When the 24 VDC is provided by either the
MMB-2/-3 or SMB-2, use TB6 on the MOM-4 to
connect the power. The wire for this connection is
not supplied (See the MMB-2 Installation Instruc-
tions, P/N 315-095097, the MMB-3 Installation
Instructions, P/N 315-048860 or the SMB-2
Installation Instructions, P/N 315-095931).
When the system includes an MMB-2/-3 or
SMB-2, the maximum load current for the MOM-4
is 6A when using an MPS-6 and 12 amps when
using an MPS-12. However, the 6A must be
reduced by the amount of current being used by
the CZM-1, PS-5A/-5N7, and NAC outputs. Thus,
if the full 1A available to the CZM-1 and
PS-5A/-5N7, and the 3A available to the NAC
outputs are used, derate the MOM-4 current to 2
amps (or, if an MPS-12 is used, derate the MOM-4
current to 8A).
When the 24 VDC is provided by PSR-1, use
TB6 on the MOM-4 to connect the power. The
wire for this connection is not supplied (See the
PSR-1 Installation Instructions, P/N 315-090911,
for terminal connections).
When the system includes a PSR-1, the maximum
load current for the MOM-4 is 6A when using an
MPS-6 and 12 amps when using an MPS-12.
However, the 6A must be reduced by the amount of
current being used by the CZM-1 and PS-5A/-5N7
output. Thus, if the full 2A available to the CZM-1
and PS-5A/-5N7 are used, derate the MOM-4
current to 4A (or, if an MPS-12 is used, derate the
MOM-4 current to 10A).
Depending on the optional modules installed,
additional power may be available at TB5 and for
notification appliances. See Table 1 for the
maximum current required by each module under
full load conditions.
Determine which optional plug-in modules are used
in your CSG-M configuration. Depending on the
optional modules used, determine the outstanding
power by using Table 1 (See the EXAMPLE). This
power can be used for notification appliances or
for the optional power connector on TB5.
P/N 315-090852-13
1ELBAT
STNERRUCDAOLELUDOMMUMIXAM
I2-DLA ecivedrepAm1.1+Am501
003-IMC Am69
4-MRC )dezigrenesyaler4(Am57
4-MSC secnailppanoitacifitonon(Am43
)detcennoc
4-MZC nisenoz4htiw(xamAm027
)mrala
W1/R1-MIN Am0
1-PER Am051
1-DLX )mralanisecived021(Am593
NOTE: When a CSM-4 is used, you may add
notification appliances to it if the maxi-
mum load current to the MOM-4 does
not exceed 2 amps (MMB-1 or SMB-1)
or with an MMB-2/-3, SMB-2, or PSR-1, 6
amps (MPS-6) or 12 amps (MPS-12).
Include the total alarm current on each
CSM-4 notification appliance circuit when
performing the calculations.
EXAMPLE:
With: one CRM-4 and one CSM-4
Total load current = 0.075 + 0.034 = 0.109A
With MPS-6:
Remaining Available Current =
2.0 - 0.109 = 1.891A (MMB-1 or SMB-1)
6.0 - 0.109 = 5.891A (PSR-1 / MMB-2/-3 / SMB-2)
with no CZM-1, PS-5A/-5N7, or NAC load
With MPS-12:
Remaining Available Current =
2.0 - 0.109 = 1.891 (MMB-1 or SMB-1)
12.0 - 0.109 =11.891 (PSR-1 / MMB-2/-3 / SMB-2)
with no CZM-1, PS-5A/-5N7, or NAC load
The remaining current may be used for alarm notifica-
tion appliances.