OUMAN EXP-800 Deployment Manual

Type
Deployment Manual

OUMAN EXP-800 is an external unit for the EH-800 series controllers that allows for parallel control of another source of heat, control of another heating circuit, or control of a solar collector's charging pump. The device has relay control and can be used with various measurement channels. With the EXP-800, you can connect the controller to multiple heat sources or heating circuits, allowing for more efficient and flexible heating control. The unit is easy to install and comes with detailed instructions.

OUMAN EXP-800 is an external unit for the EH-800 series controllers that allows for parallel control of another source of heat, control of another heating circuit, or control of a solar collector's charging pump. The device has relay control and can be used with various measurement channels. With the EXP-800, you can connect the controller to multiple heat sources or heating circuits, allowing for more efficient and flexible heating control. The unit is easy to install and comes with detailed instructions.

Installation guide
External unit for the EH-800 series controllers
www.ouman.
EXP-800






   

 
 
 
 















 






 
                                                                 





               

            
                                                                     

                                                                      
                                                                                    
                                                                           
                                                                           
                    
                                                                              
                                                                      
                           



















External unit for the EH-800 series controllers
2
NOTES
3
CONTENTS
EXP-800 for parallel control
of another source of heat page 4
EXP-800 for control
of another heating circuit page 5
Control of a solar collectors
charging pump with the
EH-800 controller page 6
Other connections for the
EXU-800 external unit pages 7–8
External unit for the EH-800 series controllers
4
This guide explains how to connect another heating circuit to the EH-800 series controller and
take it into use using the EXP-800 package. Make sure that power supply is not connected!
1. Attach the EXU-800 unit so that its valve actuator can be connected to the heating circuit’s
mixing valve, its surface sensor can be connected to the supply water pipe which is after
the mixing valve and the EXU-800’s RJ-45 cable can be connected to the EH-800 control-
ler.
2. Check the direction of the mixing valve and, if necessary, change the direction of the ac-
tuator to correspond to it. To change the direction of the actuator, look in the actuators
instructions. The factory set actuator opens clockwise and its range is 0…10V control.
3. Attach the actuator to the valve using the fitting piece.
- MS-NRE: Fitting pieces for Esbe and Termomix mixing valves,
black: Esbe, white: Termomix
- MS-NRE6; Fitting piece for Esbe VRG or VRB valves
4. Follow the instructions in the product package to attach the TMS-3m surface sensor to the
heating source’s supply water pipe after the mixing valve.
5. Connect the other end of the EXU-800’s RJ cable to the RJ-45-2 connection on the left side
of the EH-800 controller. Make sure that it “clicks” shut!
If a GSM modem is connected to the RJ-45-2 connection, it must be disconnected and
reconnected to the EXU-800 expansion unit as follows: Go to “Device settings” -> “text
message settings” in the controllers menu. Then go to “Text message settings” in the
controllers user manual, connect the GSM modem according to the instructions and
check the text message settings.
6. In the controllers menu go to “Device settings” -> “H2 Process settings”. Then go to “H2
Process Settings” in the controllers user manual. Follow the instructions. Installation and
initiation are completed when the functions have been tested and they function correctly.
EXP-800 for control of another heating circuit
Diagram 1.
A basic diagram for connecting two heating circuits. The controller controls both heating circuits on the basis of the
same outdoor temperature measurement but different supply water temperature measurements. Each heating
circuit has its own curve and other settings that effect control.
!
EXU-800
Outdoor sensor
H1 supply
water sensor
H2 supply
water sensor
H2 valve actuator
H2
heating
circuit
Electricity
supply
Room sensor
Electric
resistor
Boiler/
accumulator
H1 heating circuit
5
This guide explains how the EH-800 series heating controller can take parallel control of a
second heating source into use using the EXP-800 package. The surface temperature sensor
(TMS-3M) included in the product package is not needed, so you can install it wherever you
want to obtain an informative measurement. (number 4). Make sure that power supply is not
connected!
EXP-800 for parallel control of another source of heat
Diagram 2.
A basic diagram for hybrid heating, with the cascade control actuator getting its power from the first source of heat.
When the power is depleted from first source of heat, the controller begins taking additional power from the second
source of heat. The surface temperature sensor measures the temperature of the accumulator (1. heat source)
1. Attach the EXU-800 unit so that its valve actuator can be connected to the mixing valve
and the EXU-800’s RJ-45 cable can be connected to the EH-800 controller.
2. Check the direction of the mixing valve and, if necessary, change the direction of the actua-
tor to correspond to it. To change the direction of the actuator, see the actuators instruc-
tions. The factory set actuator opens clockwise and its range is 0…10V control.
3. Attach the actuator to the valve using the fitting piece.
- MS-NRE: Fitting pieces for Esbe and Termomix mixing valves,
black: Esbe, white: Termomix
- MS-NRE6; Fitting piece for Esbe VRG or VRB valves
4. Follow the instructions in the product package to attach the TMS-3m surface sensor to e.g.,
the water pipe coming from the accumulator. In the controllers menu go to “Device set-
tings” -> Measurement channel settings -> Measurement 5 . Select the correct label for the
measurement channel (in this case “accumulator temperature”) or label it yourself. Go to
Alarms” in the controllers menu and check the measurement channel’s alarm limits
5. Connect the other end of the EXU-800’s RJ cable to the RJ-45-2 connection on the left side
of the EH-800 controller. Make sure that it “clicks” shut!
If a GSM modem is connected to the RJ-45-2 connection, it must be disconnected and
reconnected to the EXU-800 external unit as follows: Go to “Device settings” -> “text
message settings” in the controllers menu. Then go to “Text message settings” in the
controllers user manual, connect the GSM modem according to the instructions and
check the text message settings.
6. In the controllers menu go to “Device settings” -> “Cascade control” and select “In use,
actuator control 0-10v. Process Settings” in the controller’s user manual. Installation and
initiation are completed when the functions have been tested and they function correctly.
EXU-800
Accumulator temperature
1.Source of heat
2.Source of heat
Cascade control motor
E.g., solar collector
or air-to-water heat
pump
Heating
circuit
Accumulator
E.g.,
Oil-fired boiler
Electricity
supply Outdoor sensor
Room sensor
Supply water sensor
Electric
resistor
!
External unit for the EH-800 series controllers
6
Diagram 4.
Basic diagram of hybrid heating, with the heating controller controlling the charging pump between the solar col-
lector and accumulator and controlling the heating system according to the outdoor temperature and supply water
temperature.
This guide explains how to connect the EH-800 series so it controls the charging pump be-
tween the solar collector and accumulator. The function can be taken into use when two
measurement channels (3/4/5) and relay control of the EXU-800 external unit are in use. Make
sure that power supply is not connected!
Solar collector’s charging pump control EH-800 + EXU-800
1. Attach the EXU-800 external unit in an accessible place so it is easy to connect things to it.
2. Connect the charging pump according to EXU-800 diagram 3.
3. Connect the temperature sensors: The sensor that measures the temperature of the solar
collector can be, e.g., the Ouman TME/NTC10, connected to measurement channel 3 or 4
(connecting cable). The sensor that measures the temperature of the lower part of the ac-
cumulator can be the Ouman TME/NTC10, connected to the EXU-800 measurement chan-
nel 5 or EH-800’s measurement channel 3 or 4.
4. Connect the other end of the EXU-800’s RJ cable to the RJ-45-2 connection on the left side
of the EH-800 controller. Make sure that it “clicks” shut!
If a GSM modem is connected to the RJ-45-2 connection, it must be disconnected and
reconnected to the EXU-800 expansion unit as follows: Go to “Device settings” -> “text
message settings” in the EH-800 heating controllers menu. Then go to “Text message
settings” in the controllers user manual, connect the GSM modem according to the
instructions and check the text message settings.
5. In the controllers menu go to “Device settings” ->
“Measurement channel settings”, select the correct la-
bels for the measurements you have connected. Go to
Alarms” in the controller’s menu and check the meas-
urement channel’s alarms.
6. Go to “Device settings” -> “Relay control” in the con-
trollers menu, select According to temperature dif-
ference”. Then go the corresponding place in the con-
trollers user manual and follow the instructions.
7. Installation and initiation are completed when the func-
tions have been tested and they function correctly. Diagram 3.
Relay control of the sun collector’s
charging pump.
Distributon
centre
EXU-800 Pump
C NO NC PE PE N L L
N L
N PE
PE
L
21 22 23 24 25 26 27 28
!
Accumulator temperature
measurement. E.g.,TME
Solar collector
temperature mesurement
Solar collector
TE
TE
EXU-800
Hybrid
accumulator
Electricity supply
Outdoor sensor
Room sensor
Supply water sensor
Heating
circuit
7
Other connections for the EXU-800 external unit
Make sure that power supply is not connected!
RJ45-2 contact
EH-800 controller’s measurement 6:
contact information
( alarm or home/away switch)
EH-800 controller’s
measurement 5:
H2 supply water, other temp.
measurement or contact information
Modem
current feed
red+
red-black
C NO NC PE PE N L L
21 22 23 24 25 26 27 28
24 Vdc
7 8 9 10 11
OUT Y DI UI
3 4
12-24V
DC IN
+
Separate additional power source
12 or 24 VDC
Actuator connection
(max 24VDC/3W actuator)
24 VDC 0-10 V (tape)
Belimo HTC24-SR
The instructions for chang-
ing the direction the actuator
runs in can be found in the
manufacturers instructions
(comes with the actuator).
re2
bk1
wh3
wh5
24 VDC 0-10 V
ESBE ARA 659
br
bl
bk
(Connect if a battery-backed additional power source is in use)
RJ45-1 connector
fuse
2,5A telecommunication
Modem RJ45-1
RJ45-2
External unit for the EH-800 series controllers
8
Other connections for the EXU-800 external unit
Make sure that power supply is not connected!
Relay control used for
giving alarms (general alarm)
Indicator
light or
siren
C NO NC PE PE N L L
N
N L
L
21 22 23 24 25 26 27 28
Distribution
center
PE
PE
Relay control is used for
pump summer stop
Distribution
center
Surface
thermostat
C01A Pump
C NO NC PE PE N L L
N L
N PE
PE 2 1
PE
L
21 22 23 24 25 26 27 28
Control of th 230 VAC contactor
e.g., control of the heating resistor
C NO NC
Distribution
center
230 VAC
contactor
230 VAC
control voltage
3 4
12-24V
DC IN
A separate 12 VDC or 24 VDC power source e.g., for
battery backup or additional power source
With 12 VDC’s the controller operates
and sends alarms
With 24 VDC’s the controller operates
normally
Connect the RJ45-1 using the battery
backup
OUMAN OY, Voimatie 6, FI-90440, Kempele, Finland
Telephone +358 424 8401, telefax +358 8 815 5060, www.ouman.
11/2 010
We reserve the right to make changes to our products without special notice.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

OUMAN EXP-800 Deployment Manual

Type
Deployment Manual

OUMAN EXP-800 is an external unit for the EH-800 series controllers that allows for parallel control of another source of heat, control of another heating circuit, or control of a solar collector's charging pump. The device has relay control and can be used with various measurement channels. With the EXP-800, you can connect the controller to multiple heat sources or heating circuits, allowing for more efficient and flexible heating control. The unit is easy to install and comes with detailed instructions.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI