Danfoss Termix VMTD MIX IE Operating instructions

Type
Operating instructions
InstallationGuide
TermixVMTDMIX-IEwithcompleteinsulation
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Start-up..............................................................8
4.3Electricalconnections.............................................9
5.0Design.............................................................10
5.1Design...............................................................10
5.2Schematicdiagram................................................11
6.0Controls..........................................................12
6.1Heatingcircuit......................................................12
6.2DHWtemperaturecontrol........................................16
6.3Other.................................................................16
6.4Extras................................................................18
6.5Maintenance........................................................18
7.0Troubleshooting..............................................19
7.1Troubleshootingingeneral......................................19
7.2TroubleshootingDHW............................................19
7.3TroubleshootingHE...............................................20
7.4Disposal.............................................................21
8.0Declaration......................................................23
8.1Declarationofconformity........................................23
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
1
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
2
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
2.0Functionaldescription
Districtheatingsubstationfordirectheatingand
instantaneousdomestichotwaterwiththermostaticcontrol.
Designedforwall-mounting.
Application
TheTermixVMTDMIX-IEisacompletesolutionwithbuilt-inwater
heaterandheatingsystemwithdifferentialpressurecontrol
andmixingloop.TheTermixVMTDMIX-IEisapplicableforfor
single-familyhousesandfordecentralizedsystemsinmulti-family
houses.
Districtheating(DH)
Thesubstationisprefabricatedwithadifferentialpressure
controller,ttingpieceandsensorpocketforinsertionofa
heatmeteraswellasstrainerandballvalves.Furthermorethe
substationisdeliveredwithamixingloopincludingpump,controls
andnon-returnvalve.
Heating(HE)
Theheatingcircuitisdesignedfordirectconnection.The
differentialpressurecontrollersetstheoptimumoperation
conditionsforradiatorthermostatsinordertoenableindividual
temperaturecontrolineachroom.Themixingloopcreatesa
suitabletemperaturelevele.g.foroorheating.Inordertoenable
atimedependenttemperaturecontrolprogram,azonevalvewith
actuatorandaroomthermostatcanbeincludedasanoption.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand
theheatexchangerandthetemperatureisregulatedwithaow
compensatedtemperaturecontrollerwithintegrateddifferential
pressurecontroller.TheheatexchangercoolsouttheDHwater
veryefciently,therebycreatinganexcellentoperatingeconomy.
TheDanfossIHPTvalveensuresastablehotwatertemperature
byvaryingloads,supplytemperaturesandbyhighandvarying
differentialpressurewithouttheneedforreadjustingthevalve.
Thisprotectstheheatexchangeragainstoverheatingandlime
scaleformation.FurthermoretheIHPTvalvehasanintegrated
idletemperaturecontroller,whichkeepsthehousesupplyline
warm.Thisshortensthewaitingperiodsduringsummerwhen
theheatingsystemisinreducedoperation,whichisidealwhere
highcomfortisrequested.
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
3
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Domestichotwater(DHW)
6.Domesticcoldwater(DCW)
Connectionsizes:
DH+HE:
G¾”(int.thread)
DCW+DHW:
G¾”(int.thread)
Dimensions(mm):
Withoutinsulation:
H800xW530xD375
Withcover:
H800xW540xD430
Weight(approx.):25kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
5
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
4.1.2Dismantletheinsulationfront
Pulltheinsulationfrontusingthehandleinthetopofthecover
whilstkeepingtheECLcontrollerinitsplace.
6
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
KeeptheECLcontrollerinitspositionwhileremovingtheinsulation
frontcompletelybypullingatthelowerendoftheinsulationfront.
4.1.3Mountingthedisplayoftheenergymeter
Markthepositionofthexationpointsofthebracketfortheenergy
displayandscrewthetwoplugssuppliedintotheinsulationfront.
Mountthebracketforthedisplayoftheenergymeter.
Mountthedisplay/calculatoroftheenergymeterontothebracket.
Pullthewiresfromthesensorsinsidetheunitthroughthe
duct/cut-outintheinsulationplate.
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
7
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
4.2Start-up
Start-up,Heatingwithmixingloop
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Ifthesystemoperatesinaccordancewithdesign,itcanbeput
toregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
8
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
9
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
27
Actuator,HE
F
Electroniccontroller
31
Differentialpressurecontroller
9
Strainer
41
Fittingpiece,energymeter
10
Circulatorpump,HE
63
Sieve
14
Sensorpocket,energymeter
74
IHPTcontroller,DHW
10
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
5.2Schematicdiagram
DHW
DCW
DH
Supply
HE
Supply
DH
Return
HE
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
B
Heatexchanger,DHW
14
Sensorpocket,energymeter
31
Differentialpressurecontroller
F
Electroniccontroller
16
Outdoorsensor
39
Connectionclosed
1
Ballvalve
18
Thermometer
41
Fittingpiece,energymeter
2
Singlecheckvalve
19
Surfacesensor
63
Sieve
9
Strainer
27
Actuator
74
IHPTcontroller
10
Circulatorpump
29
2-waymotorizedvalve
DHW:DomesticHotWater
DCW:
DomesticColdWater
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:PN10(PN16versionsareavailableonenquiry)
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
1.0bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
11
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2HEtemperaturecontrol
TheHEowtemperatureintheheatingcircuitiscontrolledbythe
HEtemperaturecontroller.
6.1.3RAVKcontroller
RAVKcontroller(25-65°C).Thetemperaturesettingisasfollows:
1=25°C
2=35°C
3=45°C
4=55°C
5=65°C
Thevaluesareintendedasaguide.
