H3C S7500-LSQM1SRPB0-SALIENCE VI FRU PRE REL Installation guide

Category
Network switches
Type
Installation guide
H3C S7500E Series Ethernet Switches
Installation Manual
Hangzhou H3C Technologies Co., Ltd.
http://www.h3c.com
Manual Version: T2-080406-20080725-C-1.04
Copyright © 2007-2008, Hangzhou H3C Technologies Co., Ltd.
All Rights Reserved
No part of this manual may be reproduced or transmitted in any form or by any means
without prior written consent of Hangzhou H3C Technologies Co., Ltd.
Trademarks
H3C, , Aolynk, , H
3
Care,
, TOP G, , IRF, NetPilot,
Neocean, NeoVTL, SecPro, SecPoint, SecEngine, SecPath, Comware, Secware,
Storware, NQA, VVG, V
2
G, V
n
G, PSPT, XGbus, N-Bus, TiGem, InnoVision and
HUASAN are trademarks of Hangzhou H3C Technologies Co., Ltd.
All other trademarks that may be mentioned in this manual are the property of their
respective owners.
Notice
The information in this document is subject to change without notice. Every effort has
been made in the preparation of this document to ensure accuracy of the contents, but
all statements, information, and recommendations in this document do not constitute
the warranty of any kind, express or implied.
Technical Support
customer_service@h3c.com
http://www.h3c.com
About This Manual
Organization
H3C S7500E Series Ethernet Switches Installation Manual is organized as follows:
Chapter Contents
1 Product Overview
Introduces the H3C S7500E Series Ethernet
Switches in terms of chassis, SRPUs, LPUs,
power supply, and fan tray.
2 Installation Preparations
Specifies the installation requirements of the H3C
S7500E Series Ethernet Switches and presents
installation precautions.
3 Hardware Installation
Introduces how to install the H3C S7500E Series
Ethernet Switches and how to connect the power
supply, ground cables, and the console cable.
4 System Commissioning
Introduces the startup process of the H3C S7500E
Series Ethernet Switches, including power-on and
system initialization.
5 Hardware Maintenance
Introduces how to install and remove power
modules, cards, fans, mounting ears, cable
management bracket, CF card, and air filters of the
H3C S7500E Series Ethernet Switches.
6 Software Maintenance
Introduces how to load and upgrade the software
of the H3C S7500E Series Ethernet Switches.
7 Troubleshooting
Introduces how to troubleshoot the configuration
system, power modules, fans, and LPUs of the
H3C S7500E Series Ethernet Switches.
Appendix A List of Pluggable
Modules
Introduces pluggable modules for different types of
ports and their related parameters.
Appendix B AC Power Cables
Used in Different Countries or
Regions
Introduces AC power cables used in different
countries or Regions, including 10A AC power
cables and 16A AC power cables.
Appendix C Compliance and
safety manual
Provides Compliance and safety manual
Conventions
The manual uses the following conventions:
I. Command conventions
Convention Description
Boldface
The keywords of a command line are in Boldface.
italic
Command arguments are in italic.
[ ]
Items (keywords or arguments) in square brackets [ ] are
optional.
{ x | y | ... }
Alternative items are grouped in braces and separated by
vertical bars. One is selected.
[ x | y | ... ]
Optional alternative items are grouped in square brackets
and separated by vertical bars. One or none is selected.
{ x | y | ... } *
Alternative items are grouped in braces and separated by
vertical bars. A minimum of one or a maximum of all can be
selected.
[ x | y | ... ] *
Optional alternative items are grouped in square brackets
and separated by vertical bars. Many or none can be
selected.
&<1-n>
The argument(s) before the ampersand (&) sign can be
entered 1 to n times.
# A line starting with the # sign is comments.
II. GUI conventions
Convention Description
< >
Button names are inside angle brackets. For example, click
<OK>.
[ ]
Window names, menu items, data table and field names
are inside square brackets. For example, pop up the [New
User] window.
/
Multi-level menus are separated by forward slashes. For
example, [File/Create/Folder].
III. Symbols
Convention Description
Warning
Means reader be extremely careful. Improper operation
may cause bodily injury.
Caution
Means reader be careful. Improper operation may cause
data loss or damage to equipment.
Note
Means a complementary description.
Related Documentation
In addition to this manual, each H3C S7500E Series Ethernet Switches documentation
set includes the following:
Manual Description
H3C S7500E Series Ethernet Switches
Operation Manual
It guides users how to use H3C S7500E
Series Ethernet Switches.
H3C S7500E Series Ethernet Switches
Command Manual
It provides detailed descriptions of the
commands available on H3C S7500E
Series Ethernet Switches.
Obtaining Documentation
You can access the most up-to-date H3C product documentation on the World Wide
Web at this URL: http://www.h3c.com.
The following are the columns from which you can obtain different categories of product
documentation:
[Products & Solutions]: Provides information about products and technologies, as well
as solutions.
[Technical Support & Document > Technical Documents]: Provides several categories
of product documentation, such as installation, operation, command, and typical
configuration example.
[Technical Support & Document > Product Support > Software]: Provides the
documentation released with the software version.
Documentation Feedback
You can e-mail your comments about product documentation to [email protected].
We appreciate your comments.
Environmental Protection
This product has been designed to comply with the requirements on environmental
protection. For the proper storage, use and disposal of this product, national laws and
regulations must be observed.
Installation Manual
H3C S7500E Series Ethernet Switches Table of Contents
i
Table of Contents
Chapter 1 Product Overview ........................................................................................................1-1
1.1 Introduction........................................................................................................................1-1
1.2 Physical Description of the S7500E Series.......................................................................1-1
1.2.1 Chassis and Slots ...................................................................................................1-1
1.2.2 Backplane................................................................................................................1-9
1.2.3 Power Supply System.............................................................................................1-9
1.2.4 Fan Tray................................................................................................................1-18
1.2.5 Air Filter.................................................................................................................1-19
1.3 SRPUs.............................................................................................................................1-19
1.3.1 SRPU Types..........................................................................................................1-19
1.3.2 LSQ1MPUA0 SRPU..............................................................................................1-20
1.3.3 Dedicated S7503E-S SRPU-LSQ1CGP24TSC0..................................................1-24
1.3.4 Salience VI-10GE SRPU-LSQ1SRP2XB0............................................................1-28
1.3.5 Salience VI SRPU-LSQ1SRPB0...........................................................................1-33
1.3.6 Salience VI-Turbo SRPU-LSQ1SRP1CB0 ...........................................................1-36
1.3.7 Salience VI-Lite SRPU-LSQ1MPUB0...................................................................1-40
1.3.8 Salience VI-Plus SRPU-LSQ1SRPD0 ..................................................................1-44
1.3.9 Salience VI-GE SRPU-LSQ1SRP12GB0 .............................................................1-47
1.4 LPUs................................................................................................................................1-52
1.4.1 LSQ1FP48SA0......................................................................................................1-52
1.4.2 LSQ1FV48SA0......................................................................................................1-53
1.4.3 LSQ1GP12EA0.....................................................................................................1-54
1.4.4 LSQ1GP12SC0.....................................................................................................1-55
1.4.5 LSQ1GP24SC0.....................................................................................................1-56
1.4.6 LSQ1GP48SC0.....................................................................................................1-57
1.4.7 LSQ1GT24SC0.....................................................................................................1-58
