  • Hello! I am an AI chatbot trained to assist you with the Alpha AlphaNet EDH-A2 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
1745-838-C5-001 Rev. A
Power
Alpha XP-EDH-A2 Transponder Field Installation Instructions
A grounded Surge Protector (Alpha P/N 162-028-10) or equivalent) is required for all installations.
Do not place the transponder on top of the power supply or the batteries.
Make all battery harness connections to the batteries and connect the interface cables to the power supply before connecting the cables to the
transponder.
First, verify the transponder bears the warning label as shown at right. This indicates the unit is an XP-EDH-A2,
and the jump and switch settings described in this instruction will work properly.
Verify the transponder's MAC address is loaded into the CMTS, and DOCSIS conguration le options should be
set. Detailed instructions for eld installation procedures are available in the XP-EDH-A2 Technical Manual
(Alpha P/N 745-838-B2) available at www.alpha.com.
Alpha XM Series 2 Power Supply
1. Switch the battery breaker OFF.
2. Remove the Inverter Module from the power supply. See the power supply's technical manual for instructions.
3. Position jumpers and switches as shown below.
ON
USM2.5
48V and ≥ 20A
ON
48V and <20A
ON
<48V and ≥ 20A
ON
ON
<48V and <20A
ON
JUMPED
ON
ON
1
2
3
ON
USM2
ON
48V and ≥ 20A
ON
48V and <20A
<48V and ≥ 20A
ON
<48V and <20A
ON
JP2: 2-3 Jumped
JP1 (5V Position)
SW1
SW1 Settings:
SW1 Settings:
SW2 Setting:
SW1
SW2
UNLATCH RIBBON CABLE RETAINER
BEFORE FULLY REMOVING MODULE.
OUTPUT 1
OUTPUT 2
N + 1
SSR
OUTPUT
N
L
LRI
WHT
RED
BLACK
BATTERY
BLK
INPUT
BREAKER
BATTERY
transformer
m o d u l e
module
inverter
ALARM
OUTPUT
ESC
M
TEMP
PROBE
BLACK
RED
TEST
S
S
C
O
Y
TMPR
Power Supply
PWR
Power
14 PIN
US
DS
Battery
18 PIN
16 PIN
ONLINE
DOCSIS Transponder
AlphaNet
0A C4 36
System RF Cable in
To Battery Harness
Black
wire
Yellow
wire
To Batteries
Important!
Plug in the 13 pin
connector so that the
black wire is in pin 1 (the
bottommost pin) and two
open pins are left at the
top for tamper switch
connector.
AC voltage input (USM2 cards only)*
Power Supply Interface Cable
cbl-ps-intfc-01-003, Alpha p/n: 875-565-10
* CBL-PS-PWR-01-001 120V p/n: 875-563-10
CBL-PS-PWR-03-002 220V p/n: 875-562-10 (3' cord with IEC C13 connector and 220V US NEMA 6-15 plug)
CAUTION!
(AC Scaling of
Output Voltage)
2745-838-C5-001 Rev. A
Power Supply
PWR
Power
14 PIN
US
DS
Battery
18 PIN
16 PIN
Fuse
WARNING:
3
INDICATOR
LAMP
REMOTE
STATUS
RELAY
STANDBY
1 2
OUTPUT
4 65
AC
BLACK
RED
BATTERY
CONNECTOR
+
CIRCUIT
BREAKER
-
BATTERY
OFF
BLACK
RED
DOCSIS Transponder
AlphaNet
0A C4 36
ONLINE
System RF Cable in
AC Voltage Input
120V p/n 875-563-10
220V p/n 875-562-10
To Battery Harness
Power Supply Interface Cable
p/n 875-565-10
Black
wire
Yellow
wire
To Batteries
Jumper Position
P1 2-3
P2 open
P3 open
P4 closed
P5 closed
P6 closed
P7 5V
P8 1-2
P9 1-2
P13 1-2
P14 1-2
SW4 0
SW1
DC
1
2
3
18 PIN
Battery
Black
wire
Red/Green
wire
View
Side
Cut
Here
CUT AND REMOVE A PIECE OF
RED/GREEN WIRE IF PRESENT
FOR XM SERIES ONLY
!
CUT THE WIRE
IN UPPER LEFT POSITION
AS SHOWN. ANY WIRE COLOR.
Remove the USM and
set the jumpers as shown
below:
120VAC
TO
9VAC
CBL-PS-PWR-01-001
Alpha P/N 875-563-10
3 FT CORD
NEMA 6-15P
220V US
220VAC
IEC C13
9VAC
TO
CBL-PS-PWR-03-002
Alpha P/N 875-562-10
CBL-PS-INTFC-01-003
CBL-PS-INTFC-01-003
Alpha P/N 875-565-10
Or
Necessary Cables
Alpha XM Series Power Supply
Set to 0
(SWs 1,2,3 may not
be present on some
boards)
Potentiometer
Adjuster
RJ Connector
Power Supply
Interface
= Jumped
SW2 SW3 SW4
R8
12
12
12
1
1
1
P1
P2
P3
P4
P5
P6
P7
5V
24V 15V
P8
P9
P13 P14
AC
CUR
AC Volts
1
2
3
1
2
3
1
2
3
USM
3
PIN 1
A
A
B
B
Important!
Plug in the 13 pin
connector so the black
wire is in pin one (the top
pin) and two open pins
are left at the bottom for
tamper switch connection.
NOTE:
A chipset upgrade to the XM Inverter Module and/or USM Card may be required; contact Alpha for
more information.
Set the jumpers and calibrate the USM card before making cable connections and applying load.
1. Switch the battery breaker OFF.
2. Remove the Inverter Module from the power supply. See the power supply's technical manual for instructions.
3. Position jumpers and switches as shown below.
First, verify the transponder bears the warning label as shown at right. This indicates the unit is an XP-EDH-A2, and the
jump and switch settings described in this instruction will work properly.
NOTE:
The EDH-A2 calculates Output Voltage using AC Scaling as opposed
to the EDH-A which uses DC Scaling. This requires changes to the
USM card jumper settings and eliminates the need to calibrate the USM
potentiometer.
3745-838-C5-001 Rev. A
Alpha AM/AP Series Power Supply
Switch the battery breaker OFF.
The power supply must be disconnected from line voltage during installation.
If not already installed, install an RPM card. Refer to RPM instructions for details.
120VAC
TO
9VAC
CBL-PS-PWR-01-001
Alpha P/N 875-563-10
3 FT CORD
NEMA 6-15P
220V US
220VAC
IEC C13
9VAC
TO
CBL-PS-PWR-03-002
Alpha P/N 875-562-10
Or
CBL-PS-INTFC-01-002
Alpha P/N 875-564--10
Note:Rev. B of this cable does
not have a Violet wire
Necessary Cables
NOTE:
Outer band on
DIN connector
is black on older
ZTT+ models and
silver on newer
models.
Switch to ZTT Only for ZTT power
supplies. Switch to +Silver or +Black
for ZTT+ power supplies, depending
on whether the outer band on the
DIN connector is silver or black.
Lectro ZTT and ZTT+ Power Supplies
Switch the battery breaker OFF.
ZTT
ZTT
+
ZT
T+
SILVER
GROUND
TA
M
P
E
R
B
L
ACK
CBL-PS-INTFC-02-005
9VAC
120VAC
TO
CBL-PS-INTFC-02-005
Alpha P/N 875-566-10
CBLPS-PWR-02-002
Alpha P/N 875-718-10
CBLPS-PWR-04-001
Alpha P/N 875-717-10
Necessary Cables
or
NOTE:
Maintain correct polarity when making this connection. If
reversed, the transponder will be damaged and V
out
will
not be readable.
Power Supply
PWR
Power
110V AC Line Input
14 PIN
ONLINE
US
DS
16 PIN
CBL-PS-INTRFC-01-001
Battery
CBL-PS-BAT-04-004
18 PIN
DOCSIS Transponder
AlphaNet
R
0A C4 36
BLACK
RED
C
BL-PS-
I
N
T
R
FC-
01-002
Alpha
S
E
R
I
E
S
T
e
chno
l
ig
i
es
AM/AP
1
2
3
4
5
6
7
8
9
10
NO
COM
NC
LAMP
OUTPUT
BATT
+
-
RED
BLACK
0A C4 36
DOCSIS Transponder
AlphaNet
To Battery Harness
Power Supply Interface Cable
p/n 875-566-10
To Batteries
System RF
Cable in
Ground
Tamper
Power Output Cable with transformer
120V p/n 875-718-10, 220V p/n 875-717-10
To Load
The power supply must be disconnected from line
voltage during installation.
Important!
Plug in the 13 pin connector so the black wire is in pin
one (the right-hand pin) and two open pins are on the
left for tamper switch connection. If present, cut the
Violet wire (pin 9).
CBL-PS-INTRFC-01-002
HOT
N
EUT
CBL-PS-INTFC-01-002
Alpha P/N 875-564-10
Alpha Technologies reserves the right to make changes to the products and information contained in this document without notice.
Copyright © 2009 Alpha Technologies. All Rights Reserved. Alpha
®
is a registered trademark of Alpha Technologies. member of The Alpha Group™ is a trademark of Alpha Technologies.
745-838-C5-001, Rev. A (07/2009)
For more information visit www.alpha.com
United States Bellingham, Washington Tel: 360 647 2360 Fax: 360 671 4936
Canada Burnaby, British Columbia Tel: 604 430 1476 Fax: 604 430 8908
To report errors in this document send email to: T[email protected]
member of The Group
TM
4
Total Power Solutions
RF Drop
The downstream level (DS) into the transponder should be ± 15dBmV. However, for optimal performance, set the level as
close to 0 dBmV as possible
Verifying Installation and Network Connectivity
Once the rmware initializes, the LED sequence is as follows:
1. POWER LED on; all other LEDs off
2. DS, US ashing intermittently
3. ONLINE LED ashing fast and slow until registration is complete
4. ONLINE LED on solid indicating IP address has been assigned
5. DS ickering as data are sent from transponder to Network Management System
Once the AM MIBs have been set through the network using SNMP, the network connection can be remotely veried
by entering the IP address into a web browser and conrming the display of correct power supply measurements.
For additional product information, refer to the XP-EDH-A2 technical manual (P/N 745-838-B2).
Generic Power Supplies
Switch the battery breaker OFF.
9VAC
120VAC
TO
220VAC
NEMA 6-15P
220V US
9VAC
3 FT CORD
IEC C13
TO
CBLPS-PWR-02-002
Alpha P/N 875-718-10
CBLPS-PWR-04-001
Alpha P/N 875-717-10
or
Necessary Cables
NOTE:
0A C4 36
DOCSIS Transponder
AlphaNet
To Load
To Batteries
For any power supply that has a compatible
output power connector, the XP-EDH-A2 can
monitor the following parameters:
• Input V
• Output V
• Battery string V
• Individual battery V
• Temperature
System RF
Cable In
To Battery Harness
Provides Input Voltage Monitoring
Power Output Cable
with Transformer
120Vac P/N 875-718-10
220Vac P/N 875-717-10
A
A
The power supply must be disconnected from line
voltage during installation.
2013
10/2013
604 436 5900 604 436 1233
/