No. Installer Setting Factory Setting Comments
(
Notes follow this table) Default Options (More information follows this table)
11
CompressorPowerOutage
oF CPOP oF CPOP DisablesPowerOutageLockoutDelay
Protection [notes 3, 5] on CPOP EnablesPowerOutageLockoutDelay
12 ACPowerInterrupt
AC oF MONR
AC oF MONR DisablesACPowerInterruptWarning
Warning[note 5] AC on MONR EnablesACPowerInterruptWarning
13 CompressorShort 5 CSCP 5, 4, 3, 2or Selectacompressorshortcycleprotectiondelayof5,
CycleProtection[note 6] 0 CSCP 4,3,2or0minutes
14 ResidualCooling 60 FAN 90, 60, 30 SelectaResidualCoolingFanDelayof90,60,
FanDelay[note 6] or0 FAN 30or0seconds.
15 IndoorRemoteSensor I SENS I SENS Temperatureissensedfromthermostatonly.
Control*[note 7] E SENS Temperatureissensedfromremotesensoronly.
A SENS Temperatureiscombinedwiththethermostatand
theremotesensor.
16 LockoutSecurityLevel 2 LOCK 2 LOCK Iflocked–Completelockoutisenabled
1 LOCK Iflocked–Partiallockoutisenabled(SpeedBar
®
is
stillfunctional)
17 AutoChangeover 3 BAND 2, 3, 4or5 SelectaDeadBandof2°,3°,4°or5˚F
DeadBand[note 8] BAND (1°,2°or3°C)forAutoChangeovermode.
18 CompressorBalance NO BALC NO BALC DisablesBalancePoints
Point[notes 3, 9] 15-50 BALC SelectaCompressorBalancePointof15°-50°F
(-9°-10°C)
19 AuxiliaryHeatBalance NO BALA NO BALA DisablesBalancePoints
Point[notes 3, 9]
70-40 BALA
SelectaAuxiliaryHeatBalancePointof70°-40°F
(21°-4°C)
20
HeatSetPointUpperLimit
90LIM 90-60 LIM
SelectaHeatSetPointUpperLimitof90°-60°F(32°-10°C)
21
CoolSetPointLowerLimit
45LIM 45-80 LIM
SelectaCoolSetPointLowerLimitof45°-80°F(7°-27°C)
[note 6]
*WhenaBraeburn
®
outdoorsensorisconnected,thethermostatautomaticallyrecognizesit.PressBACKandNEXTatthesame
timetodisplayoutdoortemperature.
NOTE: Additional options such as Service Monitors, Setting the lock code, etc. are located in the User Settings –
See User manual for information on setting these options.
NOTES - Installer Settings
1 Onlyavailableifa2or3stagesystemtypewasselectedinoption3.
2 OnlyavailableifaConventionalsystemwasselectedinoption3.
3 Onlyavailableifa2or3stageHeatPumpsystemwasselectedinoption3.
4 OnlyavailableifaHeatPumpsystemwasselectedinoption3.
5 Onlyavailableifthe24VoltACcommonwireisconnectedtotheCterminal.
6 NotavailableifaHeatOnlyHydronicsystemisselectedinoption3.
7 OnlyavailableifaBraeburn®indoorremotesensorwasconnected.
8 Onlyavailableifautochangeoverwasenabledinoption2.
9 OnlyavailableifaBraeburnoutdoorsensorwasconnected.
Detailed Explanation of Installer Settings (also see NOTES above):
1 Temperature Scale–Selectsatemperaturescaleofeither°For°C.
2 Auto Changeover–Selectsautochangeoveronoroff.Whenautochangeovermodeisenabledand
selected,thesystemautomaticallyswitchesbetweenheatingandcoolingmodes.Thereisa5minutedelay
whenswitchingfromheatingtocoolingorcoolingtoheatinginautochangeovermode.
NOTE: Also see “Auto Changeover Dead Band” in option 17.