Johnson Controls NIE29 Series Installation Instructions Manual

Type
Installation Instructions Manual
NIE29 Installation Instructions
MS-NIE29xx-x
(barcode for factory use only)
Part No. 24-10143-594, Rev. H
Software Release 9.0
Issued August 2017
Refer to the QuickLIT website for the most up-to-date version of this document.
Application
Important: NIEx9s are compatible with Metasys® system Release 7.0 and later. You may apply the dual trunk
integration feature to NIEx9s purchased prior to the current release by using the NIEx9 Driver Manager
tool. For information on how to apply the latest package and license files that support dual trunks, refer
to the NIEx9 Driver Manager Application Note (LIT-12011919).
The Metasys Network Integration Engine (NIE) controller is a web-enabled, Ethernet-based, supervisory device that
serves two roles. Its first role is to integrate the Metasys Building Management System to other standard building
management communication technologies. Integrations include the following network protocols: BACnet®, LONWORKS®,
N2 Bus, Modbus®, Meter-Bus (M-Bus, European Standard EN 1434-3), KNX, and other third-party proprietary
protocols. In this capacity, the NIE29 monitors and supervises a wide variety of HVAC, lighting, security, fire, electrical
and thermal measuring and access control equipment.
Its second role is to provide the I/O point connectivity and digital control capabilities of a Metasys Field Equipment
Controller (FEC). In this capacity, the NIE29 Series controller provides a cost-effective solution designed for central
plant applications and large built-up air handlers.
For the Modbus and M-Bus protocols, one NIE29 can support two integrations: two Modbus, two M-Bus, or one of
each, significantly expanding the engine's flexibility. See Table 11 for a list of all supported dual trunk applications.
Important: The NIE29 is shipped with a license and driver for the communication protocol that was ordered. If you
re-image the engine, the license and driver are deleted and the engine is not able to communicate with
the required protocol. If you need to re-image the engine, use the NIEx9 Driver Manager first to preserve
the protocol driver and license file before you re-image. For details, refer to the NIEx9 Driver Manager
Application Note (LIT-12011919).
Figure 1 shows the physical features and dimensions of the MS-NIE2966-0 model. See NIE29 Model Ordering
Information Table for NIE29 Series model information and features.
Installation
Follow these guidelines when installing an NIE:
Transport the NIE in the original container to minimize vibration and shock damage to the NIE.
Verify that all the parts shipped with the NIE.
Do not drop the NIE or subject it to physical shock.
Parts Included
one NIE with removable terminal plugs
one data protection battery (installed and connected when the NIE is shipped)
one installation instructions sheet
Materials and Special Tools Needed
three fasteners appropriate for the mounting surface (M4 screws [#8] screws)
one 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for mounting the DIN rail
1NIE29 Installation Instructions
Figure 1: NIE29 Physical Features, Dimensions, and Required Mounting Space Around Engine
Mounting
Location Considerations
Follow these guidelines when mounting an NIE:
Ensure that the mounting surface can support the NIE and any user-supplied panel or enclosure.
Mount the NIE in a horizontal, upright orientation.
Mount the NIE on an even surface in wall mount applications whenever possible. If you must mount the NIE on
an uneven surface, be careful not to crack the mounting clips or NIE housing when tightening the screws. Use
shims or washers to mount the NIE evenly on the mounting surface.
Mount the NIE in areas free of corrosive vapors, and observe the environmental limitations listed in the Technical
Specifications section.
Allow sufficient space to accommodate cable and wire connections (Figure 2).
Do not mount the NIE where the ambient temperature may exceed 50°C (122°F).
Do not mount the NIE on surfaces that are prone to vibration or in areas where electromagnetic or radio frequency
emissions can interfere with NIE communication.
Do not obstruct the NIE housing ventilation holes.
Do not mount a power transformer below the NIE.
On applications where the NIE is mounted inside a panel or enclosure, follow these additional guidelines:
Do not install the NIE in an airtight enclosure.
Do not install heat-generating devices in the enclosure with the NIE that may cause the ambient temperature to
exceed 50°C (122°F).
2NIE29 Installation Instructions
Mounting the NIE
Wall Mount Applications
Use the holes in the three mounting clips for wall mount applications.
To mount the NIE on a wall (or other vertical surface):
1. Ensure that all three mounting clips are inserted into the back of the NIE housing and then pulled outward and
snapped firmly into the extended position (Figure 3).
2. Mark the location of the three wall mount holes using the dimensions in Figure 2.
3. Drill holes in the wall at the locations marked in Step 2 and insert wall anchors (if necessary).
Figure 2: NIE Mounting Screw Hole Dimensions and Mounting Area Requirements (mm/in.)
4. Position the NIE and insert the screws through the holes in the mounting clips, and carefully tighten all the screws.
Important: Do not overtighten the mounting screws. Overtightening the screws may damage the mounting
clips or NIE housing.
DIN Rail Mount Applications
To mount the NIE on a DIN rail:
1. Securely mount a 20 cm (8 in.) or longer section of DIN rail horizontally and centered in the required space.
2. Ensure that the bottom two mounting clips are pulled outward and snapped firmly into the extended position
(Figure 3).
Figure 3: DIN Rail and Mounting Clip Features on the Back of an NIE
3. Hang the NIE by the DIN rail hooks (Figure 3) on the top track of the DIN rail, and position the NIE DIN rail
channel snugly against the tracks of the DIN rail.
4. Push the bottom mounting clips up to secure the NIE on the DIN rail tracks.
3NIE29 Installation Instructions
To remove the NIE from the DIN rail, snap the bottom DIN clips to the outward extended position and carefully lift
the NIE off the DIN rail.
Enclosure Mount Applications
Mount the enclosure in accordance with the manufacturer’s instructions, and then mount the NIE in the enclosure
following the guidelines in the Location Considerations and Mounting the NIE sections.
Wiring
Power Supply, Network, and Communication Connections
See Figure 1 for the location of the NIE’s power supply terminal, bus terminals and ports, USB port, and Ethernet
port.
Note: Do not remove the red terminal block keys from the board mounted terminal blocks. Removing the keys can
result in a removable terminal plug being plugged into the wrong terminal block, which can cause the NIE to
malfunction.
24~ Supply Power Terminal Block
The 24~ supply power terminal block is a gray, keyed, removable 3-terminal block located on the top side of all NIE
models (Figure 1 and Figure 13).
In North America, the NIE requires a Class 2, 24 VAC, 25 VA minimum power supply. Outside North America, use
a 24 VAC safety extra-low voltage (SELV) transformer at the appropriate rating. A minimum input voltage of 20 VAC
is required for the NIE to operate properly.
Note: The maximum power consumption of an NIE29 is 25 VA, but that does not include power for internally sourced
binary output (BO) points. Applications that provide power to BO points and configurable output (CO) points
configured as BO points can require up to 125 VA of additional power over the 25 VA minimum required for
the NIE29.
SA Bus Terminal Block
The brown, keyed, removable, 4-terminal SA BUS terminal block (Figure 1) is provided on all NIE models. Connect
the 4-wire SA Bus cable to the SA BUS terminal block. See the SA Bus Rules section for more information.
SA Bus Modular Port
The 6-Pin modular Sensor/Actuator (SA) Bus port is available on all NIE models (Figure 1 and Figure 4). The SA
BUS port connects to:
a Wireless Commissioning Converter (MS-BTCVT-1) to commission the NIE with the Controller Commissioning
Tool
a DIS1710 Local Controller Display to provide a display screen on NIE29 models without an integral display
screen
an NS Series Network Sensor to provide room temperature data to the NIE
4NIE29 Installation Instructions
Figure 4: Pin Number Assignments for Sensor, SA Bus, and FC Bus Ports on NIE, FEC, IOM, and VMA16
FC Bus Terminal Block
The blue, keyed, removable 4-terminal block FC BUS terminal block (Figure 1) is designed for RS485 serial protocol
field buses and is available on NIE models that support N2 Bus, Master-Slave/Token-Passing (MS/TP) FC Bus
applications. Depending on the NIE29 model:
connect the 3-wire N2 Bus to the FC BUS terminal block on NIE models that support N2 Bus applications. See
Figure 5 and the N2 Bus Rules section for more information.
connect the 3-wire MS/TP FC Bus to the FC BUS terminal block on NIE models that support MS/TP FC Bus
applications. See Figure 5 and the MS/TP Bus Rules section for more information.
The SHLD terminal on the FC BUS terminal block can be used as a convenient terminal to connect cable shield
drains in daisy-chain bus applications that use shielded cable.
FC Bus Modular Port
The 6-pin modular Field Controller (FC) BUS port is available only on NIE models that support MS/TP or N2 Bus
applications (Figure 1 and Figure 4). Connect a Wireless Commissioning Converter (MS-BTCVT-1) to the modular
FC BUS port to commission the NIE with the Controller Configuration Tool (CCT).
