Comelit ILS-2 User manual

Category
Smoke detectors
Type
User manual
1
ASPIRATING SMOKE DETECTOR, 1 ZONE, 2
DETECTORS
ILS-2
2
DISCLAIMER
The content of this document is provided “as seen”. No responsibility is taken and no guarantee (express or
implied) is made in terms of the complete nature, accuracy or reliability of the content of this document. The
manufacturer reserves the right to make changes to the design or the specifications, without any obligation and
without prior notice. Unless otherwise stated, any express or implied guarantee is strictly excluded; this includes,
without restrictions, all implied warranties relating to saleability and fitness for particular purposes.
Conventions used
The following typographic conventions are used in this manual:
Convention
Description
Bold
Used to indicate: emphasis used for menu names, menu options,
toolbar icons
Italic
Used to indicate:
links to other sections
of this manual or other documents, or to indicate the result of
an action.
The following symbols are used in this document:
Convention Description
Caution: this symbol is used to indicate danger to the equipment. The danger
may include loss of data, physical damage or permanent corruption of
configuration parameters.
Danger: this symbol is used to indicate a risk of electric shocks, which
could result in death or permanent injury.
Danger: this symbol is used to indicate a danger of inhaling dangerous
substances, which could result in death or permanent injury.
3
Summary
1 Introduction ............................................................................................................................................................. 4
2 Installing the detector .............................................................................................................................................. 4
3 Terminal block connections ..................................................................................................................................... 4
3.1 Connection to external devices ......................................................................................................................... 5
4 Installing the piping .................................................................................................................................................. 7
4.1 Piping specifications .......................................................................................................................................... 7
4.2 Fixing ................................................................................................................................................................. 7
4.3 Bends ................................................................................................................................................................. 7
4.4 End caps ............................................................................................................................................................ 8
4.5 Sampling holes .................................................................................................................................................. 8
4.6 Air outlet ........................................................................................................................................................... 8
4.7 Filters ................................................................................................................................................................. 8
4.8 Standard pipe configurations ............................................................................................................................ 9
5 Detectors .................................................................................................................................................................. 9
6.2 User functions ................................................................................................................................................. 11
6.3 Setup notes ..................................................................................................................................................... 14
7 Testing .................................................................................................................................................................... 16
7.1 Point detectors ................................................................................................................................................ 16
7.2 System ............................................................................................................................................................. 16
8 Maintenance .......................................................................................................................................................... 17
9 EN54-20 Sensitivity classes .................................................................................................................................... 18
10 Troubleshooting ................................................................................................................................................... 19
11 Specifications ....................................................................................................................................................... 20
4
1 Introduction
The ILS-2 System is an aspirating detector which uses a network of sampling pipes to channel air to the two high-
sensitivity point detectors housed inside the casing of the main detector. The use of a network of pipes offers a
larger area of protection coverage in comparison to traditional point detectors.
Up to three alarm levels can be configured, depending on the specific application.
A high-efficiency aspirator and a system of flow sensors guarantee correct airflow.
The amount of extracted air can be displayed on a 10-LED bar graph which also indicates the low and high airflow
thresholds.
Parameter configuration can take place entirely using the integrated buttons on the sensor.
ILS-2 is an autonomous device capable of signalling fault and alarm events via a relay with voltage-free contacts.
These contacts may then be connected to a monitoring and signalling control panel.
Important note: Aspirating Fire Detection Systems installed in the EU since June 2009 must comply with the
Construction Products Regulation Directive (89/106/EEC) and the corresponding European standard EN54-20.
This appliance has been tested and approved to guarantee general compliance with the abovementioned directive
and standards, strict adherence to this Product Guide is required to ensure that the installation meets all aspects
of these requirements.
2 Installing the detector
Note: this device should be installed by authorised personnel in accordance with local and national regulations.
Remove the transparent cover using the keys provided and loosen the fasteners. Use the template to position
the fixing holes accurately and secure the unit to a surface (wall or ceiling) using the 4 corner fixing points.
Make sure the wall plugs and fixing screws are suited to the installation surface.
3 Terminal block connections
For the system to work properly, it is essential that the enclosure is sealed so that air can only be drawn into the
system from the sampling pipe(s). For this reason, all wiring must pass through the specific cable routes and no
other holes must be made. To run the cable through the relevant inlet, make a small hole (using the tip of a
screwdriver) in the middle of the membrane and push the cable through into the unit. The hole in the membrane
can accommodate cables with a diameter between 4 and 10 mm, thus guaranteeing an airtight seal.
To access the terminal block and connect the cables, it is necessary to remove the display plate housing the
indicators, which is held in place and shut off by the transparent top cover. Take care when removing the board
and make sure that the ribbon cable underneath is not stretched. The ribbon cable must be removed from the
connector on the underside of the board to allow full removal of the board (see figure 2 and 3).
To prevent electric shocks or potential damage caused by fan rotation, cut off the
power supply before removing the cover.
All connections from the site to the main circuit board are made via terminals that can accommodate cables up to
2.5 mm
2
.
5
3.1 Connection to external devices
Figure 3-1: terminal block for connection to external devices
3.1.1 Connecting the Batteries / Power supply input
Figure 3-2: Ferrite core
ILS-2 must be powered by means of a 24 Vdc power supply unit with EN54-4 approval. The power supply must
be connected using the BATTERY terminals on board the terminal block, observing the correct polarity. The
minimum recommended size is 16 x 0.25 mm (18 AWG), or greater if the power supply unit is further than 5 m
away from the sensor.
A ferrite core is supplied to ensure correct electromagnetic compatibility (EMC). This core must be positioned
inside the unit and the power supply cables wound as shown in figure 3-2. The type of power supply unit required
depends on the speed of the fan used for the application; please refer to Table 11-2: Current Consumption vs Fan
Speed.
3.1.2 ACTION 2, ACTION 1 - Relay output
The voltage-free contacts of the relay ACTION (ACTION) will change status when the pre-alarm level is
exceeded. The Normally Open (NO) and Normally Closed (NC) contacts on the terminal block are available.
3.1.3 FIRE 2, FIRE 1 - Relay output
The voltage-free contacts of the relay FIRE (FIRE ALARM) will change status when the alarm level is
exceeded. The Normally Open (NO) and Normally Closed (NC) contacts on the terminal block are available.
3.1.4 FAULT 2, FAULT 1 - Relay output
In fault conditions, the FAULT relay will change status. The Normally Open (NO) and Normally Closed (NC)
contacts on the terminal block are available.
Note: NO/NC shown in the terminal block refers to the un-powered sensor status. In normal operating
conditions (power supply present) the NO contact is closed, while the NC contact is open.
6
3.1.5 External Reset
The application of a voltage of +24 Vdc to these terminals triggers a reset of all fault and alarm events
present.
7
3.1.6 USB Connector
The detector is equipped with a USB type B connector to allow connection to a PC via a US cable (not supplied).
This communication port allows configuration of the sensor, and downloading of logged data using the VSC
software.
The connector is protected by a screw-fit cover and this must be re-fastened after every use, to prevent dust and
dirt from settling on it.
4 Installing the piping
Several standard configurations of the pipe network are illustrated below.
TThe sizing software ASPIRE2 must be used to calculate the channelling time, dilution effects etc. for all the
pipe networks required for individual applications.
Use 25 mm red ABS piping with sampling holes drilled along its length. The piping will terminate with an end
cap, with a hole drilled in its centre. The position of each sampling hole should adhere to guidelines for point
smoke detectors. It is important to note that the concentration of smoke entering a single hole will be diluted
by clean air from other sampling holes and from the end cap hole.
4.1 Piping specifications
In accordance with EN54-20 standards, the pipes must be red ABS and conform to EN 50086-1
(Crushing 1, Impact 1, Temperature 31) with a nominal external diameter of 25 mm. The pipes are
normally supplied in 3-metre lengths and cut as required, but linked using solvent welded sockets or
connected with socket unions (inspectable).
IMPORTANT note: the ILS-2 pipe inlets are tapered so as to allow “push-fit” coupling of the piping coming
from the site. The end of the inlet pipe must be cut cleanly so as to allow airtight
coupling with the tapered inlet. The inlet piping junction with the tapered collector
MUST NOT BE GLUED: doing so will invalidate the sensor warranty.
4.2 Fixing
The standard fixing method for piping requires special clips or clamps. The fixing spacing (distance between two
adjacent clips) is typically 1.5 m.
4.3 Bends
Figure 4-1: 45° bend and 90° bend
The available bends are 90° and 45°. It is important to use 90° swept bends and not “sharp” ones, as sharp
bends introduce high pressure losses and increase the channelling time for the sampling holes downstream of
the bend.
8
4.4 End caps
Figure 4-2: End cap with central hole
The sampling pipes terminate with a cap which has a hole at the centre. The end cap hole should be considered
as the final sampling hole.
4.5 Sampling holes
The sampling holes are distributed along the piping and are usually drilled once the pipes have been installed,
using a drill bit with a suitable diameter. Drilling can be carried out prior to installation, taking care to space the
holes correctly in the area you wish to protect. Drilling should also be performed in such a way that residual ABS
is not left around the hole. After drilling, remove any ABS residue that has collected inside the pipe. This can be
done by sucking the air out with an external extractor, or by blowing compressed air through, which will push the
debris through to the end of the pipe; in the latter case you will need to fit the end cap afterwards. In standard
applications, the sampling hole faces “downwards”.
4.6 Air outlet
The extracted air, after being analysed, exits via the relevant hole on the enclosure. In some applications, the air
outlet must be moved so that it is a certain distance from the detector; this requires an outlet pipe. This is
necessary when, for example, you wish to reduce the noise level, reduce the risk of outlet obstruction, or the static
pressure of the room in which the air is released must be the same as the room from which the air is extracted,
etc.
The maximum permitted length for this outlet pipe is 10 m, in order to minimise airflow reduction.
The air outlet must be positioned with care, to ensure it is not obstructed accidentally.
4.7 Filters
Figure 4-3: Filters at the inlet of the ILS-2 detector
The sampled air is passed through a filter (code: 02-FL53) before it enters the optical detection
chamber.
9
4.8 Standard pipe configurations
Figure 4-4: Standard configuration for ILS-2
The double pipe configuration can have a maximum length of 200 m (max. 100 m per incoming pipe), with up to
18 x 3 mm sampling holes and a 6 mm end cap hole for each pipe.
The pipes must be the same length and have the same number of holes.
All configurations with maximum permitted pipe length and/or maximum number of sampling holes should have
the Alarm (FIRE) threshold set to LEVEL 1 (maximum sensitivity) and the fan speed set to 9 (maximum). The
use of bends as described in section 4.3 will have a minimal effect on performance (e.g. response time).
Note: the abovementioned values are based on EN54-20 certification testing. A reduction in pipe length may be
reflected in a lower fan speed, just as fewer holes may be reflected in an increased sensitivity level.
Complex piping configurations must be checked using the ASPIRE2 software.
5 Detectors
Caution:
If the detector/s is/are removed for maintenance purposes, it/they must be fitted in the positions
described above.
Changing the position of the detector(s) may result in false reporting in the event of a fault or
alarm.
USB port Type “B”
10
6 Setup
6.1 Display functions
ALERT (Alert)
ACTION (Pre-alarm)
LED BAR CHART (Smoke level and Fan speed)
FIRE (Fire alarm)
SMOKE DETECTOR FAULT (detector fault -
1 per detector)
ISOLATE (Disabled=relays not active)
AIRFLOW OK - HIGH AIRFLOW - LOW AIRFLOW
POWER ON (Power supply present)
FAN FAULT (Fan fault)
GENERAL FAULT (General fault)
RESET
MAINS FAILURE (Mains pow. supp. fault)
UNLOCK (Unlocked)
BATTERY LOW (Battery low)
CODE ENTRY (Access code)
DETECTION MODE
11
6.2 User functions
Figure 6-1: Programming buttons
Press and hold the SELECT and CHANGE buttons simultaneously until you hear the initialisation beep.
Press and release the SELECT button to move through the various configuration steps.
Press and release the CHANGE button to change the current parameter.
The corresponding LED will flash continuously to indicate the active function in that step.
To change the parameters, use access code 510.
Enter the three-digit access code 510. The numbers must be selected one at a time; e.g. press the CHANGE
button six times to illuminate the number 5 LED on the display, then press the SELECT button, etc. (the CODE
LED flashes during this procedure; the Unlock LED will light up on successful entry of the code).
Every time the CHANGE button is pressed, the LED indicator shifts one position to the right.
The following table lists the chronological steps to carry out in order to start the smoke detection aspiration system
correctly.
Bear in mind that:
Pressing the SELECT button scrolls through the various functions and the CHANGE button confirms any changes
made.
Pressing the CHANGE button changes the function values.
The list of available functions is provided in the table below.
12
Table 6-1: User functions for ILS-2
FUNCTION
DISPLAY
VALUE
NOTES
RECOMMENDE
D
Reset the unit
The RESET LED
flashes
Press CHANGE to reset the
outputs
Isolate the relay outputs
The ISOLATE LED is lit
steadily
Press CHANGE to Isolate or
when the system is
Reset the outputs
isolated and flashes
when it is running
Adjust the speed
The POWER LED
5
The greater the assigned value,
of the fan (0 = min., 9 =
max.)
flashes
the shorter the response time
Adjust the sensitivity
The FLOW OK LED
5
Sensitivity = 9 (flow sensor
of the airflow (v. 6.3.3)
flashes
most sensitive)
Sensitivity = 2 (flow sensor
less sensitive)
Select the value of the
The FLOW HIGH LED
8
HIGH FLOW threshold
flashes
Select the value of the
The FLOW LOW LED
2
LOW FLOW threshold
flashes
DOWN
Set the delay in
FLOW HIGH and LOW
LEDs
2
See table,
paragraph 6.3.3
indication of
flash together
FLOW FAULT
Set ALERT threshold
The ALERT LED flashes
3
Set threshold for
The ACTION LED
5
ACTION
flashes
Set FIRE threshold
The FIRE LED flashes
7
Select the mode of
One of the MODE LEDs
LED 1 ON = use only
detection
flashes
detector 1
LED OR ON = use only one
of the two detectors, the other is
for
backup
LED 1&2 ON = use
both detectors
Buzzer (buzzer)
The buzzer sounds
If the sounds emitted are
intermittently
long, the buzzer is active; if
the sounds are short it is not.
Set Autoreset or
The Laser fault LED
0 = Autoreset
Manual Reset
flashes
1 = Manual Reset
Calibrate flow
The FAN FAULT
Press and hold the CHANGE
button
sensors
LED flashes
for at least 2 seconds
The fan will stop temporarily
and restart
later.
Calibration is complete
when you see the
high and low flow LEDs, and an
LED among them indicating the
value
of the current flow across the
13
sensors.
14
If the access code has been entered (unit unlocked), press and hold the SELECT button for longer than
one second to exit “configuration” mode.
Press and release either the SELECT or CHANGE button (when the unit has exited configuration mode -
code not entered) to view the AIRFLOW on the LED bar chart.
The LED bar chart automatically reverts to displaying the smoke level (analogue value reading) after a few
seconds.
6.2.1 Detector mode
ILS-2 has three different operating modes as illustrated below (1 and 2 are internal detectors):
Mode 1 (1 only): Single detector
The detector displays the analogue smoke reading value in real time and the unit indicates when the
Alert, Action and Fire thresholds are exceeded.
Mode 2 (1 OR 2): Two installed detectors operating INDEPENDENTLY from one another.
The unit will show the HIGHEST reading obtained from the TWO detectors and will activate the Alert,
Action and Fire relays when ONE OF THE TWO detectors detects smoke values exceeding the relevant
thresholds. This mode allows detection redundancy and therefore guarantees correct operation even if
one of the detectors becomes faulty.
Mode 3 (1 AND 2): Two detectors work in tandem (Dual Consent)
The unit will show the LOWEST reading obtained from the TWO detectors and will activate the Alert,
Action and Fire relays when BOTH analogue values from the TWO detectors exceed the relevant
thresholds.
Notes: Mode 3 is not permitted in installations which require VdS approval.
ILS-2 is supplied in standard mode 1. If required jointly, the second detector will be supplied in Mode 2. If the
unit only houses one detector and mode 3 is programmed, a Detector Fault will be signalled.
6.3 Setup notes
The Fan Speed, Airflow Limits and Flow Sensitivity must be configured BEFORE unit calibration and
testing.
The following guidelines should assist in the commissioning of the system.
6.3.1 Fan Speed
The Fan Speed should be set as high as possible to achieve the fastest transport time from the sampling holes
to the sensor, which is especially important for longer pipe lengths that must conform to the requirements of
EN54-20 (please refer to Section 4.8: Standard pipe configurations).
However, a balance also needs to be achieved between unit performance and power
consumption. Table 11-1 provides the values necessary for this evaluation.
6.3.2 Airflow Fault signalling delays
When the airflow limits are exceeded, a Flow Fault indication will appear after a programmable time period.
The default Flow Fault indication delay time is approximately 30 seconds. Once the airflow reverts to a normal level,
the Flow Fault will be cleared within 18 seconds.
Table 6-2 lists the available values for this parameter.
In environments where the airflow may be affected by sudden temperature or pressure
changes, it may be necessary to increase the delay time accordingly.
15
Table 6-2: Flow Fault delay times
Bar chart
Flow Fault ind.
Flow Fault status
LED
delay (seconds)
exit delay (seconds)
0
15
2
1
30
18
2
60
18
3
90
18
4
120
18
5
150
18
6
180
18
7
210
18
8
240
18
9
270
18
Notes: Timings are approximate.
6.3.3 Flow Sensitivity
This setting determines the sensitivity of the unit in detecting blocked sampling holes or broken pipes.
The default flow sensitivity value of 9, which corresponds to a change in volumetric airflow of ± 20% from the
calibrated reading for at least the duration of the flow fault indication delay, see section 6.3.2 above.
For most installations, especially if compliance with EN54-20 is required,
the default setting should be used.
In certain circumstances, such as rapid changes in ambient air pressure due to the activation of air handling
units, doors opening/closing etc. the default setting may appear to be too sensitive.
Under these conditions, the flow fault indication delay setting should be increased to allow time for the air
pressure to stabilise after the temporary event.
Decreasing the flow fault indication times is only necessary under extreme operating conditions.
16
7 Testing
Note: the system checks should only be carried out by authorised personnel. Before undertaking any testing,
make sure that the proper authorities have been informed and that signals to the monitoring and signalling
control panel have been disabled, in order to prevent unwanted alarms.
7.1 Point detectors
With the unit powered up and plastic top cover removed, detector operation can be tested using a low
concentration smoke source or aerosol spray.
The point detectors can also be checked using a permanent magnet positioned at 7 o’clock on the sensor
cover.
This test electronically simulates the effect of smoke in the optical chamber.
7.2 System
Before checking the system as a whole, make sure the top cover of the unit is in place.
As a minimum requirement, a small amount of smoke should be introduced to the last sampling hole on each pipe
(or branch).
The choice of smoke source is dependant on the installation but in all cases the
smoke must be present for the duration of the test – aerosol sprays do NOT work on aspirated systems.
If the sampling holes are accessible then a basic check can be carried out with smoke matches or lighted tapers,
etc.; however, to carry out a test in which performance can be measured, please refer to Appendix A of the Code
of Practice for Aspirating Systems published by the F.I.A.
17
8 Maintenance
With normal use, the filter element will eventually become contaminated with dust particles contained in the
extracted air. It is recommended that the filter element (code 02-FL53) is replaced and detectors cleaned
every 6 months (more frequently for dirty environments).
Note: maintenance should be performed by authorised personnel. Before carrying out any maintenance, notify
the proper authorities and isolate (disable) the unit to prevent incorrect alarm statuses from being
triggered on the monitoring and signalling control panel.
Please follow the steps illustrated when performing a maintenance check on the system:
1. Remove the transparent cover using the special tool provided.
2. Disconnect the unit from the power supply.
3. Lift out the filter element from the inlet pipe (long-nosed pliers are recommended for this
operation).
4. Fit the new filter element, ensuring that it is not compressed during fitting. Fit it inside the pipe so that the
top surface of the filter is positioned flush with the pipe.
5. Remove the point detector(s) from the mounting base by twisting them anti-clockwise.
6. Remove the detector cover by prying away the 4 side tabs with a small-bladed flathead screwdriver.
7. Carefully vacuum the inside of the point detector. If further cleaning is required continue with Step 8,
otherwise skip to Step 12.
8. Remove the mesh insect screen and the optical chamber by pulling them out.
9. Clean the chamber again by vacuuming or blowing out dust and dirt particles.
10. Replace the optical chamber cover, aligning the arrows on the top with the arrow on the printed circuit board.
11. To replace the mesh insect screen, place it on the grooves over the optical chamber, turning it until it snaps
into place.
12. Replace the plastic cover using the status LED holes to align the cover.
13. Reinstall the detector onto its mounting base, ensuring that it is in the SAME POSITION (address 1 fitted
to detector 1 position).
14. Refit the transparent plastic cover, restore the power supply and carry out the Flow Calibration procedure.
15. Restore the relays’ enabled status.
18
9 EN54-20 Sensitivity classes
The detectors used in ILS-2 have been independently tested and approved for use in EN54-20 certified
Class A, B or C installations.
The following information will show the requirements for compliance with the abovementioned standard.
Table 9-1: Sensitivity and maximum number of holes vs Class EN54-20
Lev. Sensitivity
Maximum number of holes in each Class EN54
-
20
Maximum length of
piping (m)
Class C
Class B
Class A
1
18
6
3
100
2
9
3
1
100
3
4
1
N/A
100
4
1
N/A
N/A
100
5 or higher
N/A
N/A
N/A
N/A
Note: table 9-1 shows the limit that should not be exceeded for the 3 sensitivity classes. Figures are based on
the configurations shown in section 4.8: Standard pipe configurations.
The maximum number of holes is based on the following standard configurations:
Class A: 3 x 4 mm holes including the end cap hole.
Class B: 6 x 4 mm holes including the end cap hole.
Class C: 17 x 3 mm holes plus 1 x 6 mm end cap hole.
Note: any changes to the standard configuration should be verified using the ASPIRE2 modelling software.
19
10 Troubleshooting
PROBLEM
POSSIBLE SOLUTION
Power supply LED flashes
Make sure the power supply voltage is between 18 - 30 Vdc.
No LEDs lit on display and
fan NOT working
Make sure the 24 Vdc power supply is present and that the +/- polarities have been
observed. Make sure the fuse has been positioned correctly and that it has not
blown.
No LEDs lit on display and
fan WORKING
Make sure the ribbon cable is fully connected to the main circuit board and the
display.
Flow HI or LOW LED lit
Make sure the inlet pipes have been installed correctly, the cover is fitted properly
and the enclosure is fully sealed. Make sure the airflow calibration procedure has
been carried out (see section 6.2). Make sure the filter is in good condition (see
section 8).
Flow reading LED lit
Flow values on the LED bar
chart change erratically
Decrease the flow sensitivity and re-calibrate the unit (see section 6.2)
Flow reading LED lit No
extreme pipe breakage or
complete obstruction
conditions are detected
Increase the flow sensitivity and re-calibrate the unit (see section 6.2)
Detector Fault indication
Make sure the detector address is correct (see section 5)
Make sure the detector is fully seated in its base.
Make sure the correct mode has been selected (see section 6.2.1)
Make sure the detector optics are clean.
20
11 Specifications
Table 11
-
1: General Specifications, ILS
-
2
Number of detectors
1 or 2, laser point technology
Filter
Single-stage
Airflow sensors
Thermal devices - High and Low thresholds. 10-LED bar chart
Power supply voltage
18 - 30 VDC (24 VDC rated)
Relay contacts
1 A @ 30 Vdc
Unit current consumption
350 mA at 24 VDC without sampling pipes. See table below for typical
consumption values according to fan speed.
Maximum length of pipes
100 m
Protection rating
IP65 with air outlet piping installed (IP23 without)
Operating temperature range
From -10 to 50ºC
Operating humidity
From 10 to 95% RH (non-condensing)
Certifications
EN54-20 by VdS (G206066)
EN61000-6-3:2001(+A11:2004) (EMC)
EC Certifications
EN60950-1:2006 (Safety)
CPD (89/106/EEC)
Table 11-2: Current consumption vs Fan Speed
LED bar chart value
0
1
2
3
4
5
6
7
8
9
Fan speed
1
2
3
4
5
6
7
8
9
10
Current (mA)
110
120
130
150
170
190
220
235
265
300
Notes: the above values were recorded using an installation with a 10 m length of piping (external
diameter 25 mm). The unit was powered at 24 VDC.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21

Comelit ILS-2 User manual

Category
Smoke detectors
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI