M-system MDP-200T User manual

Type
User manual
MDP-200T
P. 1 / 3
EM-8227
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
LIGHTNING SURGE PROTECTOR FOR
PHOTOVOLTAIC SYSTEM, INSTRUMENT SHELTER
MODEL
MDP-200T
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
Surge protector ............................................................. (1)
DIN rail mounting adaptor* ........................................ (1)
Screws for mounting (M4 × 8)* .................................... (2)
*Included with option code /A33
MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
LIMITATION APPLICABLE TO M-RESTER
The M-Rester will protect electronics equipment from
damage caused by lightning by absorbing most of the
surge voltages.
However, M-Rester may not be effective against certain
extremely high voltages caused by a direct or almost di-
rect hit by lightning.
M-Rester must be installed according to this installation
/ instruction manual.
GENERAL
FUNCTION & FEATURES
•DesignedforACandspecicallyforDCpowersuppliesup
to 1 amp.
•Benecial for protectinginstruments from counter elec-
tromotive force by inductors and of course normal light-
ning surges entering from power supply lines.
•1Afuseincorporatedinelementcircuit.
SPECIFICATIONS
LINE TO LINE LINE TO EARTH
Max. line voltage (Uc)
250V AC
350V DC
----
Discharge voltage 410V min 410V min
Voltage protection level
(Up) 800V max 800V max
Leakage current
≤0.15mA
@300V DC
≤0.15mA
@300V DC
Response time ≤0.1 microsecond
Max. discharge current
(Imax)
1000A (8 / 20 µs)
Nominal current (I
N) 1.0A
Internal series resistance ≤0.4Ω including return
Dielectric strength of the
base module
1500V AC @1 minute
(G terminal to other terminals)
POINTS OF CAUTION
ENVIRONMENT
•Whenheavydustormetalparticlesarepresentintheair,
install the surge protector inside proper housing with suf-
ficient ventilation.
•Donotinstallthesurgeprotectorwhereitissubjectedto
continuousvibration.Donotsubjecttheunittophysical
impact.
•Environmentaltemperaturemustbewithin-20to+80°C
(-4to176°F)withrelativehumiditywithin30to90%RH
in order to ensure adequate life span and operation.
DIELECTRIC STRENGTH TEST
•Loosenthescrewlocatedattheleft-centeroftheelement
and remove the element module from the base before
conducting a dielectric strength testing. Otherwise the
element will start discharging at a voltage exceeding the
max. continuous operating voltage (Uc), which can cause
insulation failure of the module.
Be sure to return the element and fasten securely after
the test.
AND ....
•We recommend that you keep spare surge protectors so
that you can replace them when necessary.
•Lightning surge can enter notonly throughsignal lines
butalsothroughpowersupplylines.Werecommendthat
you also use the surge protectors for power line for suf-
ficient protection.
COMPONENT IDENTIFICATION
M•RESTER
Ground Terminal (G)
(used as mounting bracket)
Head Element
Base
Specifications
Head Element is secured to Base
with screw when the surge protector
is shipped from Factory.
MDP-200T
P. 2 / 3
EM-8227
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
INSTALLATION
In order to separate the head element from the base, loosen the screw located at the left-center of the element.
DIN RAIL MOUNTING
1. MOUNTING ONTO THE ADAPTOR
Before DIN rail mounting, secure the mounting bracket of
MDP to the mounting adaptor with a screw provided with
this product. In this step, secure at one point.
DIN Rail Mounting Adaptor
M•RESTER
2. DIN RAIL MOUNTING
Set the base socket so that its mounting slider is at the bot-
tom. Position the upper hook at the rear side of base socket
ontheDINrailandpushinthelower.Whenremovingthe
socket, push down the mounting slider utilizing a minus
screwdriver and pull.
DIN Rail Mounting Slider
35 mm wide
DIN Rail
WALL MOUNTING
Refer to the drawings below.
EXTERNAL DIMENSIONS unit: mm (inch)
P–P+
S–S+
23.5 (.93)
80 (3.15)
2–5 (.20) dia.
MTG HOLE
90 (3.54)
100 (3.94)
4–M4 TERMINAL SCREW
GROUND TERMINAL (G)
(used as mounting bracket)
27 (1.06)53 (2.09)
80 (3.15)
45 (1.77)
HEAD ELEMENT
BASE
3. GROUNDING
Secure the mounting bracket at the other point with the
other screw. In this step, secure the grounding wire togeth-
er with the screw.
Solderless Terminal
M•RESTER
MOUNTING REQUIREMENTS
unit: mm (inch)
25 (.97) MIN.
2–M4 SCREW
90 (3.54)
MOUNTING REQUIREMENTS unit: mm (inch)
8.5
(.33)
[3.3 (.13)]
DIN RAIL
35mm wide
80 (3.15)
45 (1.77)
4
(.18)
MDP-200T
P. 3 / 3
EM-8227
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MAINTENANCE
Check surge protectors periodically. Many cases of lightning are ignored, and even lightning at a far distance often causes
inductive surges.
Werecommendthatyoucheckyoursurgeprotectorabouttwiceayear,beforeandaftertherainyseason.Checkwhenever
you experience a strong lightning occurrence.
Checking procedure is explained in the following:
CHECKING
WIRING
1) Make sure that wiring is done as instructed in the connection diagram.
2) Make sure that the Ground terminal (G) is connected to the metallic housing of protected equipment.
3) Make sure that the Ground terminal (G) is grounded to earth.
DISCHARGE FUNCTION
The M-Rester Tester is available for checking the element module of this surge protector.
If you do not have one, approximate checking can be conducted as following.
1) Remove all wiring connected to the surge protector when you test the element module.
2) Check resistance across the following terminals on the high resistance range of multimeter and confirm no conduction.
The meter shows the same value as it will show when these terminals are open.
Terminals (S1) – (S2), (P1) – (P2)
3) Check that discharging occurs across the following terminals with a 500V DC 1000MΩ insulation tester. (The tester shows
≤20MΩ.)
Terminals (S1) – (S2), (S1) – (G), (S2) – (G)
If any of the above tests shows negative, replace the protector.
TERMINAL CONNECTION
Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (G) and that of the protected equipment.
M-RESTER
PROTECTED
EQUIPMENT
G
G
CROSSOVER WIRE
GROUNDING
(100 ohms or less)
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
GROUNDING
P1
P2
S1
S2
M-RESTER
Relay,
Coil, etc.
G
Discharge
Element
1A
P1
P2
S1
S2
M-RESTER
G
Discharge
Element
1A
R
CONTROL ROOM
FIELD
The M-Resters must be connected with its terminals S1 and S2 faced on power source side
in order that the fuses would be blown in case of shortcircuit of the discharge element.
  • Page 1 1
  • Page 2 2
  • Page 3 3