Danfoss Termix VX Compact 28 - 40 Operating instructions

Type
Operating instructions

Danfoss Termix VX Compact 28 - 40 is a complete solution for space heating, ensuring optimal safety, efficient energy transfer, service-friendly construction, and a compact design. It's ideal for indirect heating systems, providing a high level of security against burst pipes and water damage. The substation includes a heating circuit with a plate heat exchanger, safety valve, manometer, thermometers, ball valves, drain valve, air valve, and circulation pump. The heating temperature can be controlled thermostatically or by an electronic controller with an outdoor temperature sensor.

Danfoss Termix VX Compact 28 - 40 is a complete solution for space heating, ensuring optimal safety, efficient energy transfer, service-friendly construction, and a compact design. It's ideal for indirect heating systems, providing a high level of security against burst pipes and water damage. The substation includes a heating circuit with a plate heat exchanger, safety valve, manometer, thermometers, ball valves, drain valve, air valve, and circulation pump. The heating temperature can be controlled thermostatically or by an electronic controller with an outdoor temperature sensor.

OperatingGuide
TermixVXCompact28-40
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................6
4.3Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1Heatingcircuit......................................................10
6.2Other.................................................................12
6.3Maintenance........................................................14
7.0Troubleshooting..............................................15
7.1Troubleshootingingeneral......................................15
7.2TroubleshootingHE...............................................15
7.3Disposal.............................................................16
8.0Declaration......................................................18
8.1Declarationofconformity........................................18
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
1
OperatingGuideTermixVXCompact28-40
2.0Functionaldescription
Districtheatingsubstationforindirectheating.
Application
TheTermixVXCompact28-40isacompletesolutionfor
spaceheatingwithoptimalsafety,efcientenergytransfer,
service-friendlyconstructionandacompactdesign.Thesubstation
isapplicable,ifaheatexchangerisrequiredoronaconversionto
districtheating,wheretheexistingequipmentisunsuitablefor
directconnection.TheTermixVXCompact28-40substationis
ideal,whereahighlevelofsecurityagainstburstpipesandwater
damageintheheatingsystemisrequired.
Districtheating(DH)
Thedistrictheatingcircuitisprefabricatedwithaowcontroller
withintegratedcontrolvalve,thermometersandballvalves.
Heating(HE)
Theheatingcircuitconsistsofaplateheatexchanger,safetyvalve,
manometer,thermometers,ballvalves,drainvalve,airvalveand
circulationpump.Theheatingtemperaturecanbecontrolled
thermostaticallyorbyanelectroniccontrollerwithanoutdoor
temperaturesensor.Dependingontheapplication,differentheat
exchangersdimensionedforcentraloroorheatingcanbeused.
Domestichotwater(DHW)
TermixVXCompact28-40issuppliedwithconnectionpipesfor
aDHWtankonthesupplyline.
2
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
3
OperatingGuideTermixVXCompact28-40
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Heating(HE)supply
2.Heating(HE)return
3.Districtheating(DH)supply
4.Districtheating(DH)return
5.Tankowline(TFL)
6.Tankreturnline(TRL)
Dimensions(mm):H999xW1285xD423
Weight(approx.):70kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Mountingframe.
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
5
OperatingGuideTermixVXCompact28-40
4.2Start-up
Start-up,Indirectheating
Filling:
1:Firstll
Whencarryingoutrstll,theheatexchangermustbeslowlylled
withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This
instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tollthe
system,theballvalvemustrstbeclosed,theplugremovedand
asupplyhoseconnected.Onre-openingtheballvalve,system
llcancommence.
4:Pre-pressure
Whenllingthesystemwithwater,thepressuregaugeshouldbe
observedclosely.Theexpansionvesselissuppliedpre-pressurised
to0.5bar.Thepre-pressurerequiredateachsubstationwill
dependonsystemhead(thedistancebetweenthelowestand
highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure
approximately1-2barhigherthanthepre-pressuresetting.The
ballvalveisthenclosed,thehoseremovedandtheplugputback
in.
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Height(m)Pressure(bar)
050,5
5101,0
1015
1,5
15202,0
6
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
7
OperatingGuideTermixVXCompact28-40
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
10
Circulatorpump
27
Actuator,HE
F
Electroniccontroller
20
Filling/drainvalve
30
Flowcontrollerwithintegratedcontrolvalve
4
Safetyvalve,HE
25
Pressuregaugewithballvalve
48
Airvent,manual
9
Strainer
26
Pressuregauge,HE
8
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
5.2Schematicdiagram
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
HWC
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
10
Circulatorpump
24
Deliveredloosewithunit
E
Hotwatertankwithcoil
11
Domestichotwaterpump
25
Pressuregaugewithballvalve
F
Electroniccontroller
16
Outdoorsensor
26
Pressuregauge
L
Borderofdelivery
18
Thermometer
27
Actuator
1
Ballvalve
19
Surfacesensor
29
2-waymotorizedvalve
2
Singlecheckvalve
20
Filling/drainvalve
30
Flowcontrollerwithintegratedcontrolvalve
4
Safetyvalve
21
Tobeorderedseparately
31
Differentialpressurecontroller
9
Strainer
22
Testconnection
44
Immersionsensor
23
Ballvalve
48
Airvent,manual
DCW:
DomesticColdWater
DHW:DomesticHotWater
HWC:
HotWaterCirculation
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
9
OperatingGuideTermixVXCompact28-40
6.0Controls
6.1Heatingcircuit
6.1.1Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.owisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
6.1.2Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.1.3Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
10
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
6.1.4Outdoortemperaturesensor(ESMT)
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
6.1.5Circulatorpump
TheUPML,UPMXLcirculatorpumpsaredesignedforcirculating
liquidsinheatingsystemswithvariableows,internallycontrolled
withthreeproportionalpressurecurvesandthreeconstant
pressure/powercurvestobeselectedviauserinterface.
EuP2015Ready.
TheMAGNA3circulatorpumpsaredesignedforcirculatingliquids
inheatingsystemswithvariableowswhereyouwanttooptimise
thesettingofthepumpdutypoint,thusreducingenergycosts.
EuP2015Ready.
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
11
OperatingGuideTermixVXCompact28-40
6.1.6GrundfosUPML/UPMXLinstructions
PP=Proportionalpressure(fastash)
CP=Constantpressure(slowash)
6.1.7HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
6.2Other
6.2.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
12
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
6.2.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
6.2.3Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater
onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do
notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand
tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
13
OperatingGuideTermixVXCompact28-40
6.3Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
14
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronDHcircuit
clogged.
Cleanthelter(afterconsultingtheDH
plantoperator).
Defectiveorwronglyadjusteddifferential
pressurecontroller.
Checktheoperationofthedifferential
pressurecontrollercleanthevalveseatif
required.
Sensordefectiveorpossiblydirtinthe
valvehousing.
Checktheoperationofthethermostat
cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor
defective-possiblypowerfailure.
Checkifthesettingofthecontroller
iscorrectseeseparateinstructions.
Checkthepowersupply.Temporary
settingofmotortomanual”controlsee
instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin
thepumphousingseepumpmanual.
Thepumpissetattoolowspeedof
rotation.
Setthepumpathigherspeedofrotation.
Pressuredropthepressuredropon
theradiatorcircuitshowslowerthan
recommendedoperatingpressure.
Fillwateronthesystemandcheckthe
functioningofthepressureexpansion
vesselifrequired.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature
adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Checkreplace.
Unevenheatdistributioninbuilding
becauseofincorrectlysetbalancingvalves,
orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor
branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
15
OperatingGuideTermixVXCompact28-40
DHsupplytemperaturetoohigh.
Wrongsettingofthermostatorof
automaticcontrols,ifany.
Adjustautomaticcontrols,see
instructionsforautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callautomaticcontrolsmanufactureror
replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
DHsupplytemperaturetoolow.
Wrongsettingofautomaticcontrols,ifany.
Adjustautomaticcontrolsseeinstructions
forautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callinautomaticcontrolsmanufactureror
replacecontroller.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
Wrongplacement/ttingofoutdoor
temperaturesensor.
Adjustlocationofoutdoortemperature
sensor.
Strainerclogged.Cleangate/strainer.
ToohighDHreturntemperature.
Toosmallheatingsurface/toosmall
radiatorscomparedtothetotalheating
requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface.
Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly
acrossthefullheatingsurfaceopenall
radiatorsandkeeptheradiatorsinthe
systemfromheatingupatthebottom.It
isextremelyimportanttokeepthesupply
temperaturetotheradiatorsaslowas
possible,whilemaintainingareasonable
levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic
controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator
valve(s).Singlepipeloopsystemsrequire
specialone-piperadiatorvalves.
Checkset/replace.
Dirtinthemotorizedvalveorinthe
differentialpressurecontroller.
Checkcleanout.
Defectivemotorizedvalve,sensoror
automaticcontroller.
Checkreplace.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Noiseinsystem.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror
electroniccontroller.
Checkreplace.
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
16
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
17
OperatingGuideTermixVXCompact28-40
8.0Declaration
8.1Declarationofconformity
8.1.1Substationlabel
Normallythebelowmentioneddeclarationofconformityapplies:
"Substations-Category0withelectricalequipment".
Unlessttedwithayellowlabel(PEDKAT.1)onthesubstationlabel
thenthefollowingdeclarationofconformityapplies:"Substations-
Category1withelectricalequipment".
PED
KAT.
1
Category0withelectricalequipment
18
DEN-GT
VI.GE.F3.02/LUK43360
DanfossDistrictEnergy
OperatingGuideTermixVXCompact28-40
Category1withelectricalequipment
DanfossDistrictEnergy
VI.GE.F3.02/LUK43360
DEN-GT
19
OperatingGuideTermixVXCompact28-40
ProducedbyDanfossA/S©02/2017
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Danfoss Termix VX Compact 28 - 40 Operating instructions

Type
Operating instructions

Danfoss Termix VX Compact 28 - 40 is a complete solution for space heating, ensuring optimal safety, efficient energy transfer, service-friendly construction, and a compact design. It's ideal for indirect heating systems, providing a high level of security against burst pipes and water damage. The substation includes a heating circuit with a plate heat exchanger, safety valve, manometer, thermometers, ball valves, drain valve, air valve, and circulation pump. The heating temperature can be controlled thermostatically or by an electronic controller with an outdoor temperature sensor.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI