6.3 SET-UP NOTES
The Fan Speed, Flow Limits and Flow Sensitivity need to be set for each
installation prior to Flow Calibration and testing. It is not possible to provide
the settings for all possible installations but the following guidelines should
assist in the commissioning of the unit.
6.3.1 FAN SPEED
The Fan Speed should be set as high as possible to achieve the fastest
transport time from the sampling point to the detectors, this is especially
important for longer pipe lengths and for installations that must conform to
the requirements of CEA4022 (see Section 9). There is, however, a balance
to be achieved between performance and the units power requirements and
reference should be made to the current consumption figures in the
specifications prior to setting this value. Fan speeds 3 and below should not
be used for standard configurations.
6.3.2 FLOW SENSITIVITY
This setting determines the systems responsiveness in reporting blocked
sampling points or broken pipes. The number of sampling points and fan
speed are the main factors to consider for this setting.
The following table shows typical settings for a variety of standard fan
speed/hole quantity combinations. Other speed/hole combinations should be
verified by testing during commissioning.
6.3.2.1 TYPICAL FLOW SENSITIVITY SETTINGS
PIPE SETUP
(all 50m lengths unless otherwise stated)
RECOMMENDED
FAN SPEEDS
FLOW
SENSITIVITY
13 x 3mm Sampling Holes, 1 x 6mm End Hole 9 9
8 x 3mm Sampling Holes, 1 x 6mm End Hole 6-9 9
4 x 3mm Sampling Holes, 1 x 6mm End Hole 6-9 7
1 x 5mm Sampling Hole, 1 x 5mm End Hole 6-9 5
1 x 8mm End Hole 5-9 2
1 x 8mm End Hole (10m Pipe) 3-9 1