A-3[Revised: 11/2/15]
Electrical System Operation
When Main input power supply (230V) is on, it is
supplying line voltage to the vacuum pump electrical
system.
The Main input power supply (230V) is supplied to
the contactor, thermostat, fans, transformer, variable
frequencydrive(VFD),andthelinelter.Whenthe
On/Oswitchormastercontrolswitchareintheiro
state or the front panel is removed from the unit, the
contactor will remain open and the input power will be
connected to the input side of the contactor, thermo-
stat, fans, and the transformer only.
When the contactor is energized, it closes and con-
nectsthemaininputpowersupplytothelinelter.
Main input power supply is then applied to the VFD
through RL1 and SR2 (single phase).
Thetransformer’soutputsends24voltsACtothePC
board. 24 volts AC power is used to control the door
limitswitch,hourmeter,andoats.Theelectronicson
thePCboardconvert24VACto24VDCforthepres-
sure sensor though the means of a connector.
When instruments (suction tips) are in use, the vacu-
um pump is running and claws are turning to build up
vacuum pressure. The pressure sensor is constantly
measuring the amount of vacuum pressure. When
the pressure level drops below the vacuum set point
(12”Hg – factory setting), the pressure measure-
ment initiates the VFD to speed up the motor. When
pressure is above set point the VFD slows the motor
down.
Whenthevacuumisshutofromtheremoteswitch
the timer starts and will turn on the vacuum for one
minute every two hours. (Standard on new units,
older units can be upgraded)
Vacuum Operation.................A2
Troubleshooting.....................A4
Note
On twin units a parallel cable (4-pin Master / 6-pin Slave) connects the two base units on the side of the electrical box. The plumbing is connected using a tee assembly.
The parallel connection is controlled between variable frequency drives in a twin configuration. Twin units run the same as a single unit. Keypad, hour meter and fans are
located on the outside of the base unit. Pressure sensor and float are located on the separator tank.
AA2486i
VFD
Box
Parallel
Connection
Fans
Themostat
230 VAC
Line Voltage
Line Filter
Contactor
Pressure
Sensor
Transformer
YL
YL
3
2
1
ON
CTS
Note
Timer Bd. Std. after SN: V1648735 units prior to this can be updated
Go to Table of ContentsGo to Table of Contents