LONWORKS® Network Terminal Block
The blue, keyed, removable, 3-position LON terminal block connects a LONWORKS network trunk to NIE29 models
that support a LONWORKS network trunk. The shield (SHD) on the LON terminal block is soft grounded to the NIE
chassis terminal, and you can use it as a convenient terminal to connect cable shield drains in daisy-chain bus
applications that use shielded cable.
RS232C Serial Port
The RS232C serial port provides direct connection to a Modbus RTU or M-Bus network using a standard 9-pin
female data terminal equipment (DTE) to 9-pin female DTE null modem cable. Integration of only one device is
permitted. If the RS232C serial port is not used to integrate a vendor protocol, you can connect to a computer serial
port to browse to the NIE or to connect to a VT100 or a computer with a VT100 emulator and perform diagnostic
procedures. Refer to the Metasys® System Extended Architecture Direct Connection and Dial-Up Connection
Application Note (LIT-1201639) for more information about direct connections to an NIE.
Standard USB Port
The USB port connects to an external flash drive that can store diagnostic information when the NIE is placed in
diagnostic mode. You can otherwise configure the USB serial port to use an optional, user-supplied external modem.
5NIE29 Installation Instructions
Ethernet Port
The Ethernet port, labeled ETHERNET, is an 8-pin RJ-45 network port for connecting the NIE to Ethernet networks.
NIE29 engines can connect to Ethernet networks at 10 or 100 Mbps. Use this port for connecting a Modbus TCP,
M-Bus TCP, or KNX network.
Wiring Rules for Networks and Field Buses
All NIE29 Series models are designed to connect to Ethernet IP networks and support a single SA Bus.
Depending on the model, an NIE29 also supports either an MS/TP field bus trunk, an N2 Bus trunk, or a LONWORKS
network trunk. All models support two vendor integrations, such as two Modbus, two M-bus, or one of each. Or, if
a KNX integration is required, three KNX IP Gateways are supported for one NIE29. See Table 11 for a list of all
supported dual trunk applications. The rules, guidelines, and wiring considerations for each type of network or field
bus application are provided in the tables of this document.
IP Ethernet Network Rules
All NIE29 models are designed to connect to properly configured IP Ethernet networks, including Modbus TCP,
M-Bus TCP, or KNX. Refer to the N1 Ethernet/IP Network Technical Bulletin (LIT-6360175) for recommended parts
and part numbers. Observe the IP Ethernet network rules in Table 10.
Note: The Media Access Control (MAC) address is printed on a label on the NIE housing.
MS/TP Bus Rules
The MS/TP Bus connects Field Equipment Controllers (FECs), VMA1600s, Input/Output Modules (IOMs), TEC
Series thermostats, and third-party MS/TP controllers to NIE296-x models.
NIE296x models support an FC Bus trunk with up to 32 MS/TP devices. Observe the rules in Table 3 when designing
and installing the connected FC Bus.
SA Bus Rules
The Sensor/Actuator bus (SAB) connects the Metasys IOMs, NS Series Network Sensors, DIS1710 Local Controller
Display, specified variable frequency drives, and Wireless Commissioning Converter (MS-BTCVT-1) to an NIE.
Observe the rules in Table 4 when designing and installing the SA Bus for your application.
N2 Bus Rules
The N2 Bus connects N2 controllers to specified NIE29 models. NIE291x models support a single N2 Bus trunk with
up to 32 N2 devices.
Observe the rules in Table 1 when designing and installing the connected N2 Bus.
Modbus RTU Rules
The RS-232 port supports connection of one Modbus RTU (RS-232) device. With the addition of an RS-232/RS-485
converter and connection to the RS-232 port, up to 32 Modbus RTU (RS-485) devices are supported. Observe the
rules in Table 2 when designing and installing the connected Modbus RTU Bus.
LONWORKS Network Guidelines
The LON Bus connects up to 32 LONWORKS Network controllers to NIE292x models. Observe the rules in Table 7,
Table 8, and Table 9 when designing and installing the LONWORKS Network trunk.
For more information on LONWORKS networks, refer to the LONWORKS LN-Series Network Communication and Interface
Guide Technical Bulletin (LIT-12011253).
6NIE29 Installation Instructions
Wiring the NIE
Important: Do not connect 24 VAC supply power to the NIE before finishing wiring and checking all wiring
connections. Short circuits or improperly connected wires may result in permanent damage to the
equipment.
Important: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations.
