0.01
2
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
1000
900
800
700
600
300
200
2000
3000
4000
5000
6000
7000
8000
9000
10000
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.2
0.3
0.4
0.5
Maximum Total
Clearing Time
Available Long Delay Time
(For 1200A Only):
2, 4, 7, 10, 12, 15, 20, 24 Sec.
Shown at 6xI
2, 4, 7, 15, 24
Seconds +0/–30%
(See Chart )
r
2 3 4 5710 20 30 40 50 70 100 2 4 5710 20 30 40 50 70 100
0.5 0.7
12 3 4 5710 20 30
0.5 0.7
Minimum Total
Clearing Time
4
.
15
.
24
1.15
14400A
Application Determines
End of Curve
Instantaneous
Override (See Note 8)
.
.
300 ms
(P, Q, R)
120 ms
(M, N, O)
Inst.
(J, K, L)
Available Short Delay
Pickup Settings
2–8, 9 x I + 5%
(See Note 7)
.
12
12
r
1 Hour 2 Hours
7
2
9
6
4
3
5
2
7
500
400
100
1 Minute
Time in Seconds
Current in Multiples of (I )
rCurrent in 1000A Increments
3
Time in Seconds
Current in Multiples of ( )
r
I
Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)
8
Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
Series G N-Frame Circuit Breakers
Long Delay Response and Short Delay with Flat Response and Override
Catalog Types: NGS, NGH, NGC, NGU, GNS, GNH, GNC, and GNU circuit breakers, three- and four-pole
Trip Unit Type: 32 (LSI), 36 (LSIG), 38 (ALSI), 39 (ALSIG)
Notes:
1. Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere derating for
ambient above 40°C, refer to Eaton. Temperatures above +85°C cause an over-temperature protection
trip.
2. Application frequency is 50/60 Hz.
3. There is a memory effect that can act to shorten the Long Delay. If the breaker trips on a Long Delay
overload and is quickly reset, the memory capacitor will still have charge and a subsequent overload
will cause the breaker to trip in a shorter time than normal. The amount of time delay reduction is
inverse to the amount of time that has elapsed since the previous overload. Approximately five
minutes is required between overloads to completely reset memory.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. The left portion of the curve is shown as a multiple of the Long Delay Setting.
(Long Delay Pickup = 115% of Ir ). Range is 110–120%.
6. Total clearing times shown include the response times of the trip unit, the breaker opening,
and the interruption of the current.
7. The Short Delay Pickup has nine settings/positions, 2–8; the last two switch positions are
the same: 9X.
8. For high fault current levels, an additional fixed instantaneous hardware override is provided to trip
the breaker at 14400A. Instantaneous tolerance is +/- 20%. For the 1600A frame only, if Ir is set to
the maximum (position H) and SDPU is set to the maximum (position 9), then the SDPU setting and
the Instantaneous Override are set to the same value. The Instantaneous Override has precedence
over SDPU. Therefore, the breaker will trip on Instantaneous Override.
Available Sensors
(Ir) / (In)
Rated Amperes
800A 1200A 1250A 1600A
A
B
C
D
E
F
G
H
320A 500A 500A 630A
400A 600A 630A 630A
450A 630A 700A 700A
500A 700A 800A 800A
600A 800A 900A 900A
630A 900A 1000A 1000A
700A 1000A 1200A 1250A
800A 1200A 1250A 1600A
STATUS
TEST / ALARM
6646 C05
E
G
F
H
A
B
D
C
IR∑
120
300Inst.
tsd (ms)
SHORT
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
LSI
STATUS
TEST / ALARM
tg (ms)
tsd
(ms)
120
K
N
Q
300
L
O
R
*Inst.
J
M
P
Inst.
120
300
Settings
6646 C05
E
G
F
H
A
B
D
C
IR∑
.8 1.0
.2
.3
.6
.4
Ig (xIn)
GND N
P
O
Q
J
K
M
L
R
sd
*
/
t tg (ms)
SHORT / GND
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
LSIG
STATUS
TEST / ALARM
E
G
F
H
A
B
D
C
IR∑
120
30050
tsd (ms)
SHORT
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
ALSI (With Maintenance Mode)
8
2.5
7
6
Ii (xIn)
INST
4
Maintenance Mode
Push to Trip
Remote MM
6646 C06
STATUS
TEST / ALARM
tg (ms)
tsd
(ms)
120
K
N
Q
300
L
O
R
* 50
J
M
P
50
120
300
Settings
E
G
F
H
A
B
D
C
IR∑
.8 1.0
.2
.3
.6
.4
Ig (xIn)
GND N
P
O
Q
J
K
M
L
R
sd
*
/
t tg (ms)
SHORT / GND
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
ALSIG (With Maintenance Mode)
8
2.5
7
6
Ii (xIn)
INST
4
Maintenance Mode
Push to Trip
Remote MM
6646 C06
4
Time Current Curves TD012029EN
Effective February 2016
NG/ND-Frames
EATON www.eaton.com
0.01
2
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
3
4
5
6
7
8
9
10
20
30
40
50
60
70
80
90
100
1000
900
800
700
600
500
400
300
200
2000
3000
4000
5000
6000
7000
8000
9000
10000
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.2
0.3
Maximum Total
Clearing Time
I
r
Application Determines
End of Curve
Instantaneous
Override (See Note 10)
12 3 4 5710 20 30 40 50 70 100 2 3 4 5710 20 30 40 50 70 100
0.5 0.7
12 3 4 5710 20 30
0.5 0.7
Minimum Total
Clearing Time
2
I T Short Delay
(See Note 8)
.
.
.
1.15
14400A
67 ms
Available Short Delay
Pickup Settings
2–8, 9 x I + 5%
(See Notes 7 and 10)
r
12
12
See Note 9
.
.
.
Available Long Delay Time
(For 1200A Only):
2, 4, 7, 10, 12, 15, 20, 24 Sec.
Shown at 6x
2, 4, 7, 15, 24
Seconds +0/–30%
(See Chart) )
24
15
7
4
2
3
4
5
7
9
6
2
Current Multiples of (I )
r
2 Hours1 Hour
1 Minute
Time in Seconds
Time in Seconds
Current in Multiples of (I )
rCurrent in 1000A Increments
I2T Trip Style (LS and LSG)
8
Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
Series G N-Frame Circuit Breakers
Long Delay Response and Short Delay with I2T Response Curve and Override
Catalog Types: NGS, NGH, NGC, NGU, GNS, GNH, GNC, and GNU circuit breakers, three- and four-pole
Trip Unit Type: 33 (LS), 35 (LSG)
Notes:
1. Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere derating for
ambient above 40°C, refer to Eaton. Temperatures above +85°C cause an over-temperature protection
trip.
2. Application frequency is 50/60 Hz.
3. There is a memory effect that can act to shorten the Long Delay. If the breaker trips on a Long Delay
overload and is quickly reset, the memory capacitor will still have charge and a subsequent overload
will cause the breaker to trip in a shorter time than normal. The amount of time delay reduction is
inverse to the amount of time that has elapsed since the previous overload. Approximately five
minutes is required between overloads to completely reset memory.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. The left portion of the curve is shown as a multiple of the Long Delay Setting.
(Long Delay Pickup = 115% of Ir ). Range is 110–120%.
6. Total clearing times shown include the response times of the trip unit, the breaker opening,
and the interruption of the current.
7. The Short Delay Pickup has nine settings/positions, 2–8; the last two switch positions are
the same: 9X.
8. Short Delay I2 T band has a tolerance of +15%.
9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I2 T curve.
10. For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the
breaker at 14400A. Instantaneous tolerance is +/- 20%. For the 1600A frame only, if Ir is set to the
maximum (position H) and SDPU is set to the maximum (position 9), then the SDPU setting and the
Instantaneous Override are set to the same value. The Instantaneous Override has precedence over
SDPU. Therefore, the breaker will trip on Instantaneous Override.
Available Sensors
(Ir) / (In)
Rated Amperes
800A 1200A 1250A 1600A
A
B
C
D
E
F
G
H
320A 500A 500A 630A
400A 600A 630A 630A
450A 630A 700A 700A
500A 700A 800A 800A
600A 800A 900A 900A
630A 900A 1000A 1000A
700A 1000A 1200A 1250A
800A 1200A 1250A 1600A
STATUS
TEST / ALARM
6646 C05 H11
E
G
F
H
A
B
D
C
I
R∑
6
8
7
2
3
5
4
9
I
sd (xI
R
)
SHORT
9
t
R
(s)
LONG
LS
STATUS
TEST / ALARM
6646 C05
E
G
F
H
A
B
D
C
IR∑
.8 1.0
.2
.3
.6
.4
Ig (xIn)
GND 120
300Inst.
tg (ms)
GND
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
LSG
Figure 2. Digitrip 310+ Long Delay Response and Short Delay with Flat Response and Override Curve (LSI, LSIG, ALSI, ALSIG) -
Curve Number TC01210010E, March 2012
Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
Series G N-Frame Circuit Breakers
Long Delay Response and Short Delay with Flat Response and Override
Catalog Types: NGS, NGH, NGC, NGU, GNS, GNH, GNC, and GNU circuit breakers, three- and four-pole
Trip Unit Type: 32 (LSI), 36 (LSIG), 38 (ALSI), 39 (ALSIG)
Notes:
1. Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere derating for
ambient above 40°C, refer to Eaton. Temperatures above +85°C cause an over-temperature protection
trip.
2. Application frequency is 50/60 Hz.
3. There is a memory effect that can act to shorten the Long Delay. If the breaker trips on a Long Delay
overload and is quickly reset, the memory capacitor will still have charge and a subsequent overload
will cause the breaker to trip in a shorter time than normal. The amount of time delay reduction is
inverse to the amount of time that has elapsed since the previous overload. Approximately ve
minutes is required between overloads to completely reset memory.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. The left portion of the curve is shown as a multiple of the Long Delay Setting.
(Long Delay Pickup = 115% of Ir ). Range is 110–120%.
6. Total clearing times shown include the response times of the trip unit, the breaker opening,
and the interruption of the current.
7. The Short Delay Pickup has nine settings/positions, 2–8; the last two switch positions are
the same: 9X.
8. For high fault current levels, an additional xed instantaneous hardware override is provided to trip
the breaker at 14400A. Instantaneous tolerance is +/- 20%. For the 1600A frame only, if Ir is set to
the maximum (position H) and SDPU is set to the maximum (position 9), then the SDPU setting and
the Instantaneous Override are set to the same value. The Instantaneous Override has precedence
over SDPU. Therefore, the breaker will trip on Instantaneous Override.
9. Maximum clearing time when using zone selective interlocking is 62ms.
Available Sensors
(Ir) / (In)
Rated Amperes
800A 1200A 1250A 1600A
A
B
C
D
E
F
G
H
320A 500A 500A 630A
400A 600A 630A 630A
450A 630A 700A 700A
500A 700A 800A 800A
600A 800A 900A 900A
630A 900A 1000A 1000A
700A 1000A 1200A 1250A
800A 1200A 1250A 1600A
STATUS
TEST / ALARM
6646 C05
E
G
F
H
A
B
D
C
IR∑
120
300Inst.
tsd (ms)
SHORT
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
LSI
STATUS
TEST / ALARM
tg (ms)
tsd
(ms)
120
K
N
Q
300
L
O
R
*Inst.
J
M
P
Inst.
120
300
Settings
6646 C05
E
G
F
H
A
B
D
C
IR∑
.8 1.0
.2
.3
.6
.4
Ig (xIn)
GND N
P
O
Q
J
K
M
L
R
sd
*
/
tt
g (ms)
SHORT / GND
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
LSIG
STATUS
TEST / ALARM
E
G
F
H
A
B
D
C
IR∑
120
30050
tsd (ms)
SHORT
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
ALSI (With Maintenance Mode)
8
2.5
7
6
Ii (xIn)
INST
4
Maintenance Mode
Push to Trip
Remote MM
6646 C06
STATUS
TEST / ALARM
tg (ms)
tsd
(ms)
120
K
N
Q
300
L
O
R
* 50
J
M
P
50
120
300
Settings
E
G
F
H
A
B
D
C
IR∑
.8 1.0
.2
.3
.6
.4
Ig (xIn)
GND N
P
O
Q
J
K
M
L
R
sd
*
/
tt
g (ms)
SHORT / GND
6
8
7
2
3
5
4
9
Isd (xIR)
SHORT
9
tR (s)
LONG
ALSIG (With Maintenance Mode)
8
2.5
7
6
Ii (xIn)
INST
4
Maintenance Mode
Push to Trip
Remote MM
6646 C06
Long Delay Time Settings +0%/ -30% (seconds)
800A
1200A
1250A
1600A
2 4 6 8 10 12 14 14
2 4 7 10 12 15 20 24
2 4 6 8 10 12 14 14
2 4 7 10 12 15 20 20
Proof 4 — March 20, 2016 11:29 PM