Thermostaticcontrol
ThetemperatureoftheHEowlineisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
12
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
6.1.5Outsidetemperaturesensor(insu)
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
13
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
6.1.6Circulatorpump
UPM3Pumpscanbecontrolledinconstantpressure,proportional
pressureorconstantspeedmodedenedbythemeansofasmart
userinterface.
Thevariablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
ALPHA2pumpshavebothvariablespeedpressurecontrolled
operation,andstandardselectablethreespeedoperation.
TheuniqueAUTOADAPTfeatureallowsthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
UPSpumpsareacompleterangeofcirculatorpumpswith3
speeds.
EnergylabellinguptoclassB
14
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
6.1.7GrundfosUPM3AUTOLinstructions
Controlmode
Youcanswitchfromtheperformanceviewtothesettingsviewbypressingthepushbutton.Thesettingsviewshowswhichmode
controlsthecirculator.After2seconds,thedisplayswitchesbacktoperformanceview.
Ifyoupressthebuttonfor2to10seconds,theuserinterfaceswitchesto"settingselection"iftheuserinterfaceisunlocked.Youcan
changethesettingsastheyappear.Theselectionofthecontrolmodedependsonthesystemtypeandtheallocationofpressurelosses.
Ifyoupressthekeylockformorethan10seconds,youcantogglebetweenenabling/disablingthekeylockfunction.
Function
Recommendedfor
Green
YellowYellowYellowYellow
Proportionalpressure1
1-pipesystems
µµ
Proportionalpressure2
µµµ
Proportionalpressure3
2-pipesystems
µµµµ
Constantpressure1
Underoorheating
µµ
Constantpressure2
µµµ
Constantpressure3
µµµµ
ConstantCurve1
µµµ
ConstantCurve2
µµµµ
ConstantCurve3
µµµµµ
ConstantCurveMax.
µµµµ
Operationstatus
Function
Recommendedfor
Green
YellowYellowYellowYellow
Standby**OnlyPWMcontrolled
µ
0%P125%
µµ
25%P150%
µµµ
50%P175%
µµµµ
75%P1100%
µµµµµ
Alarmstatus
Function
Recommendedfor
RedYellowYellowYellowYellow
Blocked
µµ
Supplyvoltagelow
µµ
Electricalerror
µµ
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
15
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
6.2DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.2.1IHPT90controller(45–65°)
IHPTisaself-actingow-compensatedtemperaturecontrollerwith
integrateddifferentialpressurecontroller.
TheIHPToperatesatitsbestatDHsupplytemperaturesofupto
100°C.
Byturningthehandlefortemperaturesettingin(+)direction
thesettingisincreased,byturningitin(-)directionthesettingis
decreased.
Turns*DHWTemperatureSetting[°C]
064
1
61
258
3
55
4
52
5
48
6
44
7
43
*Startposition:Handleturnedfullyin(+)direction.
Thevaluesareintendedasaguide.
6.3Other
6.3.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
16
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
6.3.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
6.3.3GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe
secondarysideoftheTermixwaterheatersandcanbeusedasa
substitutetothesafetyvalve.
Furthermorethepressureequalizerabsorbsapossibleincreasein
pressure,soadischargeoutletisomitted.
TheGTUPressureEqualizermaynotbeappliedinsystemswithhot
watercirculation.
6.3.4Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater
onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do
notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand
tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
17
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
6.4Extras
6.4.1Circulationpipe
Thecirculationpipesetismounteddirectlyonthecontroller.
Thesetincludescirculationpipe,singlecheckvalveandtting.
Whenmountingthehotwatercirculationdirectlyonthecontroller
thehotwatercirculationtemperaturewillbeequaltotheidle
temperature.Theidletemperatureisafewdegreeslowerthanthe
setdomestichotwatertemperature.
6.5Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
18
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
Idletemperaturetoolow(forstations
equippedwithIHPT).
Setpointtoolow.Turnthermostatin(+)direction.
DanfossDistrictEnergy
VI.JV.P1.02/LUK40283
DEN-GT
19
InstallationGuideTermixVMTDMIX-IEwithcompleteinsulation
7.3TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronDHcircuit
clogged.
Cleanthelter(afterconsultingtheDH
plantoperator).
Defectiveorwronglyadjusteddifferential
pressurecontroller.
Checktheoperationofthedifferential
pressurecontrollercleanthevalveseatif
required.
Sensordefectiveorpossiblydirtinthe
valvehousing.
Checktheoperationofthethermostat
cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor
defective-possiblypowerfailure.
Checkifthesettingofthecontroller
iscorrectseeseparateinstructions.
Checkthepowersupply.Temporary
settingofmotortomanual”controlsee
instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin
thepumphousingseepumpmanual.
Thepumpissetattoolowspeedof
rotation.
Setthepumpathigherspeedofrotation.
Pressuredropthepressuredropon
theradiatorcircuitshowslowerthan
recommendedoperatingpressure.
Fillwateronthesystemandcheckthe
functioningofthepressureexpansion
vesselifrequired.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature
adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Checkreplace.
Unevenheatdistributioninbuilding
becauseofincorrectlysetbalancingvalves,
orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor
branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
Wrongsettingofthermostatorof
automaticcontrols,ifany.
Adjustautomaticcontrols,see
instructionsforautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callautomaticcontrolsmanufactureror
replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
DHsupplytemperaturetoolow.
Wrongsettingofautomaticcontrols,ifany.
Adjustautomaticcontrolsseeinstructions
forautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callinautomaticcontrolsmanufactureror
replacecontroller.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
Wrongplacement/ttingofoutdoor
temperaturesensor.
Adjustlocationofoutdoortemperature
sensor.
Strainerclogged.Cleangate/strainer.
20
DEN-GT
VI.JV.P1.02/LUK40283
DanfossDistrictEnergy
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Danfoss Termix VMTD MIX IE Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI