+24 V
V1 V2 V3
41 42 44 45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
ϑ
N
0 V
0,6 x IN
pu
21
4pu
Gasmin
PZL
Gas
max
PZH
LDS
HT
P
90°
90°
PZL
PZ
PDZ
3
4
+24 V DC
pu
PZ
k22
k12
K2 K1
IN × 0,6
k11
k21
M
P
67
13 14 15 16 17 1811 123 412
+ -+ -
5 6 7 8
P69*
D
GB
F
NL
I
E
Korrekter Anschlussplan
* Funktion über Parameter 69 einstellbar.
D
GB
F
NL
I
E
Correct connection diagram
* Function can be adjusted via parameter69.
/