The NIE is a low-voltage device (<30 VAC) in North America and an extra low-voltage device in Europe.
Do not exceed the NIE electrical ratings.
Important: Do not remove the terminal block keys. The terminal block plugs and the terminal sockets are keyed
to fit together in the correct configuration only.
Important: Prevent any static electric discharge to the NIE. Static electric discharge can damage the NIE and void
any warranties.
Important: Ensure the network and field bus wiring meets the specifications, rules, and guidelines in the Power
Supply, Network, and Communication Connections section in this document.
Mount the NIE securely before wiring the NIE.
Follow these guidelines when wiring an NIE:
Route the supply power wires and communication cables at least 50 mm (2 in.) away from the vent slots on the
sides of the NIE housing.
Provide slack in the wires and cables. Keep cables routed neatly around the NIE to promote good ventilation,
LED visibility, and ease of service.
Wiring the NIE for N2, MS/TP, LONWORKS, or Modbus RTU Protocol
1. Connect the Ethernet cable to the RJ-45, 8-pin Ethernet port on the NIE shown in Figure 1.
2. If using an external modem, connect the modem to USB A using the proper cable.
3. Connect the Building Automation System (BAS) network cables to the appropriate ports.
For an N2 or MS/TP network, connect the 3-wire bus cable to one of the removable 4-terminal blue plugs
labeled FC Bus (Figure 5).
Note: If an N2 or MS/TP bus is connected to the NIE, you must set the NIE EOL switches to the proper
positions. See the Setting the End-of-Line Switch section. The Modbus RTU network does not require
termination.
For LONWORKS compatible networks, connect the 2-wire cable from the LONWORKS network trunk to the
removable 3-terminal blue plug labeled LON (Figure 6).
Note: The LONWORKS network trunk is available on the NIE292x-0 model only.
7NIE29 Installation Instructions
Figure 5: FC Bus Terminal Block and Wiring Connections
Figure 6: LONWORKS Network Terminal Block and Wiring Connections
4. For Modbus RTU (RS-485) protocol, use a cable to connect the RS-232/RS-485 converter to the RS232C serial
port on the NIE.
Note: The maximum cable length between devices connected though an RS-232 line depends on the baud
rate. In general, the length should not exceed 15 meters at 9600 baud.
5. Terminate the wires from the RS-485 terminal on the converter to the RS-485 port on the vendor device (Figure
7). The RS-485 bus is a two-wire network.
a. Connect the converter's + A terminal to the device's + (or A) terminal.
b. Connect the converter's - B terminal to the device's - (or B) terminal.
c. If the device has a Signal Ground or Reference terminal, connect this to the converter's CG2 terminal.
8NIE29 Installation Instructions
Figure 7: Connection Between Converter and Device
6. Set the NIE EOL switches to the proper position. See Setting the End-of-Line Switch.
7. To add additional vendor devices, terminate the wires from one device to the next as shown in Figure 8. No more
than two wires may be connected to each terminal to ensure the daisy chain configuration. See Wiring Rules for
Networks and Field Buses for the Modbus protocol.
Figure 8: Daisy Chained Devices
The completed wiring should look similar to Figure 9.
Figure 9: Modbus RTU Wiring Detail Overview
8. Terminate the 24 VAC supply power wires from the transformer to the removable power terminal block plug on
the NIE (Figure 10).
9NIE29 Installation Instructions
Figure 10: 24 VAC Supply Power Wiring
Note: Power supply wire colors may be different on transformers not manufactured by Johnson Controls. Follow
the transformer manufacturer’s instructions and the project installation drawings.
9. Terminate the 24 VAC supply power wires from the transformer to the converter. No additional external power
adapter is required. Terminate the hot and common wires as desired. The NIE does not require an earth ground
connection.
Note: The 24 VAC power should be terminated to all network devices so transformer phasing is uniform across
the devices. Powering network devices with uniform 24 VAC supply power phasing reduces noise,
interference, and ground loop problems.
Wiring the NIE for M-Bus Protocol
1. Connect the Ethernet cable to the RJ-45, 8-pin Ethernet port shown in Figure 1.
2. Connect from the RS232C serial port on the NIE to the RS-232 connecter of the level converter. Wire to terminals
GND, RxD, and TxD as shown in Figure 11.
3. Terminate the M- and M+ wires on the level converter (Figure 11) to the meters using a free (star, tree, or line)
topology. Specific cabling can vary depending on the topology and site. See Wiring Rules for Networks and Field
Buses.
