Tecnoware FBBEVODS72/09 User manual

Type
User manual

This manual is also suitable for

Battery Box
FBBEVODS72/XX Type
User’s Manual
Index
1
Safety Warnings ............................................................................ 1
1.1 Product Disposal ......................................................................... 1
1.2 Lead Batteries ............................................................................ 1
2
Mechanical Drawings ...................................................................... 2
3
FBBEVODS72/07-09 ........................................................................ 3
4
FBBEVODS240/14-18 ...................................................................... 5
5
FBBEVODS240/21-27 ...................................................................... 7
6
Connections with the UPS ................................................................ 9
© Copyright 2010 TECNOWARE s.r.l. All rights reserved.
All trademarks are property of their respective owners.
TECNOWARE s.r.l.
Via Montetrini, 2E – Molino del Piano – Florence – Italy
www.tecnoware.com
This manual has been printed and edited by TECNOWARE s.r.l.
July 2010 edition – version 1.0
Battery Box Type FBBEVODS72/XX 1 User’s Manual
1 Safety Warnings
Risk of electric shock: if all the batteries are connected, inside the Battery Box there are
internal parts which are at a high Voltage and are potentially dangerous, capable of
causing injury or death by electric shock.
Any repair or maintenance work must be performed exclusively by qualified technical
personnel authorized by TECNOWARE. TECNOWARE declines any responsibility if this
warning is disregarded.
Battery fuses shall only be replaced with fuses of same rating or equivalent.
Danger of explosion and fire if the batteries of the wrong type or number are used.
Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate
batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic
The Battey Box is compliant with the European Community directives. Hence it is marked:
1.1 Product Disposal
This Battery Box cannot be disposed as an urban waste, but must be treated as a separate waste. Any
violation is indictable with financial sanctions as per in force regulations.
An incorrect waste disposal or an improper use of the same or of any parts can be damaging for the
environment and for human health.
A correct waste disposal of products having the dustbin symbol marked by a cross help to avoid
negative consequences to the environment and to human health.
1.2 Lead Batteries
The Battery Box may contain lead acid, sealed, maintenance free batteries.
This kind of batteries, if handled by non-experienced personnel, can cause electric shock or short-
circuit.
For this reason the batteries can be removed only by qualified technical personnel, specialized and
authorized by Tecnoware. Tecnoware declines any responsibilities if this rule is not followed.
The batteries cannot be disposed as an urban waste, but must be treated in conformity with
2006/66/CE European Directive; any violation is indictable with financial sanctions as established into
2006/66/CE European Directive.
User’s Manual 2 Battery Box Type FBBEVODS72/XX
2 Mechanical Drawings
Dimension (W x H x D) (19 x 31.5 x 52.7) cm
Net Weight without Batteries 14 Kg
Batteries Number 6 12 18
Net Weight with Batteries 7Ah 26 Kg 38 Kg 50 Kg
Net Weight with Batteries 9Ah 29 Kg 44 Kg 59 Kg
19 cm
31.5 cm
33.
5
52.
7
Battery Box Type FBBEVODS72/XX 3 User’s Manual
3 FBBEVODS72/07-09
BOX BATTERY MODELS
Box Battery Code Description UPS Power
Battery
Capacity
Cables Section
Breaker Max
Current
FBBEVODS72/07
Battery Box Compatible with UPS
EVO DSP MM/MM
2.4 KVA 7Ah 6 mm
2
50 A
FBBEVODS72/09 3.6 KVA 9Ah 6 mm
2
50 A
BATTERIES
Battery Type Lead acid, sealed, free maintenance, 12 Vdc
Battery Number 1 x 6
Nominal Battery Voltage 72 Vdc
ENVIRONMENTAL CONDITIONS
Storage Temperature Range -25°C to +55°C (15°C to 40°C recommended for longer Battery life)
Operating Temperature Range 0°C to +40°C (20°C to 25°C recommended for longer Battery life)
Relative Humidity Range 0% - 95% (non condensing)
Max. Altitude without Derating 1000 meters
User’s Manual 4 Battery Box Type FBBEVODS72/XX
15cm
72 VDC INPUT 72 VDC INPUT
33cm
33cm
52cm
58cm
SELECTOR
RED
(+ BATTERY)
BLACK
(
-
BATTERY)
UP
REAR SIDE
SECOND
BATTERY
SHELF
TOP VIEW OF SHELVES
FIRST
BATTERY
SHELF
FRONT SIDE
P1 P2 P3 P4 P5
P10 P9 P8 P6
P1 P2 P3 P4 P5
P10 P9 P8 P6
P7
P7
CHARGER
NH
FUSE
7A
L
BATTERY
CHARGER INPUT
N
G
OFF
ON
1A
2A 3A
4A
5A 6A
A = FIRST BLOCK
Battery Box Type FBBEVODS72/XX 5 User’s Manual
4 FBBEVODS240/14-18
BOX BATTERY MODELS
Box Battery Code Description UPS Power
Battery
Capacity
Cables Section
Breaker Max
Current
FBBEVODS72/14
Battery Box Compatible with UPS
EVO DSP MM/MM
2.4 KVA 7Ah 6 mm
2
50 A
FBBEVODS72/18 3.6 KVA 9Ah 6 mm
2
50 A
BATTERIES
Battery Type Lead acid, sealed, free maintenance, 12 Vdc
Battery Number 2 x 6
Nominal Battery Voltage 72 Vdc
ENVIRONMENTAL CONDITIONS
Storage Temperature Range -25°C to +55°C (15°C to 40°C recommended for longer Battery life)
Operating Temperature Range 0°C to +40°C (20°C to 25°C recommended for longer Battery life)
Relative Humidity Range 0% - 95% (non condensing)
Max. Altitude without Derating 1000 meters
User’s Manual 6 Battery Box Type FBBEVODS72/XX
FRONT SIDE
SECOND
BATTERY
SHELF
TOP VIEW OF SHELVES
FIRST
BATTERY
SHELF
REAR SIDE
UP
OFF
ON
CHARGER
NH
FUSE
7A
BATTERY
CHARGER INPUT
L
N
G
72 VDC INPUT 72 VDC INPUT
SELECTOR
RED
(+ BATTERY)
BLACK
(
-
BATTERY)
52cm
7cm
P1 P2 P3 P4 P5
P10 P9 P8 P6
P1 P2 P3 P4 P5
P10 P9 P8 P6
P7
P7
58cm
28cm
1B 2B 3B 4B 5B 6B
1A
2A
3A 4A 5A 6A
A = FIRST BLOCK
B= SECOND BLOCK
Battery Box Type FBBEVODS72/XX 7 User’s Manual
5 FBBEVODS240/21-27
BOX BATTERY MODELS
Box Battery Code Description UPS Power
Battery
Capacity
Cables Section
Breaker Max
Current
FBBEVODS72/21
Battery Box Compatible with UPS
EVO DSP MM/MM
2.4 KVA 7Ah 6 mm
2
50 A
FBBEVODS72/27 3.6 KVA 9Ah 6 mm
2
50 A
BATTERIES
Battery Type Lead acid, sealed, free maintenance, 12 Vdc
Battery Number 3 x 6
Nominal Battery Voltage 72 Vdc
ENVIRONMENTAL CONDITIONS
Storage Temperature Range -25°C to +55°C (15°C to 40°C recommended for longer Battery life)
Operating Temperature Range 0°C to +40°C (20°C to 25°C recommended for longer Battery life)
Relative Humidity Range 0% - 95% (non condensing)
Max. Altitude without Derating 1000 meters
User’s Manual 8 Battery Box Type FBBEVODS72/XX
P1 P2 P3 P4 P5
P10 P9 P8 P6
P1 P2 P3 P4 P5
P10 P9 P8 P6
CHARGER
OFF
ON
NH
FUSE
7A
L
BATTERY
CHARGER INPUT
N
G
72 VDC INPUT 72 VDC INPUT
33cm
33cm
52cm
58cm
52cm
58cm
28cm
15cm
7cm
28cm
P7
P7
RED
(+ BATTERY)
BLACK
(
-
BATTERY)
SELECTOR
REAR SIDE
UP
SECOND
BATTERY
SHELF
TOP VIEW OF SHELVES
FRONT SIDE
FIRST
BATTERY
SHELF
1A
2A 3A
4A
5A 6A
1C 2C 3C 4C 5C 6C
1B
2B
3B 4B 5B 6B
A = FIRST BLOCK
B= SECOND BLOCK
C = THIRD BLOCK
Battery Box Type FBBEVODS72/XX 9 User’s Manual
6 Connections with the UPS
+
-
+
BATTERY
-
BATTERY
+
BATTERY
-
BATTER
Y
BATTERY BOX
BATTERY
CONNECTOR
UPS
OTHER
BATTERY BOX
TECNOWARE s.r.l.
www.tecnoware.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Tecnoware FBBEVODS72/09 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI