ASPIRATED SMOKE DETECTOR
ASD1 (Single Channel)
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS (CE)
1 INTRODUCTION
The ASD1 has provision for one or two conventional/analogue addressable
point detectors allowing for single, failsafe redundancy or mixed detection
strategies.
The airflow level is displayed on a 10 element bar graph with adjustments for
sensitivity and high/low flow thresholds. Flow failure is reported to the central
panel as a detector/zone fault or via separate volt-free contacts.
2 SYSTEM INSTALLATION
Remove the transparent cover using the special tool provided to unscrew the
tamper proof fasteners. Use the template provided to accurately position the
holes then secure the unit to a suitable surface through the 4 corner fixing
points. Ensure that the correct fasteners are used for the type of surface that
the unit is mounted on.
3 WIRING
For correct operation of the unit, it is essential that the case is fully sealed so
that air can only be pulled into the system through the aspirating pipe. For
this reason, all wiring must pass through the cable seals provided and no
additional holes should be made. In order to pass a cable through a seal it is
necessary to make a small hole in the centre of the seal with a pointed
implement (e.g. small screwdriver) and then force the cable through the hole
into the box. The small hole will expand to accommodate any cable diameter
from 4 to 10mm and then provide an airtight seal.
CAUTION! THE ASD1 SYSTEM HAS BEEN INDEPENDENTLY TESTED AND
CERTIFIED TO CEA4022 AND MUST BE INSTALLED IN STRICT COMPLIANCE
WITH THE INSTRUCTIONS BELOW IF THE CERTIFICATION IS TO BE
MAINTAINED
WARNING! THIS EQUIPMENT MUST BE INSTALLED BY A QUALIFIED
INSTALLER IN ACCORDANCE WITH ALL LOCAL AND NATIONAL
REGULATIONS
In order to gain access to the main circuit board for connection of the wiring it
is necessary to remove the display/detector mounting board, which is held in
place by the clear top cover. Care should be taken when removing the board
to ensure that the ribbon cable on the underside is not strained. The ribbon
cable may be removed from the connector on the underside of the board to
allow the board to be fully removed.
WARNING! TO PREVENT RISK OF ELECTRIC SHOCK, OR POSSIBLE
INJURY FROM THE ROTATION OF THE HIGH PERFORMANCE FAN, THE
SYSTEM SHOULD BE ISOLATED FROM THE SUPPLY WHEN THE TOP
COVER IS REMOVED
All connections to the main circuit board are to pluggable terminals that can
accommodate wire sizes up to 2.5mm
2
.
3.1 FIELD CONNECTIONS
LOOP OUT
( + - )
LOOP IN
( + - )
BAT
FUSE
BATTERY
+24V 0V
FAULT 2
NO COM NC
3.1.1 BATTERY
The ASD1 unit is designed to run from a nominal 24V DC
supply. The supply should be connected to the 2 way
‘BATTERY’ connector on the main circuit board ensuring
that the wires are correctly orientated. It is recommended
that the wires should be a minimum size of 16 x 0.25mm
(18AWG), or larger if the supply is further than 5m from
the system.
A ferrite core is provided for EMC compliance. This should be fitted to the
supply wiring as shown above.
The power requirements are dependant on the fan speed see table in
Section 11.1 for details.
3.1.2 LOOP IN/LOOP OUT
The Loop In/Loop Out terminals are connected to the detector terminals on
the display board. This provides a convenient means of connecting the
loop/circuit wiring to the unit and allows the display and detectors to be
removed during servicing by simply disconnecting the ribbon cable.
The loop/circuit wiring can also be connected directly to the detectors if
required.
The connection to detector 1 terminal is via a relay contact that is closed
under normal operating conditions but open in the event of a flow/fan/power
fault. This takes detector 1 off the loop/circuit, which is interpreted by the
panel as a fault condition.
3.1.3 FAULT 2
In the event of a fault condition, the Fault 2 relay will change state. The
terminals provide for Normally Open (NO) or Normally Closed (NC) operation
and these can be wired using terminating resistors to simulate a zone fault
on a conventional control panel or via a loop interface module for an
analogue addressable panel.
4 POINT DETECTORS
Ensure that the selected detectors have sufficient sensitivity for the
application. See Section 5 below for further details of how dilution affects
detector sensitivity.
If the installation is to be in accordance with the CEA 4022 certification then
the detector must have been tested for use in the system. Please refer to the
list of approved detectors in Section 9.
4.1 BAFFLES
Due to the large variation in the sizes and shapes of point detectors it is
necessary to fit baffles to the ASD to ensure that the sampled air flow is
directed toward the detector. Each baffle is shaped to match a particular
model/range of detectors and simply clips into position in the slots provided
in the transparent lid.
THIS MODE OF OPERATION SHOULD ONLY BE USED IF THE UNIT IS FITTED
WITH 2 DETECTORS. IF A SINGLE DETECTOR IS USED THEN THE DETECTOR
MUST BE FITTED TO THE DETECTOR 2 POSITION
NO/NC REFERS TO THE UN-POWERED STATE OF THE RELAYS AND UNDER
NORMAL, NON FAULT, CONDITIONS NO IS CLOSED AND NC IS OPEN
4.2 DETECTOR INSTALLATION
One or two Conventional/Analogue Addressable Point Detectors are
mounted on the display/mounting board using the screws provided. The
detectors can then be wired to either the local terminals in the centre of the
detector mounting points (then to the loop/conventional circuit via the Loop
In/Loop Out terminals on the main circuit board) or directly to the
loop/conventional circuit with the wiring passing through the cut-outs on the
display/mounting board.
4.3 WIRING EXAMPLES
The following examples show typical installations for conventional and
analogue addressable detectors –
KEY – (1) Display/Detector Mounting Board (2) Main Circuit Board
(3) Ribbon Connector (4) Detector 1 Relay Contacts (5) Detector 1
(6) Detector 2 (7) Terminating Resistor (8) Loop Interface Module
(9) Addressable Loop/Conventional Circuit
4.3.1 ASD1 WITH SINGLE CONVENTIONAL DETECTOR
Detector MUST be fitted to position 2. Terminating resistor may be fitted to
position 1 if required.
-
+
+
-
+
-
2
+
-
1
LOOP IN (+)
LOOP IN (-)
LOOP OUT (+)
LOOP OUT (-)
BAT TERY +24V
BAT TERY 0V
1 2
3
3
5
6
4
7
4.3.2 ASD1 WITH 2 x CONVENTIONAL DETECTORS
Terminating resistor fitted to detector in position 1 if required.
-
+
+
-
+
-
2
+
-
1
LOOP IN (+)
LOOP IN (-)
LOOP OUT (+)
LOOP OUT (-)
BAT TERY +24V
BAT TERY 0V
1 2
3
3
5
6
4
4.3.3 ASD1 WITH 2 x ADDRESSABLE DETECTORS
Detectors wired directly to loop with Fault 2 relay connected to loop via
addressable module
-
+
+
-
+
-
2
+
-
1
BATTERY +24V
BATTERY 0V
1 2
3
3
5
6
4
8
FAULT 2
NO
COM
NC
9
+
-
+
-
9
4.3.4 SERIES OF ASD1 UNITS ON A CONVENTIONAL DETECTION CIRCUIT
Schematic shows first and last units. Zone circuit wiring returned from last
unit to first via Fault 2 relay contacts in each unit and terminating resistor
fitted to first unit as shown. Flow fault condition in any unit will break the
connection to the terminating resistor and indicate a zone fault without
affecting the operation of the detectors themselves
+
-
-
+
+
-
+
-
2
+
-
1
BATT ERY +24V
BATT ERY 0V
1 2
3
3
5
6
4
FAULT 2
NO
COM
NC
-
+
+
-
+
-
2
+
-
1
BATT ERY +24V
BATT ERY 0V
1
2
3
3
5
6
4
FAULT 2
NO
COM
NC
9
7
5 PIPE INSTALLATION
A simple guide to pipe installation follows with examples of standard
configurations and should contain all the information required for simple
installations based on the standard configurations.
Use 25mm (or ¾”) Red ABS pipe with sampling point holes drilled along its
length. The pipe run is terminated with an end cap that has a hole drilled in
its centre.
The position of each individual sampling point should be in accordance with
the rules for the positioning of point detectors. It is important to note that the
concentration of smoke on an individual sample point will be diluted by the
clean air from the other sample points and the end cap hole.
5.1 PIPE SPECIFICATION
For CEA4022 compliance, the pipe should be Red ABS to EN 50086-1
(Crush 1, Impact 1, Temp 33) with a nominal diameter of 25mm (or ¾”). The
sample pipe is normally supplied in 3 metre lengths and is cut as required
and joined by solvent welded sockets (permanent), or socket unions
(removable).
5.2 FIXINGS
The normal fixing methods are pipe clips, saddle clamps or even tie wraps.
Fixing centres are typically 1.5m apart.
5.3 HOLES
The sampling pipe is perforated with sampling holes and can either be pre-
drilled or drilled in situ. Care should be taken to avoid swarf entering the pipe.
Always blow compressed air through the pipe after drilling to clear any debris
before final connection to the equipment. In standard configuration, with pipe
REFER TO THE PIPE INSTALLATION MANUAL (AVAILABLE AS OPTIONAL CD-
ROM OR DOWNLOAD FROM FIRETRACER.COM) FOR DETAILED
INFORMATION AND MORE PRACTICAL EXAMPLES
THE ASD1 INLET PORT IS TAPERED TO ALLOW A PUSH FIT OF THE SAMPLING
PIPE. THE PIPE SHOULD BE CUT SQUARELY TO ENSURE A GOOD, AIRTIGHT
SEAL. SOLVENT ADHESIVE SHOULD NOT BE USED FOR THIS JOINT
THE PIPETRACER SOFTWARE (AVAILABLE AS OPTIONAL CD-ROM OR
DOWNLOAD FROM FIRETRACER.COM) SHOULD BE USED TO CALCULATE
TRANSPORT TIMES, DILUTION EFFECTS ETC. FOR ALL INSTALLATIONS
BEYOND THE SCOPE OF THIS GUIDE
hanging from ceiling, the holes should be placed underneath, so the smoke
can easily rise up into the hole.
5.4 END CAP
The end of the pipe is terminated with a cap, with a hole
drilled in its centre. If the end cap is not used, then
practically no air will be drawn through the side holes. If the
end cap does not have a hole then the contributions from
the side holes will tend to be very unbalanced.
5.5 BENDS
Bends are either 45 or 90 degrees. For the 90-degree bends, it is very
important that swept bends are used and not sharp elbows, as this will
introduce unacceptable pressure losses, and significantly increase the
response times from holes beyond the bend.
5.6 EXHAUST
In most installations the exhaust should be left open but there are some
circumstances when it may be necessary to connect pipe to the exhaust port
to divert the exhaust away from the location of the unit e.g. to reduce noise,
reduce risk of interference/deliberate obstruction, improved environmental
protection etc.
Pipe of the same specification as the sample runs should be used and its
length limited to a maximum of 10m to avoid significant reduction in the air
flow. Care should be taken to position the new exhaust outlet where it cannot
be accidentally or deliberately blocked.
5.7 FILTERS
The sampled air is passed through a 2 stage filter
replacement order code FL55 - before entering the detector
chamber.
As standard, the filtration should be sufficient for all but
extremely dusty conditions where a Harsh Environment
Filter order code FLU1 (3/4”) / FLU2 (25mm) - should be
fitted between the unit and the first sampling point.
5.8 STANDARD CONFIGURATIONS (Drawings not to scale)
5.8.1 Configuration 1
ASD1 with single pipe
5.8.2 Configuration 2
ASD1 with Tee and 2 pipes - Distance from unit to Tee must be <= 1m and
pipes should be balanced i.e. equal length and equal number of holes.
The use of additional bends as described in Section 5.5 will have a minimal
effect on performance – i.e. response time, of either configuration.
6 SETUP
6.1 DISPLAY FUNCTIONS
1
BARGRAPH of AIRFLOW SPEED
2, 3, 4
AIRFLOW OK - HIGH AIRFLOW - LOW AIRFLOW
5 POWER ON
6 GENERAL FAULT (Mains PSU Option Only)
7 MAINS FAILURE (Mains PSU Option Only)
8 BATTERY LOW (Mains PSU Option Only)
9 FAN FAULT
10 CODE ENTRY
THE PIPETRACER SOFTWARE SHOULD BE USED TO VERIFY THE
PERFORMANCE OF ANY NON-STANDARD CONFIGURATIONS OR WHERE
UNBALANCED PIPE RUNS ARE REQUIRED
SEE TABLE IN SECTION 9 FOR CEA 4022 HOLE AND PIPE LENGTH LIMITS
FOR CERTIFIED DETECTORS
11 UNLOCK
6.2 USER FUNCTIONS
Press and hold SELECT and CHANGE keys
simultaneously for 1 second to initialise function selection.
Press and release SELECT key to sequentially step
through functions.
Press and release CHANGE key to modify setting.
The relevant LED flashes continuously to indicate the
function selected.
1) Enter 3 digit access code - 510. Each number must be selected in turn.
e.g. press CHANGE six times to illuminate the number 5 LED on the
display then press SELECT etc. (CODE LED flashes UNLOCK LED
illuminates on successful entry).
2) Set fan speed (POWER LED flashes)
3) Set sensitivity of bar graph to changes in airflow velocity (FLOW OK
flashes)
4) Select the BARGRAPH LED segment above which the FLOW HIGH LED
will be illuminated (FLOW HIGH flashes)
5) Select the BARGRAPH LED segment below which the FLOW LOW LED
will be illuminated (FLOW LOW flashes)
6) Calibrate flow sensors (FAN FAULT LED flashes). CHANGE key must be
pressed for at least 2 seconds to initiate the flow calibration process. FAN
and POWER LEDs flash to indicate calibration in progress. Fan is
temporarily stopped as part of the calibration process. The system will
reset and revert to normal operating mode when flow calibration is
completed.
Pressing the SELECT key for longer than 1 second when the unit is unlocked
will cause the unit to revert to normal operating mode.
6.3 SET-UP NOTES
The Fan Speed, Flow Limits and Flow Sensitivity need to be set for each
installation prior to Flow Calibration and testing. It is not possible to provide
the settings for all possible installations but the following guidelines should
assist in the commissioning of the unit.
6.3.1 FAN SPEED
The Fan Speed should be set as high as possible to achieve the fastest
transport time from the sampling point to the detectors, this is especially
important for longer pipe lengths and for installations that must conform to
the requirements of CEA4022 (see Section 9). There is, however, a balance
to be achieved between performance and the units power requirements and
reference should be made to the current consumption figures in the
specifications prior to setting this value. Fan speeds 3 and below should not
be used for standard configurations.
6.3.2 FLOW SENSITIVITY
This setting determines the systems responsiveness in reporting blocked
sampling points or broken pipes. The number of sampling points and fan
speed are the main factors to consider for this setting.
The following table shows typical settings for a variety of standard fan
speed/hole quantity combinations. Other speed/hole combinations should be
verified by testing during commissioning.
6.3.2.1 TYPICAL FLOW SENSITIVITY SETTINGS
PIPE SETUP
(all 50m lengths unless otherwise stated)
RECOMMENDED
FAN SPEEDS
FLOW
SENSITIVITY
13 x 3mm Sampling Holes, 1 x 6mm End Hole 9 9
8 x 3mm Sampling Holes, 1 x 6mm End Hole 6-9 9
4 x 3mm Sampling Holes, 1 x 6mm End Hole 6-9 7
1 x 5mm Sampling Hole, 1 x 5mm End Hole 6-9 5
1 x 8mm End Hole 5-9 2
1 x 8mm End Hole (10m Pipe) 3-9 1
7 TESTING
7.1 DETECTORS
With the unit powered up and top cover removed the detectors can be tested
for functionality using methods described by the manufacturer e.g. aerosol
spray etc.
7.2 SYSTEM
The installed system must be checked with the top cover securely fitted.
As a minimum, smoke should be introduced to the furthest sampling point
from the ASD unit on each branch of the pipe. The choice of smoke source is
dependant on the installation but in all cases, the smoke must be present for
the duration of the test aerosol sprays for point detectors do NOT work on
aspirated systems.
If it is possible to get close to the sampling point then a basic, functional
check can be carried out with smoke matches or lighted taper etc. but for
measurable performance, tests then refer to Appendix A of the BFPSA Code
of Practice for Aspirating Systems to select the appropriate test for the
installation.
8 MAINTENANCE
With normal use, the filter elements will eventually become contaminated
with dust particles, impeding airflow, and it is recommended that the filter
elements – order code FL55 - are changed every six months.
1. Remove the transparent cover using the special tool provided to unscrew
the tamper proof fasteners.
TESTING SHOULD ONLY BE CARRIED OUT BY QUALIFIED PERSONNEL.
BEFORE UNDERTAKING ANY TESTING ENSURE THAT THE PROPER
AUTHORITIES HAVE BEEN INFORMED AND THAT THE UNIT HAS BEEN
ISOLATED FROM THE FIRE CONTROL PANEL IF NECESSARY TO PREVENT
UNWANTED ALARMS
MAINTENANCE SHOULD ONLY BE CARRIED OUT BY QUALIFIED
PERSONNEL. BEFORE CARRYING OUT ANY MAINTENANCE, NOTIFY THE
PROPER AUTHORITIES AND ISOLATE UNIT FROM THE FIRE CONTROL
PANEL TO PREVENT UNWANTED ALARMS
2. Lift out the foam filter elements from the filter tube (tweezers or long nosed
pliers are recommended for this operation).
3. Fit a new filter element set ensuring that the coarse grade filter is inserted
into the tube first. Care should be taken to ensure that the filters are not
compressed during fitting and that the fine filter is positioned flush with the
top of the filter tube.
4. Replace the top cover
9 CEA 4022 CERTIFIED DETECTORS
The following detectors have been independently tested and certified for use
in the ASD1 unit. The table shows the limits that should not be exceeded if
the installation is to conform to this requirement. All figures are based on the
standard configurations shown in Section 5.8. Pipe lengths are 50m pipe
with a fan speed of 9 unless otherwise stated.
Detector Brand Detector Model Configuration 1
Sampling hole limits
Configuration 2
Sampling hole limits
APOLLO S65 Optical 1 x 8mm End Hole n/a
XP95 Optical 1 x 8mm End Hole n/a
DISCOVERY Optical
1
1 x 8mm End Hole n/a
DISCOVERY Optical
2
2 x 5mm Holes n/a
DETECTOMAT CT 3000 O 1 x 8mm End Hole n/a
PL 3200 O 1 x 8mm End Hole n/a
PL 3300 O 1 x 8mm End Hole n/a
GE SECURITY DP 331I 1 x 8mm End Hole n/a
DP 721I 3 x 4mm Holes n/a
DP 2061
3
6 x 4mm Holes n/a
DP 951 1 x 8mm End Hole n/a
HOCHIKI SLR-E3 1 x 8mm End Hole n/a
ALG-E 1 x 8mm End Hole n/a
SYSTEM SENSOR 2251EM
4
1 x 8mm End Hole n/a
2251EM
5
2 x 5mm Holes n/a
7251 PINNACLE
6
13 x 3mm,6mm end 8 x 3mm, 6mm end
7
7251 PINNACLE
6
75m Pipe –
11 x 3mm,6mm end
n/a
1) Using standard sensitivity alarm level of 55
2) Using pre-alarm sensitivity level of 45
3) Using high sensitivity mode
4) Using standard sensitivity alarm level of 2200
DETECTORS SHOULD BE SERVICED IN ACCORDANCE WITH THE
MANUFACTURERS RECOMMENDATIONS
5) Using high sensitivity alarm level of 1800
6) Using alarm level 3
7) Per branch
10 PROBLEM SOLVING
PROBLEM POSSIBLE SOLUTIONS
Power light flashing. Ensure supply to BATTERY connector within limits.
No lights on display.
Fan not running
Ensure supply leads correctly orientated. Ensure that
BAT FUSE correctly seated in socket and fuse not blown.
No lights on display.
Fan running OK.
Ensure ribbon cable fully seated into main & display
boards.
Flow HI/LO light on Ensure sampling pipes correctly installed, lid fitted and
box fully sealed. Ensure flow calibration procedure has
been carried out (Section 6.2). Ensure filters are clean
(Section 8)
Flow reading on
Bargraph display moves
erratically.
Decrease Flow sensitivity setting and re-calibrate air
flows (Section 6.2).
Flow reading on
Bargraph unresponsive
to broken/blocked pipes
Increase Flow sensitivity setting and re-calibrate air flows
(Section 6.2).
Detector(s)
unresponsive to smoke
tests
Ensure sampling pipe installed correctly and undamaged
(Section 5). Ensure that holes and pipe length do not
exceed limits for detector (Section 9). Ensure that
recommended baffles are fitted (Section 4.1). Ensure that
recommended test method is used (Section 7.2).
Increase fan speed and re-test.
SIGNIFICANT REDUCTIONS IN PIPE LENGTH MAY ALLOW THE FAN SPEED TO
BE REDUCED AND/OR NUMBER OF HOLES INCREASED. RESULTS OF SUCH
CHANGES MUST BE VERIFIED WITH THE PIPETRACER SOFTWARE.
OTHER DETECTORS AND PIPE LENTHS UP TO 100m MAY BE USED IF CEA 4022
CERTIFICATION IS NOT A REQUIREMENT. DESIGNS SHOULD BE VERIFIED
WITH THE PIPETRACER SOFTWARE TO ENSURE THAT THE PERFORMANCE IS
SUITABLE FOR THE INTENDED APPLICATION.
11 SPECIFICATIONS
11.1 TYPICAL SUPPLY CURRENT/FAN SPEED
Bargraph Value 0 1 2 3 4 5 6 7 8 9
Fan Speed 1 2 3 4 5 6 7 8 9 10
Current (mA) 110 120 130 150 170 190 220 235 265 300
Typical current consumption figures for different fan speeds. Results are based upon
an ASD2 installation with 10m of standard, 25mm aspirating pipe per channel. The
unit was powered from a 24V supply.
WEEE DIRECTIVE 2002/96/EC (Waste Electrical and Electronic
Equipment)
The symbol shown is marked on this product to indicate that it must not
be disposed of with other waste. Instead, it is the user’s responsibility to
dispose of their waste equipment by handing it over to a designated
collection point for the recycling of waste electrical and electronic
Number of Detectors
(not supplied)
1 or 2 Analogue Addressable or Conventional
Filtration 2 Stage, cartridge dust particle filter
Flow Monitoring
Thermal device, high and low thresholds. 10 element
bar graph indication. Loop or relay fault reporting.
Supply Voltage
18-30V DC (24V DC Nominal)
Maximum Supply Current
350mA @24V DC with no aspirating pipe. See table
below for typical Currents/Fan Speeds
Maximum Pipe Length
Up to 100 + 100 metres in Tee configuration (50m +
50m for CEA 4022) dependant on detector type &
application
Environmental Protection IP65 with exhaust fitted (IP53 without)
Operating Temperature -10 to 50ºC
Operating Humidity 10 to 95% RH (non-condensing)
Approvals CEA 4022 by VdS (G206066)
CE Certification
EN61000-6-3:2001(+A11:2004) (EMC)
EN60950-1:2006 (Safety)
equipment. The separate collection and recycling of your waste at the time of disposal will help
to conserve natural resources and ensure that it is recycled in a manner that protects human
health and the environment. For more information about where you can drop off your waste
equipment for recycling, please contact your local city office, your household waste disposal
service or where you purchased the product.
GLT Exports Limited,
Detection House,
72-78 Morfa Road,
Hafod,
Swansea,
SA1 2EN,
United Kingdom
Telephone +44 (0)1792 455175
Fax +44 (0)1792 455176
e-mail address: [email protected]
web site: www.zeta-alarms.co.uk
ASD1 Manual (CE) – Issue 10.0
Part No. 09-0101-10
.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9