Note: If the number of M-Bus unit loads or distances exceeds the specifications of a level converter, you can
connect an M-Bus repeater to the converter to increase the number of unit loads and distances. The
converter shown in Figure 11 is capable of handling up to 6 units loads, while other models can handle
up to 100. See NIE29 Model Ordering Information Table for a list of M-Bus devices.
4. Terminate the 24 VAC supply power wires from the transformer to the removable power terminal block plug on
the NIE (Figure 10).
Note: Power supply wire colors may be different on transformers not manufactured by Johnson Controls. Follow
the transformer manufacturer’s instructions and the project installation drawings.
5. Terminate the 24 VAC supply power wires from the transformer to the -/~ and +/~ terminals as shown in Figure
11.
10NIE29 Installation Instructions
Figure 11: M-Bus Level Converter
Wiring the NIE for KNX Protocol
1. Connect an Ethernet cable to the RJ-45, 8-pin Ethernet port shown in Figure 1.
2. Connect another Ethernet cable to the port on the front of the KNX gateway (Figure 12).
Note: Depending on the size of your network, you can use either a KNX interface or router as a gateway. The
Interface connects the NIE to a single KNX line, while the router acts as both an interface and a line
coupler over Ethernet to connect the NIE to the network, not to a single device.
11NIE29 Installation Instructions
Figure 12: KNX/IP Interface Router
3. For a single KNX line, terminate the wires from the red and black terminals on the gateway to the devices. For
multiple KNX lines, terminate the wires from the red and black terminals on each gateway to the devices on the
same KNX line.
Note: Specific cabling can vary depending on the topology and site. See Wiring Rules for Networks and Field
Buses.
4. Terminate each KNX gateway to its own dedicated power supply on the KNX line.
Wiring Input and Output Terminals
NIE29 Series models support up to 33 hard-wired I/O points including:
7 BO points
4 CO points
4 analog output (AO) points
8 binary input (BI) points
10 Universal Input (UI) points
See Figure 13, Figure 14, and Terminal Wiring and Cable Length Guidelines Tables for more information.
The I/O points are designed for multiple types of input or output, and most of the points are configured in the CCT
software.
Terminal Functions, Ratings, Requirements, and Wiring Guidelines
Input and Output Wiring Guidelines
Table 12 provides information and guidelines about the functions, ratings, and requirements for the NIE input and
output terminals and references to guidelines for determining proper wire sizes and cable lengths.
12NIE29 Installation Instructions
In addition to the wiring guidelines in Table 12, observe these guidelines when wiring NIE inputs and outputs:
Run all low-voltage wiring and cables separate from high-voltage wiring.
All input and output cables, regardless of wire size or number of wires, should consist of stranded, insulated,
and twisted copper wires.
Shielded cable is not required for input or output cables.
Shielded cable is recommended for input and output cables that are exposed to high electromagnetic or radio
frequency noise.
Inputs/outputs with cable runs under 30 m (100 ft) typically do not require an offset in the software setup. Cable runs
over 30 m (100 ft) may require an offset in the input/output software setup.
Table 13 defines cable length guidelines for the various wire sizes that may be used for input and output wiring.
Maximum Cable Length versus Load Current
Use Figure 15 to estimate the maximum cable length relative to the wire size and the load current (in mA) when
wiring inputs and outputs.
FC and SA Bus and Supply Power Wiring Guidelines
Table 14 provides information about the functions, ratings, and requirements for the NIE communication bus and
supply power terminals, and guidelines for wire sizes, cable types, and cable lengths when wiring the NCE
communication buses and supply power.
In addition to the guidelines in Table 14, observe these guidelines when wiring the SA/FC Buses and supply power:
Run all low-voltage wiring and cables separate from high-voltage wiring.
All FC and SA Bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire.
Shielded cable is strongly recommended for all FC and SA Bus cables.
Refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034) for detailed information regarding
wire size and cable length requirements for the FC and SA buses.
13NIE29 Installation Instructions
Input Output Blocks Graphic
Figure 13: NIE29 Series Output Terminal Blocks, Binary Output Jumpers, and Supply Power Terminal Block
Figure 14: Universal Input and Binary Input Terminal Blocks
Wiring Rules and Guidelines for Network Integrations
Table 1: N2 Bus Network Rules
Rules/Maximums AllowedCategory
One N2 trunk network supported (on NIE291x models only).
Only daisy-chained devices (with maximum stub length of 3 m [10 ft] to any device)
General
Up to 32 N2 devices supported on the trunk.Number of Devices
Supported
1,500 m (4,921 ft) twisted pair cable
2,000 m (6,561 ft) between two fiber modems
Cable Length and Type
Solid or stranded 1.0 mm (18 AWG) 3-wire is recommended. Solid or stranded 0.5 mm (24 AWG)
larger 3-wire or 4-wire (two twisted-pairs) is acceptable.
Note: The + and - bus leads should be a twisted pair. On applications using 4-wire (two
twisted-pairs) cable, isolate and insulate unused conductor.
Cable
N2 devices are self terminating and have no end-of-line (EOL) setting.Bus Termination
14NIE29 Installation Instructions
Table 2: Modbus RTU Rules Table
Rules/Maximums AllowedCategory
One direct Modbus RTU (RS-232) connection to the RS232C port is supported.
Connection of an RS-232/RS-485 converter to the RS232C port supports up to 32 Modbus
(RS-485) devices.
FC port does not support Modbus integration.
General
RS232C port supports one Modbus RTU (RS-232) device.
RS232C port with RS-232/RS-485 converter supports up to 32 Modbus (RS-485) devices.
Number of Devices
RS-232 cable length can be up to 15 m (49.2 ft).
RS-485 cable length can be up to 1,520 m (4,987 ft).
Cable Length
RS-232 stranded cable, 3-9 conductors, serial data grade, 20–24 AWG
RS-485 stranded cable, 0.6 mm (22 AWG) 3-wire twisted, shielded cable is recommended.
Stranded 0.6 (22 AWG) 4-wire (two twisted pairs) shielded is acceptable.
Cable
RS-232: requires no termination.
RS-485: End-of-line (EOL) termination must be set to On (or an EOL terminator installed) on the
two devices located at either end of each bus segment on an RS-485 bus. The EOL switches
must be set to Off (or EOL termination disabled) for all other devices on the bus segment on an
RS-485 bus.
Termination
Table 3: MSTP FC Bus Rules Table
Rules/Maximums AllowedCategory
One FC Bus with up to 32 MS/TP devices (on NIE296x models only)
Note: An FC port on an NIE296x can connect to only one bus segment on an FC Bus.
Only a daisy-chain topology is allowed (no T or Star topology configurations).
General
Supports up to 32 MS/TP controllers on a single FC Bus segment.Number of Devices
FC Bus can be up to 1,520 m (4,987 ft) using 0.6 mm (22 AWG) 3-wire twisted, shielded cable
1
.
When using fiber-optic connections: 2,010 m (6,594 ft) between two fiber-optic modems
Cable Length for FC Bus
Stranded 0.6 mm (22 AWG) 3-wire twisted, shielded cable is recommended.
Stranded 0.6 mm (22 AWG) 4-wire (two twisted-pairs) shielded cable is acceptable.
Note: The + and - bus leads should be a twisted pair. On applications using 4-wire (two
twisted-pairs) cable, isolate and insulate unused conductor. Refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034) for more information.
Cable
The EOL switch must be set to On (or an EOL terminator installed) on the two devices located
at either end of each bus segment on an FC Bus. The EOL switches must be set to Off (or EOL
termination disabled) for all other devices on the bus segment on an FC Bus. See Setting the
End-of-Line Switch for information on setting the NIE EOL switch.
EOL Termination on the FC
Bus
1 If third-party devices are connected to the bus, the cable lengths should be reduced (if necessary) to match the third-party
vendor recommendations.
15NIE29 Installation Instructions
Table 4: SA Bus Rules
Rules/LimitsCategory
Each bus supervisor supports one SAB.General
An SAB supports up to 10 devices.
Note: The SAB supervisor provides power for the NS network sensors on the bus. Due to
power limitations, only 4 of the 10 devices on an SAB can be NS sensors.
Note: The SAB on NIE29 models that have an integral Local Controller Display do not support
an optional DIS1710 Local Controller Display.
SABs do not support repeaters.
Number of Devices
Supported on the Bus
365 m (1,198 ft) maximum bus length
152 m (500 ft) maximum between an NS network sensor and the bus supervisor FEC or VAV
Modular Assembly (VMA) supplying power to the sensor) using bus cable connected to the SAB
screw terminal blocks
30 m (98 ft) maximum length for network sensors using bus cables connected to the 6-pin
modular jack (6-Pin SAB port)
366 m (1,198 ft) maximum bus length
1.5 m (5 ft) maximum between NIE and DIS1710 Local Controller Display
SAB Cable Length
Screw Terminal Connections: 0.6 mm (22 AWG) Stranded 4-wire, 2-wire twisted pair, Shielded
Cable for screw terminals
Modular Jack Connections: 6-Pin Modular Connectors with 24 or 26 AWG 6-wire, 3-wire twisted
pair
Recommended Bus Cable
Type
1
Each SAB supervisor has integral (fixed ON) EOL termination, which typically provides sufficient
EOL termination on an SAB. Long SAB runs or persistent communication problems on an SAB
may require EOL termination at the last device on the SAB (in addition to the integral EOL
termination at the SAB supervisor). All NIE29 models are SAB supervisors.
EOL Termination on the SAB
1 If third-party devices are connected to the bus, the cable lengths should be reduced (if necessary) to match the third-party
vendor recommendations. Also, use only one type of connection, either Screw Terminal or Modular Jack, but not a combination
of both.
Table 5: Rules for M-Bus Protocol
Rules/Maximums AllowedCategory
One direct M-Bus serial (RS-232) connection to the RS232C port is supported.
Connection requires an RS232-to-M-Bus Level Converter on the RS232C port.
FC port does not support M-Bus integration.
No restrictions in topology, but bus topology is strongly recommended
General
Depends on level converter (logical maximum is 250 devices).Number of Devices
16NIE29 Installation Instructions
Table 5: Rules for M-Bus Protocol
Rules/Maximums AllowedCategory
Length depends on cable resistance, capacitance, number of devices, position of devices, and
configured communication speed. Example scenarios to help with calculation:
Line Length and Type
Maximum Distance for
Entire Bus
Maximum Distance
Between Converter and
Devices
Maximum Number of Unit
Loads
1, 2
Baud
Rate
5,000 m (16,404 ft)
(2 x 1.0 mm [18 AWG],
shield recommended,
resistance < 90 Ohms)
3,000 m (9,842 ft)642400
4,000 m (13,123 ft)
(2 x 1.0 mm [18 AWG],
shielded, resistance < 90
Ohms)
1,000 m (3,281 ft)64
4,000 m (13,123 ft)
(2 x 0.8 mm [20 AWG],
shielded, resistance < 30
Ohms)
350 m (1,148 ft)250
4,000 m (13,123 ft)
(2 x 0.8 mm [20 AWG],
shielded, resistance < 30
Ohms)
350 m (1,148 ft)649,600
1,000 m (3,281 ft)
(2 x 0.8 mm [20 AWG],
shielded, resistance < 30
Ohms)
350 m (1,148 ft)250
1,000 m (3,281 ft)
(2 x 0.8 mm [20 AWG],
shielded, resistance < 30
Ohms)
350 m (1,148 ft)6438,400
Twisted pair cable (shielding optional)Cable
No terminationTermination
1 Unit load is a defined standby current. A device is permitted a current drain of one unit load by default but may consume
more if it is shown at the device (by an integer) and in documentation.
2 Use M-Bus Repeaters to increase the length and the number of unit loads permissible.
Table 6: Rules for KNX Protocol
Rules/Maximums AllowedCategory
No restrictions in topologyGeneral
Depends on chosen topology and cable typeNumber of Devices
Twisted pair cable recommended; length depends on cable resistance, capacitance, number
devices, position of devices, and communication speed.
Line Length and Type
Copper, solid and stranded wires with outer sheath, one- or two-twisted pair; 0.8 to 1.0 mm (20
to 18 AWG)
Screen is required and must cover the entire diameter.
Drain wire: Diameter minimum 0.4 mm (26 AWG)
Cable
17NIE29 Installation Instructions
Table 6: Rules for KNX Protocol
Rules/Maximums AllowedCategory
No terminationTermination
At least ISO 9002Manufacturer's Quality
Management System
Table 7: Guidelines for LONWORKS Network Bus Topology
Maximum Segment Length with
FTT10 and/or LPT10 Devices
1
Maximum Segment Length with FTT10
Devices Only
1
Cable Type
2,200 m (7,218 ft)2,700 m (8,858 ft)Belden® 85102 Cable
2,200 m (7,218 ft)2,700 m (8,858 ft)Belden 8471 Cable
1,150 m (3,773 ft)1,400 m (4,593 ft)Level IV 0.6 mm (22 AWG)
750 m (2,460 ft)900 m (2,953 ft)JY (St.) Y 2 x 2 x 0.8
1 For the bus topology, the maximum length stub cable is 3 m (10 ft), and the stub lengths must be calculated into the overall
segment length.
Table 8: Guidelines for LONWORKS Network Free Topology
Maximum Segment Length with
FTT10 and/or LPT10 Devices
Maximum Node-to-Node DistanceCable Type
500 m (1,640 ft)500 m (1,640 ft)Belden 85102 Cable
500 m (1,640 ft)500 m (1,640 ft)Belden 8471 Cable
500 m (1,640 ft)400 m (1,312 ft)Level IV 0.6 mm (22 AWG)
500 m (1,640 ft)320 m (1,050 ft)JY (St.) Y 2 x 2 x 0.8
Table 9: Maximum Number of Devices per LONWORKS Network Segment
Maximum AllowedDevice Type
32 LONWORKS devices supported (on NIE292x Type models only).FTT-10 Nodes Only
([FTT10 x 2] + LPT10) < 32Mixed FTT-10 and LPT-10
Nodes
1
Terminators
2 bus type EOL terminators required (NU-EOL202-0)Bus Topology
1 free topology terminator required (NU-EOL203-0)Free Topology
Maximum of 1 per segmentPhysical Layer Repeaters
1 Each LPT10 channel segment (between repeaters) requires its own power supply. Other factors, such as power consumption
of individual LPT10 devices, may limit a segment to fewer devices. The NCE does not have an internal network terminator.
Table 10: NIE Ethernet Network Rules
Rules/Maximums Allowed
1
Category
Point-to-point star topology with network hubs and switchesGeneral
Maximum of 100 supervisory devices may be connected to one site in the Metasys system.
Number of Devices
2,000 m (6,600 ft) for plastic or glass fiber optic with external adapterLine Length and Type
100 m (330 ft) CAT5 cable
For 10/100 BaseT, no line terminators allowedTerminations
18NIE29 Installation Instructions
Table 11: NIE29 Dual Trunk Options
Supported Dual Trunk ApplicationTrunk Type
1 RS232
1 TCP
Modbus
2 TCP
1 RS232
1 TCP
M-Bus
2 TCP
1 RS232 Modbus
1 TCP M-Bus
Modbus and M-Bus
1 RS232 M-Bus
1 TCP ModBus
1 TCP Modbus
1 TCP M-Bus
1
Refer to the N1 Ethernet/IP Network Technical Bulletin (LIT-6360175) for recommended parts and part numbers.
19NIE29 Installation Instructions
Terminal Wiring and Cable Length Guidelines Tables
Table 12: Terminal Wiring
Determine Wire Size and
Maximum Cable Length
1
Function, Ratings, and
Requirements
Terminal LabelsTerminal Block
Label
Same as (Universal) INn.
Note: Use 3-wire cable for
devices that source
power from the +15 V
terminal.
15 VDC Power Source for active (3-wire)
input devices connected to the Universal
INn terminals.
Provides 100 mA total current.
+15 VUNIVERSAL
(Inputs)
See Guideline A in Table 13.
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage Internal
75k ohm Pulldown
INn
See Guideline B in Table 13.
Analog Input - Current Mode (4–20 mA)
Internal 100 ohm load Impedance
See Guideline A in Table 13.
Analog Input - Resistive Mode (0–600k
ohm)
Internal 12 V, 15k ohm pull up
Qualified Sensors: 0–2k potentiometer,
Resistence Temperature Detector (RTD),
1k Nickel sensor, 1k Platinum, and A99B
Silicon temperature sensor
Negative Temperature Coefficient (NTC)
Sensor (10k Type L, 10k JCI Type II,
2.252k Type II)
See Guideline A in Table 13.
Binary Input - Dry Contact Maintained
Mode1 second minimum pulse width
Internal 12 V, 15k ohm pull up
Same as (Universal) INn.Universal Input Common for all Universal
IN terminals
Note: All Universal ICOMn terminals
share a common, which is isolated
from all other commons.
ICOMn
See Guideline A in Table 13.
Binary Input - Dry Contact Maintained
Mode
0.01 second min. pulse width
Internal 18 V, 3k ohm pull up
INn
BINARY
(Inputs)
Binary Input - Pulse Counter Mode
0.01 second min. pulse width
(50 Hz at 50% duty cycle)
Internal 18 V, 3k ohm pull up
Binary Input Common for all Binary Input
(IN) terminals
Note: All Binary ICOMn terminals share
a common, which is isolated from
all other commons, except the CO
common (OCOMn) when the CO
is defined as an AO.
ICOMn
20NIE29 Installation Instructions
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Johnson Controls NIE29 Series Installation Instructions Manual

Type
Installation Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI