Allen-Bradley 160-NX3 User manual

Type
User manual

This manual is also suitable for

160-NX3
Chassis Mount
(Series C)
User Manual Supplement
Important User Information
Solid-State equipment has operational characteristics differing from those of
electromechanical equipment.
“Safety Guidelines for the Application, Installation
and Maintenance of Solid-State Controls”
(Publication SGI-1.1) describes some
important differences between solid-state equipment and hard-wired
electromechanical devices. Because of this difference, and also because of the wide
variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment
is acceptable.
In no event will Rockwell Automation be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
Important:
Identifies information that is especially important for successful
application and understanding of the product.
SSC is a trademark of Rockwell Automation, Inc.
!
ATTENTION:
Identifies information about practices or
circumstances that can lead to personal injury or death, property
damage or economic loss.
Shock Hazard
labels located on or inside the drive indicate that
dangerous voltage may be present.
Contents
Exceptions to Drive User Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Drive Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Input/Output Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Control Inputs (Analog Signal Follower Model Only) . . . . . . . . . . . . . . . . . . 2
Control Inputs (Preset Speed Model Only) . . . . . . . . . . . . . . . . . . . . . . . . . 2
Control Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Protective Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ii
160-NX3 Series C Drive
These instructions are intended to be used as a supplement to the drive user manual.
For information regarding drive programming and operation, refer to the 160
SSC™ Variable Speed Drive (Series C)
User Manual
, Publication 0160-5.17ML.
Exceptions to Drive User Manual
Important:
Set
P42 - [Motor Overload Current]
to motor nameplate full load
amps (FLA). Settings that are not within Min / Max levels will
cause premature failure of the product.
Specifications
Drive Rating
Input/Output Ratings
Environmental Specifications
Parameter Min / Max Range Units Factory Default
P42 - [Motor Overload Current] 2.0 / 4.5 Amps 9.2 Amps
P43 - [Current Limit] 1.6 / 8.0 Amps 12 Amps
IP20 Catalog
Number Output Ratings Input Ratings Dynamic Braking Torque
Power
Dissipation
Three-Phase
Input, 50/60 Hz kW HP
Output
Current
Operating
Voltage
Range kVA
Without
External
Resistor
With 160-BMA1
External Resistor
With 160-BMA2
External Resistor
IP20 (Chassis
Mount)
160-NX3 0.55 0.75 3.0A 180-265V 1.8 100% 233% 366% 11W
Output Voltage
0V to Input Voltage (Adjustable)
Output Frequency
0 to 240 Hz (Programmable)
Efficiency
97.5% (Typical)
Transient Protection
Standard 6kV(Series C drives)
Enclosure
Heatsink meets NEMA Type 4/4X/12 (IP66) requirements.
The drive is an open style (IP20) device.
Ambient Temperature
Internal Enclosure Ambient: 0 to 50 degrees C (32 to 122 degrees F)
External Heatsink Ambient: 0 to 40 degrees C (32 to 104 degrees F)
Maximum Heatsink Temperature: 90 degrees C (194 degrees F)
Storage Temperature
–40 to 85 degrees C (–40 to 185 degrees F)
Relative Humidity
0 to 95% (non condensing)
Vibration
1.0 G Operational - 2.5 G Non-operational
Shock
15 G Operational - 30 G Non-operational
Altitude
1,000 meters (3,300 feet) without derating
2
160-NX3 Series C Drive
Control Inputs
Control Inputs (Analog Signal Follower Model Only)
Control Inputs (Preset Speed Model Only)
Control Output
Control Features
Control Input Type
For dry contact closure input - drive has an internal 12V power supply that provides 10mA (typical)
current. Also accepts open collector/solid-state input with maximum leakage current of 50µA.
Optional 24V DC interface allows use of 24V DC “sink logic” inputs.
Start, Stop, Forward/Reverse
Configurable inputs for 2 or 3 wire control
Analog Input (4 to 20mA)
Input impedance 250 ohms
Analog Input (-10 to +10V DC)
Input impedance 100k ohms
External Speed Potentiometer
1k to 10k ohms, 2 Watt minimum
PI Control
Users of Firmware Version FRN 7.05 and earlier use Parameter 46 setting 9 to activate the PI
Control function.
Users of Firmware Version FRN 7.06 can use Parameter 46 settings 0 through 7 and 9 to activate
the PI Control function.
SW1, SW2
Parameter 46, setting 8 provides 4 preset speeds and 2 accel/decel times
SW1, SW2, SW3
Configurable inputs for control of 8 preset speeds and 2 accel/decel times
Programmable Output
(from C relay contact)
Resistive Rating: 0.4A at 125V AC, 0.2A at 230V AC, 2A at 30V DC
Inductive Rating: 0.2A at 125V AC, 0.1A at 230V AC, 1A at 30V DC
Programmable for eleven different functions
PWM Algorithm
Sine weighted PWM with harmonic compensation
Switching Device
(3-Phase Output) IGBT (Insulated Gate Bipolar Transistor)
V/Hz Ratio
Programmable
Carrier Frequency
Adjustable from 2 kHz to 8 kHz in 100 Hz increments (factory default is 4 kHz)
DC Boost
Adjustable - Select from a family of boost curves
Current Limiting
Trip free operation, coordinated for drive and motor protection. Programmable from 1% to 180%
of drive Output Current.
Motor Protection
I
2
t overload protection - 150% for 60 seconds, 200% for 30 seconds (Provides Class 10 overload
protection). Percentage refers to Parameter 42 setting.
Overload Pattern #0
Flat response over speed range (no speed compensation)
Overload Pattern #1
Speed compensation below 25% of base speed
Overload Pattern #2
Speed compensation below 100% of base speed
Acceleration/Deceleration Time(s)
0.1 to 600 seconds
S-Curve Accel/Decel Time(s)
0 to 100% of accel/decel time - not to exceed 60 seconds
Stopping Models
4 modes (programmable)
Ramp to Stop
0.1 to 600 seconds
Coast
Stops all PWM output
DC Injection Brake
Applies DC voltage to the motor for 0 to 25 seconds
DC Injection Braking w/ Auto Stop
Applies DC voltage to the motor for 0 to 25 seconds with Auto Shutoff
160-NX3 Series C Drive
3
Protective Features
Programming
Overcurrent
200% hardware limit (16 amps), 300% instantaneous fault (24 amps)
Excessive Temperature
Embedded temperature sensor trips if heatsink temperature exceeds 95 degrees C
(203 degrees F)
Over Voltage
Drive Rated Input = 200-240V AC
Drive Rated Input = 380-460V AC
DC Bus voltage is monitored for safe operation
Overvoltage trip occurs at 400V DC bus voltage (equivalent to 290V AC incoming line voltage).
Overvoltage trip occurs at 800V DC bus voltage (equivalent to 575V AC incoming line voltage).
Under Voltage
Drive Rated Input = 200-240V AC
Drive Rated Input = 380-460V AC
DC Bus voltage is monitored for safe operation
Undervoltage trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line voltage).
Undervoltage trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line voltage).
Control Ride Through
Minimum ride through is 0.5 seconds - typical value 2 seconds
Ground Fault
Protection in both Start and Run Mode
Faultless Ride Through
100 milliseconds
Output Short Circuit
Any output phase to phase short
Programmer / Display Type
Program Keypad Module - 6 character LED display
Remote Keypad Module - 4 character LED display
CopyCat Keypad Module - 2 line, 16 character LCD display
Local Controls
SPEED, RUN, STOP, and DIRECTION controls
4
160-NX3 Series C Drive
Installation
!
ATTENTION:
To guard against electrical shock, disconnect from
power source before installing or servicing.
!
ATTENTION:
Do not touch drive surfaces. Temperatures are hot
enough to cause severe burns.
!
ATTENTION:
After system installation, remove the debris label
from the unit. Failure to remove this label may result in overheating
or nuisance tripping.
Cut-out and Mounting Detail For Customer Panel
114
(4.49)
8
(0.31)
195
(7.68)
97.5
(3.84)
16
(0.63)
49
(1.93)
98
(3.86)
130
(5.12)
8
(0.31)
mm
(in)
179
(7.05)
5.5
(0.22)
6 Holes
1
(Heatsink)
(Heatsink)
160-NX3 Series C Drive
5
Item Qty. Description Required to Install
A
8 3.2 mm (0.125 in.) Spacer 6
B
8 #10-32 Sealing Screw 6
2
A
To p
Outside
Inside
Customer
Panel
Mounting holes intended to support weight
of Allen-Bradley enclosed drives only.
B
Torque to 1.35 N-m
(12 lb-in)
#10-32 × .63 in
Sealing Screw
Customer
Panel
Max.
4.1 mm (0.16 in)
Min.
1.5 mm (0.06 in)
Heatsink
Gasket
Spacer
Thickness: 3.2 mm
(0.125 in)
3
6
160-NX3 Series C Drive
Dimensions
Important:
Bulletin 160 drives installed in user supplied enclosures are
mounted to allow the heatsink to extend outside the enclosure. Use
the information below in combination with the enclosure
manufacturers guidelines for sizing.
Clearances: There must be a minimum of 12.5 mm (0.5 in.) around
all sides of the drive module, 100 mm (4 in.) on the top and bottom
of the heatsink, and 50 mm (2 in.) on the sides of the heatsink.
120 mm (4.72 in.) with DeviceNet accessory.
175
(6.89)
98
(3.86)
114
(4.49)
130
(5.12)
145
(5.71)
Customer
Panel
210
(8.27)
92
(3.63)
55
(2.16)
97.5
(3.84)
195
(7.68)
179
(7.05)
Publication 0160-5.33 — February 2001 P/N 194406 (02)
Copyright 2001 Rockwell International Corporation. All rights reserved. Printed in USA.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Allen-Bradley 160-NX3 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI