Metasys Ventilation Controller
12
Procedure Overview
Table 2: Using the MVCA with the DX-9100
To Do This Follow These Steps:
Install a UPM
In a secure location, install the UPM according to procedures listed in the
Universal Packaging Module Technical Bulletin (LIT-6363070). Note
shock and equipment damage hazards. Connect the N2 Bus to the
DX-9100. Complete field connections to the terminal blocks before the
controller is attached to the base. If you need more room, remove the
bottom endcap of the UPM by disconnecting the assembly screws.
Complete the field wiring and reassemble the endcap, making sure not to
pinch any wires. In cramped or poorly-lit areas, reassembly can be
difficult.
Install Air Sampling Devices
and Tubing
Select locations for the air sampling devices in the air flows. Place the
sampling device with the open end facing into the air flow. Seal the vent
around the tubing. Install the remaining devices. Remove the packing
material and tie-wrap from the air pump.
Trend Data
For simple monitoring, refer to the appropriate workstation user’s manual
for your system.
Check the Solenoid Valves
Make sure the valves change state every sixty seconds and verify that
these state changes are in the proper sequence.
Calculate the OA Flow
After the system has stabilized and the Supply Air (SA) flow has been
checked, use the following equation to determine whether the system is
functioning correctly based on the CO
2
levels of OA, SA, and
RA (Return Air) flows: [OA CO
2
] ≤ [SA_CO
2
] ≤ [RA_CO
2
].
Check the Controller
Application
To check the controller application, use the GX-9100 software to verify
that the system remains stable as the control strategy changes from
OA flow to air temperature. If the OA Flow Controller is in stable control
and, for five minutes, the Discharge Air Temperature
Controller/Economizer control is calling for a larger output than the OA
Flow Controller, the Discharge Air Temperature Controller/Economizer will
take control. If, for five minutes, the Discharge Air
Temperature/Economizer is in control, and the feedback of the OA Flow
Controller is less than the setpoint of the OA Flow Controller, and the
30 ppm CO
2
differential exists between the OA CO
2
and the RA CO
2
concentration values, the OA Flow Controller will take control.
Reload the Controller
Application
No installation is required, but if you need to reload the MVCA, obtain
DXMVCA.EXE from The Advisor by clicking on Engineering/Technical >
Field Support Center > Digital Controllers > DX-9100 > DXMVCA.EXE.
For ABCS, on The Exchange, click on Technical Support > Digital
Controllers > DX-9100 > DXMVCA.EXE. Use the GX-9100 Configuration
Tool to download the contents into the controller.