  • Hello! I am an AI chatbot trained to assist you with the Danfoss Termix Compact 28 VX-FI Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
TermixCompact28VX-FI/HWP/HWS
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1MountingtheCompactstation..................................4
4.2Start-up..............................................................11
4.3Electricalconnections.............................................13
5.0Design.............................................................14
5.1Design...............................................................14
5.2Schematicdiagram................................................15
6.0Controls..........................................................18
6.1Heatingcircuit......................................................18
6.2Other.................................................................22
6.3Maintenance........................................................24
7.0Troubleshooting..............................................25
7.1Troubleshootingingeneral......................................25
7.2TroubleshootingHE...............................................26
7.3Disposal.............................................................28
8.0Declaration......................................................31
8.1Declarationofconformity........................................31
©Danfoss|2019.01VI.LZ.J2.02/LUK42365|1
2.0Functionaldescription
Districtheatingsubstationforindirectheating.
Spaceheating
TheTermixCompact28VX-FIisaheatexchangerunitforthe
productionofheatinginlargebuildingssuchassportscentres,
schools,blocksofflatsetc.Itcanbeusedforconnectiontoindirect
districtheatinginplaceswherethedistrictheatingplantrequiresa
hydraulicbreakontheplantside.Itisalsosuitableforconversion
todistrictheatingwhenthesecondaryheatingsystemissuitable
tobeingconnectedtodirectdistrictheatingorwhenaparticularly
effectivesecurityagainstleakageintheheatingsystemisrequired.
Itispossibletoconnectahot-watertank.
Efficientheatexchanger
Thesubstationisfittedwithanefficientplateheatexchanger,
whichensuresthemostfavourableheatextractionandachieves
optimumcomfortandoperatingeconomy.
Severalvariants
TermixCompact28VX-FIisbuiltwithaheatexchangerforspace
heating,flowcontroller,pump,electronicregulationoftheheating
circuitaswellasadirectoutletforahotwatertank.Theelectronic
controllerisfactorypre-set.Electricalcomponentsarepre-wired,
andtheunitisequippedwithaplugfor230Va.c.
Itisrecommendedthatdynamicbalancingvalvesareinstalledin
thebuildingsrisersintheheatsupplyandontheheatingsystems
returnlineimmediatelybeforetheunit.
TermixCompact28VX-FIisproducedinstandardconstructions:
VXwithheatexchangerforindirectheating.
VXwithheatexchangerforindirectheatingandintegrated
tankregulation.
Flexiblesolution
Pipeconnectioncanbemadefromeitherthetoporbottom,which
makesthissolutionhighlyflexible.Atthesametime,bothspace
andtimearesavedwheninstalling.
Minimalheatloss
Completeinsulationoftheunitensuresminimalheatloss.
Reliableandeasytoinstall
TermixCompact28VX-FIisoperationallyreliable.Aqualityproduct
manufacturedinDenmark,whichiseasytoinstallandquickly
commissioned.
2|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheflowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH.
OneoftheobligationsinREACHistoinformcustomersabout
presenceofCandidatelistsubstancesifany,weherebyinform
youaboutonesubstanceonthecandidatelist:Theproduct
containsbrasspartswhichcontainslead(CASno:7439-92-1)ina
concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis
110°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|3
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.0Mounting
4.1MountingtheCompactstation
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Tankflowline(TFL)
6.Tankreturnline(TRL)
Connectionsizes:
DH+HE:
G1”(int.thread)
TFL+TRL:
G¾”(int.thread)
Dimensions(mm):
Withinsulation:
H890xW905xD400
Weight(approx.):60kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
Removethefront.
Removeotherblocks.
Attachthemountingrailtothewall.
Liftthestation.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|5
OperatingGuideTermixCompact28VX-FI/HWP/HWS
Mountthestationonthemountingrail.
Attachthestationtothewallintheholesonthemountingplate.
Installthesafetyvalve.
Installballvalves.
MountblockA(CifitistheMagnapump)ontheleft-handsideof
thepump.AttachblockEtoblockA/C,andattachittothepipe
abovethepumpbyclickingitinplace.
6|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
MountblockB(DifitistheMagnapump)ontheright-handsideof
thepump.
MountblockF(GforVM2valve).Theblockishingedandcanbe
drawnaroundthevalve.AttachtheblocktoblockB/DandE.
MountblockJandHaroundthevalveforthetankcontrol.
Mountthefrontcover.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|7
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.1.1InstallingtheCompactstation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,flangedorweldedconnections.
Keyholeformounting.
8|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.1.2Pipeconnectionsup
Removethetopblock.
Removethepipeplugsatthetopofthestation.
RemoveU-clamps.
Removepipes.Anglesandteesareturnedsothatpipescanbe
installedfromabove.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|9
OperatingGuideTermixCompact28VX-FI/HWP/HWS
Installthepipes.Districtheatingsupplypipestobeinterchanged.
FitU-clamps.
Fitthepipeplugsatthebottomofthestation.
Fitthetopblock.
10|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.2Start-up
Start-up,Indirectheating
Filling:
1:Firstfill
Whencarryingoutfirstfill,theheatexchangermustbeslowlyfilled
withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This
instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tofillthe
system,theballvalvemustfirstbeclosed,theplugremovedand
asupplyhoseconnected.Onre-openingtheballvalve,system
fillcancommence.
4:Pre-pressure
Whenfillingthesystemwithwater,thepressuregaugeshouldbe
observedclosely.Theexpansionvesselissuppliedpre-pressurised
to0.5bar.Thepre-pressurerequiredateachsubstationwill
dependonsystemhead(thedistancebetweenthelowestand
highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure
approximately1-2barhigherthanthepre-pressuresetting.The
ballvalveisthenclosed,thehoseremovedandtheplugputback
in.
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconfirmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderfloorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemfill.
Height(m)Pressure(bar)
050,5
5101,0
1015
1,5
15202,0
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|11
OperatingGuideTermixCompact28VX-FI/HWP/HWS
Underfloorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderfloorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderfloorheatingcontroller.Thepumpmustbestoppedif
allunderfloorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenflowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
12|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|13
OperatingGuideTermixCompact28VX-FI/HWP/HWS
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
10
Circulatorpump
26
Pressuregauge,HE
F
Electroniccontroller
14
Sensorpocket,energymeter
27AActuator,HE
4
Safetyvalve,HE
20
Filling/drainvalve
48
Airvent,manual
9
Strainer
25
Pressuregaugewithballvalve
14|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
5.2Schematicdiagram
5.2.1SchematicdiagramTermixCompact28VX-FI
DH
Supply
HE
Supply
DH
Return
HE
Return
TRL
TFL
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
11
Domestichotwaterpump
25
Pressuregaugewithballvalve
E
Hotwatertankwithcoil
14
Sensorpocket,energymeter
26
Pressuregauge
F
Electroniccontroller
16
Outdoorsensor
27
Actuator
L
Borderofdelivery
18
Thermometer
29
2-waymotorizedvalve
1
Ballvalve
19
Surfacesensor
30
Flowcontrollerwithintegratedcontrolvalve
2
Singlecheckvalve
20
Filling/drainvalve
31
Differentialpressurecontroller
4
Safetyvalve
23
Ballvalve
44
Immersionsensor
9
Strainer
24
Deliveredloosewithunit
48
Airvent,manual
10
Circulatorpump
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|15
OperatingGuideTermixCompact28VX-FI/HWP/HWS
5.2.2SchematicdiagramTermixCompact28VX-FIHWP
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
HWC
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
16|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
5.2.3SchematicdiagramTermixCompact28VX-FIHWS
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
HWC
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
11
Domestichotwaterpump
25
Pressuregaugewithballvalve
E
Hotwatertankwithcoil
13
Chargingpump
26
Pressuregauge
F
Electroniccontroller
14
Sensorpocket,energymeter
27
Actuator
L
Borderofdelivery
16
Outdoorsensor
29
2-waymotorizedvalve
1
Ballvalve
18
Thermometer
30
Flowcontrollerwithintegratedcontrolvalve
2
Singlecheckvalve
19
Surfacesensor
44
Immersionsensor
4
Safetyvalve
20
Filling/drainvalve
48
Airvent,manual
9
Strainer
24
Deliveredloosewithunit
69
On/offvalve
10
Circulatorpump
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
TFL:
Tankflowline
TRL:
Tankreturnline
DHW:
Domestichotwater
HWC:
Hotwatercirculation
DCW:
Domesticcoldwater
5.2.4Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
110°C
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|17
OperatingGuideTermixCompact28VX-FI/HWP/HWS
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsoutthefluctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingflowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.flowisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
18|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
6.1.3Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
6.1.5Outsidetemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.01|19
OperatingGuideTermixCompact28VX-FI/HWP/HWS
6.1.6Circulatorpump
TheUPML,UPMXLcirculatorpumpsaredesignedforcirculating
liquidsinheatingsystemswithvariableflows,internallycontrolled
withthreeproportionalpressurecurvesandthreeconstant
pressure/powercurvestobeselectedviauserinterface.
EuP2015Ready.
TheMAGNA3circulatorpumpsaredesignedforcirculatingliquids
inheatingsystemswithvariableflowswhereyouwanttooptimise
thesettingofthepumpdutypoint,thusreducingenergycosts.
EuP2015Ready.
6.1.7GrundfosUPML/UPMXLinstructions
PP=Proportionalpressure(fastflash)
CP=Constantpressure(slowflash)
20|©Danfoss|2019.01
VI.LZ.J2.02/LUK42365
OperatingGuideTermixCompact28VX-FI/HWP/HWS
/