GeniSys Intermittent Pilot Gas Ignition Control Installation and Operation Manual
◦ If ame is not proved, the control will
lockout or enter the inter-trial waiting
period. Status LED will ash rapidly for
lockout or slowly for inter-trial waiting.
◦ If multiple trial logic is used, the control
will complete the trials for ignition.
◦ If continuous retry logic is used, the
control will wait 5 minutes and restart
the ignition sequence. The Status LED
will ash slowly during waiting period.
◦ When ame is proved and the main
valve is opened, the control will
continue in run mode until the end of
the call for heat.
◦ When the call for heat is ended, the
pilot valve, main valve and all LEDs are
de-energized.
Settings
The trade replacement version of the 7586
can be congured using the diagnostic
tool to replace many intermittent pilot
controls. Settings are locked after 4 hours
of burner operation.
Lockout without Retry
If the Status LED is ashing rapidly (3 times
per second), the control is in lockout. All
control outputs are turned off and the control
will not respond to a call for heat. The
control enters lockout when:
◦ The control fails to prove ame during
the trial for ignition period
◦ The control fails the valve relay check
Lockout with Retry (optional)
Interruptions in the gas supply can prevent
the burner from lighting during the trial for
ignition and cause the control to lockout.
If the house or building is unoccupied
for long periods during cold weather, a
lockout can lead to low temperatures or
freezing in the structure.
The 7586S, D and T models can be
congured to automatically allow an
ignition retry once every 1-8 hours
(selectable using the diagnostic tool or by
factory conguration). This conguration
may help by allowing periodic ignition
retries until the gas supply is restored.
The control will only allow retry if the
lockout is caused by failure to prove ame
during the trial for ignition. If the lockout is
caused due to a failed valve relay check,
no retry is allowed. The ignition retries
will only happen if there is power to the
control and there is a call for heat from
the thermostat or controller. This retrial
feature may not be available (factory
locked) in some controls including the
7586C version.
The green Status LED will ash slowly
(once per second) during waiting period.
Reset from Lockout
Reset control from lockout by turning
down the thermostat for 10 seconds or
by removing power from system for 10
seconds. Manual reset control must be
reset by pushing reset button when control is
powered
.
Fire or Explosion
Hazard
Can cause severe injury, death,
or property damage.
Replacement control must be congured
to match all timings, settings and the pre-
purge of the control being replaced.
• DO NOT SET THE TRIAL FOR
IGNITION TIMING LONGER
THAN THE TIMING ON THE
ORIGINAL CONTROL. Severe
injury, death, or substantial
property damage could result from
a longer trial for ignition timing.
• MATCH THE LOCKOUT LOGIC
SEQUENCE TO THE ORIGINAL
CONTROL. If the original control
is a single trial for ignition or
allows three trials for ignition
before lockout, the replacement
control must match the number of
ignition trials.