LG LMVN240HV Product information

  • Hello! I am an AI chatbot trained to assist you with the LG LMVN240HV Product information. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
pp
roval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
MultiFVertical/HorizontalAirHandlingUnit
LMVN240HV
Performance:
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor:
80°FDB/67°FWB
Indoor:
70°FDB/60°FWB
Outdoor:
95°FDB/75°FWB
Outdoor:
47°FDB/43°FWB
Electrical:
PowerSupply(V¹/Hz/Ø)
208230/60/1
RatedAmps(A)
0.59
Piping:
LiquidLine(in,OD)
1/4
VaporLine(in,OD)
1/2
Features:
•ESPcontrol
•Hotstart
•Autorestart
•Childlock
•Inverter(variablespeedfan)
•Groupcontrol
•Sleepmode
•Timer(on/o)
O
p
tionalAccessories
(
soldse
p
aratel
y
DrainOD,ID(in)
3/4FPT
TemperatureSensor
Thermistor
UnitData:
RefrigerantType
R410A
RefrigerantControl
EEV
SoundP ressure³H/M/L(±3dB(A) )
43/42/ 41
NetUnitWeight(lbs)
117
ShippingWeight(lbs)
140
Fan:
Type
Sirocco
Quantity
1
Motor/Drive
BrushlessDigitallyControlled/Direct
AirflowRate H/M/L(CFM)
710/640/ 480
Notes:
1.Acceptableoperangvoltage:187V253V.
2.RequiresanLGwiredthermostat.
3.SoundPressurelevelsaretestedinananechoicchamberunderISOStandard1996.
4.Adjustfanspeedtocorrectforstacpressureincreaseswhenusingeldsuppliedairlter.
5.Atfactoryfanspeedseng.
6.Airowrate(C
FM)athighspeed.
7.SeeEngineeringManualforse nsibleandlatentcapacies.
8.Allpower/communicaoncabletobeminimum18AWG,4conductor,stranded,shiel ded
andmustcomplywithapplicablelocalandnationalcode.
9.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcodes.
10.Thisunitco
meswithadryheliumcharge.
11.Correspondingrefrigerantpipinglengthisinaccordancewithstandardlengthofeach
outdoorunitandtheleveldifferenceis0ft.Allcapacitiesarenetwithacombinationratio
between95105%.
12.MustfollowinstallationinstructionsintheapplicableLGinstallationmanual.
LGProgrammableThermostat‐PREMT B10U
ExternalStaticPressure⁴⁵(inwg)
0.5
Page1of2
SBMultiFLMVN240HV0914
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregi steredtra demarkofLGCorp./ www.lghvac.com
WirelessHandheldRemoteController‐PQWRHQ0FDB
ACEz‐PQCSZ250S0
DryCon tactUnitDryContactUnit(1contact,24VACexternalpower)‐PQDSB1
DryCon tactUnitDryContactUnit(2input,powerfromindoorunit) ‐PQDSBC
DryCon tactforthirdpartythermostat‐PQDSBNGCM1
Btu/hIndoorUnit
24,000
StandardFeatures:
Acces s PanelforFieldSuppliedAirFilter
(16x20x1inch)
RemoteTemperatureSensor‐PQRSTA0
5kWElectricHeater‐ANEH 053B1
10kWElectricHeater‐ANEH103B2
IncludedAccessories:
•SimpleControllerwithMode(White)AKB72955816
NominalCoolingCapacity(Btu/h)
24,000
Foracomplet e listof availableaccessories,contactyourLG representative.
ACPPremium‐PQCPC22A1
ACPStandard‐PQCPC22N1
LonWorksGateway‐PQNFB16A1
BACnetGateway‐PQNFB17C1
ACSmartPremium‐PQCSW421E0A
Enterin
g
MixedAir:
NominalHeatingCapacity(Btu/h)
27,000
Heating(°FDB)
5981
Cooling (°FWB)
5777
MinimumExternalStaticPressure⁶ 0.1
MaximumExternalStaticP ressure⁶ 1.0
JobName/Location:
Tag#:
Date:
PONo.:
LMVN240HV
MultiFVertical/HorizontalAirHandlingUnit
Btu/hIndoorUnit
24,000
Page2of2
SBMultiFLMVN240HV0914
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
/