1.4.8 LSQ1GV48SA0.....................................................................................................1-59
1.4.9 LSQ1GV48SC0.....................................................................................................1-60
1.4.10 LSQ1P24XGSC0 ................................................................................................1-61
1.4.11 LSQ1T24XGSC0.................................................................................................1-63
1.4.12 LSQ1TGX1EA0...................................................................................................1-64
1.4.13 LSQ1TGX2SC0...................................................................................................1-65
1.4.14 LSQ1GP24TSC0.................................................................................................1-66
1.4.15 LSQ1GV40PSC0 ................................................................................................1-68
1.4.16 LSQ1PT4PSC0...................................................................................................1-69
1.4.17 LSQ1PT8PSC0...................................................................................................1-71
1.4.18 LSQ1PT16PSC0.................................................................................................1-73
1.5 Ordering Information for the S7500E Series ...................................................................1-74
Installation Manual
H3C S7500E Series Ethernet Switches Table of Contents
ii
1.5.1 Purchasing a Switch..............................................................................................1-74
1.5.2 Purchasing SRPUs ...............................................................................................1-76
1.5.3 Purchasing LPUs...................................................................................................1-76
1.5.4 Purchasing Optical Modules .................................................................................1-77
1.5.5 Purchasing Air Filters............................................................................................1-77
1.5.6 Purchasing Fan Trays...........................................................................................1-78
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-1
Chapter 1 Product Overview
1.1 Introduction
The S7500E Series Ethernet Switches (hereinafter referred to as the S7500E series)
are high performance, cost-effective Layer-3 switches with a large capacity. The
S7500E series are designed to operate at the core layer of small- and medium-sized
networks, the convergence layer of large enterprise networks, and the convergence
and access layers of metropolitan area networks (MANs). The S7500E series have
been optimized to meet users’ diversified demands for devices used on these
networks.
The S7500E series include six models, as described in
Table 1-1.
Table 1-1 Dimensions of the S7500E series
Model Slot direction Number of slots Number of SRPU slots
S7502E Horizontal 4 2 half-sized slots
S7503E-S Horizontal 3 1
S7503E Horizontal 5 2
S7506E Horizontal 8 2
S7510E Horizontal 12 2
S7506E-V Vertical 8 2
1.2 Physical Description of the S7500E Series
1.2.1 Chassis and Slots
The integrated chassis of the S7500E series consists of a card area, a fan area, and a
power supply area.
Table 1-2 Dimensions of the S7500E series
Model Dimensions (H × W × D)
S7502E 175 × 436 × 420 mm (6.89 × 17.17 × 16.54 in.)
S7503E-S 175 × 436 × 420 mm (6.89 × 17.17 × 16.54 in.)
S7503E 441 × 436 × 420 mm (17.36 × 17.17 × 16.54 in.)
S7506E 575 × 436 × 420 mm (22.64 × 17.17 × 16.54 in.)
S7510E 708 × 436 × 420 mm (27.87 × 17.17 × 16.54 in.)
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-2
Model Dimensions (H × W × D)
S7506E-V 930 × 436 × 420 mm (36.61 × 17.17 × 16.54 in.)
Note:
z The backplane, switching & routing processing unit (SRPU), power modules, and
fan tray are all required parts of the S7500E series.
z SRPUs and line processing units (LPUs) are distinguished by their edge colors.
SRPUs have pink edges while LPUs have purple edges. SRPUs must be inserted in
pink slots while LPUs must be inserted in purple slots.
z The power supply of the S7500E series can be AC or DC, depending on the actual
requirement. However, it is forbidden to insert different power modules into one
S7500E Ethernet switch.
I. S7502E
Figure 1-1 shows the front panel of the S7502E.
(1) Power modules (2) SRPUs (in slot 0 and slot 1)
(3) Fan tray (4) LPUs (in slot 2 and slot 3)
(5) Jack for ESD-preventive wrist strap
Figure 1-1 Front panel of the S7502E
All modules of the S7502E are hot swappable.
z The S7502E has four horizontal slots. SRPUs are inserted into the upper two slots.
See callout (2) in
Figure 1-1. SRPUs are required and support active-standby
switchover. Different LPUs are inserted into the other two slots. See callout (4) in
Figure 1-1.
z The fan tray is installed on the right side of the chassis. See callout (3) in Figure
1-1.
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-3
z The two power modules, which sit in the upper part of the chassis provide 1+1
redundancy backup. See callout (1) in
Figure 1-1. You can select either AC power
supply or DC power supply.
Figure 1-2 shows the rear panel of the S7502E.
(1) COM port for monitoring PoE (RS485) (2) COM port for monitoring PoE (RS232)
(3) Grounding screws
(4) RTN terminal (+) of external PoE power
supply
(5) Negative terminal (–) of external PoE
power supply (–46 V to –55 V)
Figure 1-2 Rear panel of the S7502E
There are two DC power input (PoE power supply input) terminals and two COM ports
(monitor ports) on the rear panel of the chassis.
Note:
z The S7500E series are Power over Ethernet (PoE) capable, that is, they can supply
power to devices such as IP phones, wireless access points, and network cameras
connected to their Ethernet ports through twisted pair cables.
z For the S7502E and S7503E-S, the external PoE power supply is connected to the
PoE power supply input terminals on the rear panel, while for the other models of
the S7500E series, the external PoE power supply is connected to a power module.
For details, refer to section
1.2.3 VI. “PSR1400-D” on page 1-15 and section 1.2.3
VII. “
PSR2800-ACV” on page 1-16.
II. S7503E-S
Figure 1-3 shows the front panel of the S7503E-S.
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-4
(1) Power modules (2) SRPUs (in slot 0)
(3) Fan tray (4) LPUs (in slot 1 and slot 2)
(5) Jack for ESD-preventive wrist strap
Figure 1-3 Front panel of the S7503E-S
All modules of the S7503E-S are hot swappable.
z The S7503E-S has three horizontal slots. SRPUs are inserted into the upper slot.
See callout (2) in
Figure 1-3. Dedicated S7503E-S SRPUs are required. Different
LPUs are inserted into the other two slots. See callout (4) in
Figure 1-3.
z The fan tray is installed on the right side of the chassis. See callout (3) in Figure
1-3.
z The two power modules, which sit in the upper part of the chassis provide 1+1
redundancy backup. See callout (1) in
Figure 1-3. You can select either AC power
supply or DC power supply.
Figure 1-4 shows the rear panel of the S7503E-S.
(1) COM port for monitoring PoE (RS485) (2) COM port for monitoring PoE (RS232)
(3) Grounding screws
(4) RTN terminal (+) of external PoE power
supply
(5) Negative terminal (–) of external PoE
power supply (–46 V to –55 V)
Figure 1-4 Rear panel of the S7503E-S
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-5
There are two DC power input (PoE power supply input) terminals and two COM ports
(monitor ports) on the rear panel of the chassis.
III. S7503E
Figure 1-5 shows the front panel of the S7503E.
(1)
(3)
(4)
(5)
(2)
(3)
(1) Fan tray (2) Jack for ESD-preventive wrist strap
(3) Power modules (4) LPUs (in slot 2 to slot 4)
(5) SRPUs (in slot 0 and slot 1)
Figure 1-5 Front panel of the S7503E
All the modules of the S7503E are hot swappable.
z The S7503E has five horizontal slots. SRPUs are inserted into the upper two slots
(see callout (5) in
Figure 1-5). SRPUs are required and support active-standby
switchover. Different LPUs are inserted into the other three slots (see callout (4) in
Figure 1-5).
z The fan tray is installed on the right side of the chassis (see callout (1) in Figure
1-5).
z The two power modules, which sit in the lower part of the chassis (see callout (3) in
Figure 1-5), provide 1+1 redundancy backup. You can select either AC power
supply or DC power supply.
IV. S7506E
Figure 1-6 shows the front panel of the S7506E.
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-6
(1)
(3)
(4)
(5)
(2)
(3)
(1) Fan tray (2) Jack for ESD-preventive wrist strap
(3) Power module (4) LPUs (in slot 2 to slot 7)
(5) SRPUs (in slot 0 and slot 1)
Figure 1-6 Front panel of the S7506E
All the modules of the S7506E are hot swappable.
z The S7506E has eight horizontal slots. SRPUs are inserted in the upper two slots
(see callout (5) in
Figure 1-6). SRPUs are required and support active-standby
switchover. Different LPUs are inserted into the other six slots (see callout (4) in
Figure 1-6).
z The fan tray is installed on the right side of the chassis (see callout (1) Figure 1-6).
z The two power modules, which sit in the lower part of the chassis (see callout (3) in
Figure 1-6), provide 1+1 redundancy backup. You can select either AC power
supply or DC power supply.
V. S7510E
Figure 1-7 shows the front panel of the S7510E.
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-7
(3)
(5)
(4)
(4)
(3)
(1)
(2)
(1) Fan tray (2) Jack for ESD-preventive wrist strap
(3) Power module (4) LPUs (in slot 0 to slot 4 and slot 7 to slot 11)
(5) SRPUs (in slot 5 and slot 6)
Figure 1-7 Front panel of the S7510E
All the modules of the S7510E are hot swappable.
z The S7510E has twelve horizontal slots. SRPUs are inserted in the middle two
slots (see callout (5) in
Figure 1-7). SRPUs are required and support
active-standby switchover. Different LPUs are inserted in the other ten slots (see
callout (4) in
Figure 1-7).
z The fan tray is installed on the right side of the chassis (see callout (1) in Figure
1-7).
z The two power modules, which sit in the lower part of the chassis (see callout (3) in
Figure 1-7), provide 1+1 redundancy backup. You can select either AC power
supply or DC power supply.
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-8
VI. S7506E-V
Figure 1-8 shows the front panel of the S7506E-V.
(1)
(4)
(2)
(6)
(3)
(4)
(5)
(1) Fan tray (2) LPUs (in slot 2 to slot 7)
(3) Jack for ESD-preventive wrist strap (4) Power module
(5) Air filter (6) SRPUs (in slot 0 and slot 1)
Figure 1-8 Front panel of the S7506E-V
All the modules of the switch are hot swappable.
z The S7506E-V switch has eight vertical slots. SRPUs are inserted in the left two
slots (see callout (5) in
Figure 1-8). SRPUs are required and support
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-9
active-standby switchover. Different LPUs are inserted in the other six slots (see
callout (2) in
Figure 1-8).
z The fan tray is installed above the SRPUs and LPUs (see callout (1) in Figure 1-8)
and the air flows up from the bottom.
z The two power modules, which sit in the lower part of the chassis (see callout (3) in
Figure 1-8), provide 1+1 redundancy backup. You can select either AC power
supply or DC power supply.
1.2.2 Backplane
The backplane in the integrated chassis of the S7500E series implements high-speed
data exchange as well as management & control signal exchange between SRPUs and
LPUs.
The backplane mainly provides the following functions:
z Interconnection between cards
z Card hot-swapping
z Automatic slot recognition
z Automatic chassis type recognition
z Distributed power supply to the system. The S7506E-V has two backplanes:
signal backplane and power supply backplane. The power supply backplane is
connected to the power modules and is also connected to the signal backplane
with an internal cable.
z Connection of the signal cable that monitors the fan tray and power supply
1.2.3 Power Supply System
The S7500E series support a variety of power modules, as listed in Table 1-3.
Table 1-3 Power module models of the S7500E series
Model Height
Power input
mode (AC/DC)
Support PoE
power (Yes/No)
PSR320-A 1 U AC No
PSR320-D 1 U DC No
PSR650-A 1 U AC No
PSR650-D 1 U DC No
PSR1400-A 3 U AC No
PSR1400-D 3 U DC No
PSR2800-ACV 3 U AC No
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-10
Table 1-4 Features of power modules
Feature Description
Protection functions
Support input under-voltage protection, output
over-voltage protection, short-circuit protection,
over-current protection, and overheat protection
1+1 hot backup support Support 1 + 1 hot backup and current sharing
Hot swap support
Support hot swap with the power switch turned off
while the device is in operation
Typically, the S7502E and the S7503E-S use 1U power modules, while the other
models of the S7500E series use 3U power modules.
The S7500E series support a large variety of card types, and system power
consumption of a switch varies with different types of cards in use. You can choose an
appropriate power module model for your switch based on its system power
consumption.
H3C has designed a power module adapter, PWR-SPA, to allow flexible power module
options to suit different system power consumption characteristics.
You can use PSR650 power modules in combination with PWR-SPA power module
adapters to power a switch with system power consumption lower than 650 W, instead
of using heavy-duty power modules like the PSR1400 or PSR2800.
The system power consumption of a switch is determined by its SRPUs, LPUs, and fan
tray. Specifically, the system power consumption of a switch is equal to the power
consumption of its SRPUs, LPUs, and fan tray put together.
For how to install power modules and power module adapters, refer to section 5.2
"Removing and Installing a Power Module."
Table 1-5 Compatibility matrix between power modules and switch chasses
Chassis
(right)
Power
module
(below)
S7502E
S7503E-
S
S7503E S7506E
S7506E-
V
S7510
E
PSR320-A Y1 Y1 N N N N
PSR320-D Y1 Y1 N N N N
PSR650-A Y1 Y1 Y2 Y2 Y2 N
PSR650-D Y1 Y1 Y2 Y2 Y2 N
PSR1400-A N N Y1 Y1 Y1 Y1
PSR1400-D N N Y1 Y1 Y1 Y1
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-11
Chassis
(right)
Power
module
(below)
S7502E
S7503E-
S
S7503E S7506E
S7506E-
V
S7510
E
PSR2800-AC
V
N N Y1 Y1 Y1 Y1
Note:
z Y1 means that the power module directly fits the chassis.
z Y2 means that you need to insert a power module adapter into the chassis and then
inserting the power module into the power module adapter.
z N means that the power module cannot be used in the chassis.
z Do not use different types of power modules in the same device.
I. PSR320-A
(1) Power cable retainer (2) AC power socket
(3) Power switch (4) Power LED
(5) Power module handle (6) Captive screws
Figure 1-9 PSR320-A power module
As shown in the figure, above the power switch is the power LED. If the power LED is
green, the power supply operates normally. If the LED is red, the power supply is
abnormal.
Table 1-6 Technical specifications of the PSR320-A power module
Item Specifications
Rated voltage range 100 VAC to 240 VAC; 50 Hz or 60 Hz
Maximum output power 300 W
Dimensions (H × W × D) 40 × 140 × 350 mm (1.57 × 5.51 × 13.78 in.)
Installation Manual
H3C S7500E Series Ethernet Switches Chapter 1 Product Overview
1-12
Note:
The PSR320-A uses a 10-A AC power cable.
II. PSR320-D
(1) Grounding screws (2) RTN terminal (+) of DC input
(3) Negative terminal (–) of DC input (–48 V to –60 V) (4) Power switch
(5) Power LED (6) Power module handle
(7) Captive screws
Figure 1-10 PSR320-D power module
As shown in the figure, above the power switch is the power LED. If the power LED is
green, the power supply operates normally. If the power LED is red, the power supply is
abnormal.
Table 1-7 Technical specifications of the PSR320-D power module
Item Specifications
Rated voltage range –48 VDC to –60 VDC
Maximum output power 300 W
Dimensions (H × W × D) 40 × 140 × 350 mm (1.57 × 5.51 × 13.78 in.)
III. PSR650-A
(1) Power cable retainer (2) AC power socket
(3) Power switch (4) Power LED
(5) Power module handle (6) Captive screws
Figure 1-11 PSR650-A power module
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198