IC.PI.200.F2.02 / 520B4300
© Danfoss A/S 12-2010 (AC-AKC/bpv)
032R9314
032R9314
Instruction
EV210B 6, 8, 10, 15, 20, 25
Normally Closed (NC)
Types
Type EV210B 6, 8, 10, 15, 20, 25 Normally Closed (NC)
NC
Coil replacement
1. Before removing the coil, voltage
must be disconnected, otherwise
the coil will burn out.
2. Use a screwdriver to lever the coil
from the armature.
Mounting the valve
1. Clean the pipe system before
mounting the valve.
2. Mount lter in front of the
valve if there are impurities in
media.
3. The arrow cast on the body
and cover must point in the
direction of the ow.
4. Mount the valve as shown in
the pictures. The valve can be
mounted with a angle of 360o
from upright position. Installa-
tion with the coil upwards is pre-
ferred.
5. Use counterforce when tight-
ening up pipe connections,
i.e. use a spanner on both the
valve body as well as on the
pipe connector.
To be continued on page 2
Media temperature
Gasket material Media Temperature
EPDM Water
-30°C → +120°C
FKM Oil / Inert gas incl air
-10°C → +100°C