Eaton 93E XL Operating instructions

Category
Uninterruptible power supplies (UPSs)
Type
Operating instructions
Eaton
®
93E XL UPS
10-40 kVA (380/400/415V)
Installation and Operation Manual
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE
INSTRUCTIONS
This manual
contains important instructions
that you should follow during installation
and
maintenance
of the UPS
and
batteries. Please
read all
instructions before operating
the
equipment
and save this manual for future
ref
erence.
WARNING
The sales of this product is strictly restricted to knowledgeable service partner (GB/T 17626). To prevent Electromagnetic
Interference (EMI), Extra precaution will be necessary
©2016 Eaton Cor
por
ation
All Rights
Reserv
ed
The
contents
of this manual are the copyright of the
publisher
and may not be
reproduced
(even
e
xtracts)
unless
permission granted.
Every care has
been
taken to
ensure
the
accuracy
of the inf
ormation
contained
in this manual, but
no
liability
can be
accepted
for any errors or
omission.
The right to
mak
e
design modifications
is
reser
v
ed.
T
able
of
Contents
1 INTRODUCTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1. 1 U P S
Standard Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
1.1.1 Installation
Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.1.2 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.1.3
Customer Interface.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.1.4 High-Efficiency
Mode.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.1.5
Advanced
Battery
Management
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.1.6
Maintenance Bypass
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1. 2
Options
and
A
ccessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.2.1 External Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.2.2 Parallel
System
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.2.3 Monitoring and
Communication
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
1. 3 B a tt e ry
System.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
1. 4 B a s i c
System Configurations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
1.5 Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
1. 6
Conventions
Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
1. 7
Symbols,
Controls, and
Indicators
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
1.8 For More
Information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
1.9 Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
2 SAFETY WARNINGS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . .
2-1
3 UPS INSTALLATION PLAN AND UNPACKING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
3.1 Creating an Installation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
3.2
Preparing
the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
3.2.1
Environmental
and Installation
Considerations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
3.2.2 UPS
System
P
o
w
er
Wiring
Preparation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
3.2.3 UPS
System Interface
Wiring
Preparation.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3
Inspecting
and Unpacking the UPS
Cabinets
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4 UPS SYSTEM INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4.1 Preliminary Installation
Information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4.2 Unloading the UPS Cabinet from the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4.3 External Battery Cabinet Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
4.4 External
P
o
w
er
Wiring Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26
4.5 Installing
Interface Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
4.5.1 Installing Building Alarm
Connections.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
4.5.2 Installing Parallel Pull Chain and CAN Control Wiring and
Connections
. . . . . . . . . . . . . . . . . . . . . . . . . 31
4.5.3 Installing Mini-Slot
Interface Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.6 Installing a REPO Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.7 Initial
Startup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.8
Completing
the Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
1. 1.7
Dual input
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Table of
Contents
5
UNDERSTANDING UPS OPERATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5.1 UPS
System
O
v
er
vie
w
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5.2
Single UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
5.2.1
Modes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
5.2.2
Standard
Normal
Mode.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
5.2.3 High-Efficiency Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
5.2.4
Bypass
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
43
5.2.5 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
5.3 Single UPS Unit
System
Oneline
Configurations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
45
6 UPS OPERATING INSTRUCTIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6.1 UPS Controls and
Indicators
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6.2
Using the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50
6.2.1
Status
Indicators
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50
6.2.2
System Events
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
51
6.2.3 Using the LCD and
Pushbuttons
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
52
6.2.4 Using the Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53
6.2.5 Mimic
Screen
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53
6.2.6 Display Menu
Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54
6.2.7
System
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
56
6.3 Single UPS
Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
58
6.3.1 Starting the UPS in
Standard
Normal Mode (Default Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.3.2 Starting the UPS in
Bypass
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
59
6.3.3 Transfer from Normal to
Bypass
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.3.4 Transfer from
Bypass
to Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.3.5 Transfer from
Standard
Normal Mode to HE
mode
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.3.6 Transfer from HE Mode to
Standard
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
6.3.7 Transfer from Normal Mode to Internal
Maintenance Bypass
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
1
6.3.8 Transfer from Internal
Maintenance Bypass
to Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.3.9 UPS and Critical Load
Shutdown.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
62
6.3.10 Charger Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
2
6.3.11 Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
3
6.3.12 Using the UPS LOAD OFF
Command
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
3
6.3.13 Using the
Remote Emergency Power-off
Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
4
6.4 Multiple UPS Parallel
Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
6
6.4.1 Starting the Parallel UPS in
Standard
Normal Mode (Default Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
7
6.4.2 Starting the Parallel UPS in
Bypass
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
8
6.4.3 Transfer from Normal to
Bypass
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
9
6.4.4 Transfer from
Bypass
to Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
9
6.4.5 Single UPS
Shutdown.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6.4.6 Single UPS
Restart
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
70
6.4.7 UPS and Critical Load
Shutdown.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
6.4.8 Charger Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
6.4.9 Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
72
6.4.10 Using the UPS LOAD OFF
Command
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.4.11 Using the
Remote Emergency Power-off
Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
Table of
Contents
7
COMMUNICATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1
7.1 Mini-Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1
7.2 Building Alarm Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
76
8 UPS MAINTENANCE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-1
8.1
Important
Safety
Instr
uctions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-1
8.2
Performing Preventative Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
78
8.2.1
DAILY
Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
78
8.2.2
MONTHLY
Maintenance.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
78
8.2.3 PERIODIC
Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
79
8.2.4
ANNUAL
Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
79
8.2.5
BATTERY
Maintenance.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
79
8.3 Installing
Batteries
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
8.4 Recycling the Used Battery or UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
8.5
Maintenance
Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
9
PRODUCT SPECIFICATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-1
9.1 Model
Numbers
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-1
9.2
Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-1
9.2.1 UPS
Environmental.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-1
9.2.2 UPS Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
82
9.2.3 UPS
Output
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
82
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
List of
Figures
Figure 1-1. Eaton 93E XL UPS (10–40
kVA)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Figure 3-1. UPS Cabinet
Dimensions 10/15/20/30 kVA
(Front, Right Side, and Rear Views) . . . . . . .. . . . . . . . . . . . . . . . . .
10
Figure 3-2. UPS Cabinet
Dimensions 40 kV
A
(Front, Right Side, and Rear Views) . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . .
11
Figure 3-3. UPS Cabinet
Dimensions
(Bird and Bottom Views) . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Figure 3-5. UPS Cabinet as
Shipped
on Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . .
20
Figure 4-1.
Removing
the Shipping Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
Figure 4-2. Attaching the Ramp to the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
Figure 4-3. Rolling the Cabinet Down the Ramp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
Figure 4-4.
P
o
w
er
Te rm inal
Locations 10/15/20/3
0 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
Figure 4-5.
P
o
w
er
Te rm inal
Locations
40 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
Figure 4-6.
Interf
ace
Te rm i nal
Locations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
Figure 4-7.
Interf
ace
Terminal Detail
(
T
erminal
Cover R
emo
v
ed)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
Figure 4-8. Building Alarm Terminal Block
Connector
A
ssignments
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
Figure 4-9.
Interface
Wiring
A
ccess
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
Figure 4-10. Pull Chain Terminal Block
Connector
A
ssignments
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
Figure 4-11. Parallel UPS Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
Figure 4-12. Parallel UPS
system connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
Figure 4-13. REPO Terminal Block
Connector
A
ssignments
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
Figure 4-14.
Normally-Open
REPO Switch Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
Figure 4-15. Normally-Closed REPO Switch Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
Figure 5-1. Main
Elements
of the UPS
System
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40
Figure 5-2. Path of Current Through the UPS in
standard
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
Figure 5-3. Path of Current Through the UPS in
Bypass
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
43
Figure 5-4. Path of Current Through the UPS in Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
Figure 5-5. UPS
System
One line (Dual Input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46
Figure 5-6. UPS
System
One line (Single Input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
Figure 6-1. UPS Controls and
Indicators
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
48
Figure 6-2. UPS
Switches.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49
Figure 6-3. UPS Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50
Figure 6-4. Parts of the
LCD
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
52
Figure 6-5. Main Menu and Mimic
Screen
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53
Figure 6-6. Typical Initial
Setup Screen
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
56
Figure 6-7. Typical
System
Control
Screen
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
Figure 7-1. Optional Mini-Slot Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
Figure 8-1.
Air
Filter Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
79
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
List of
T
ables
Table 3-1. UPS Cabinet
Weights
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Table 3-2. UPS Cabinet
Clearances.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Table 3-3. UPS Cabinet
Clearances
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Table 3-4. Air Conditioning or Ventilation
Requirements
During Full Load
Operation.
. . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Table 3-5. Input
/Output
Ratings and External Wiring
Requirements
for the Eaton 93E XL 10-40
kVA
.. . . . . . . . . . . . . .
14
Table 3-6. UPS External
Power
Cable
Terminations
for the Eaton 93E XL 10-40 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
Table 3-7.
Recommended
Input Circuit Breaker Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
Table 3-8.
Recommended Bypass Circuit Breaker,
and
Output
Circuit Breaker and Bypass Fuse Ratings. . . . . . . . . . . . .
16
Table 3-9.
Recommended
DC input circuit
breaker
rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
Table 4-1. Building Alarm
Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
Table 4-2. Pull Chain
Connections.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
Table 4-3. REPO
Connections.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
Table 4-4.
Normally-Open
REPO Wire
Terminations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
Table 4-5. Normally-Closed REPO Wire
Terminations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
Table 6-1.
Status Indicators
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50
Table 6-2. Display Function Menu Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53
Table 6-3. Display Menu
Operation.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54
Table 6-4.
Command
Menu
Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
Table 6-5. Typical
System Status Messages
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
Table 9-1. UPS Model
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
81
Table 9-2.
UPS Operating Environment
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .
81
Table 9-3.
UPS Input Rating
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . ..
82
Table 9-4.
UPS Output Rating
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . .. . .
82
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
Chapter
1 Introduction
The Eaton 93E XL 10-40
kVA
uninterruptible power
supply (UPS) is a true online,
transf
ormer-
free,
double-
conversion, solid-state, three-phase system,
providing
conditioned
and
uninterruptible
AC
po
w
er
to
protect
the
customer's
load from
power f
ailures. With selectable internal batteries setup configuration of 1-6
strings, each strings with 36 blocks of 9AH batteries.
The Eaton 93E XL 10-40
kVA
online
power protection system
is
used
to
prevent
loss of valuable
electronic
information, minimise equipment downtime,
and
minimise
the
adverse effect
on
production equipment
due
to
unexpected power problems.
The Eaton 93E XL 10-40
kVA
UPS continually
monitors
incoming electrical
power
and
removes
the
surges,
spik
es,
sags,
and other irregularities that are
inherent
in
commercial
utility
power.
Working with a
building's
electrical
system,
the UPS
system supplies
clean,
consistent power
that
sensitive electronic equipment
requires f
or
reliable
operation.
During
brownouts, blackouts,
and other
power interruptions, batteries
provide
emergency
power
to
safeguard operation.
The UPS is
housed
in a single
free-standing cabinet,
with
safety shields
behind the door for
hazardous v
olt
age
protection.
This
manual
is for 93E XL series UPS, refer to Table 9-1 for
product
models.
NOTE1:
Startup
and
operational checks
for parallel
systems
or
installations
with
accessor
y
cabinets must
be
performed
by an
authorised
Eaton
Customer
Service
Engineer,
or
the
warranty terms
may
become
void. This
service
is
offered
as part of the
sales contract f
or
the UPS.
Contact
an Eaton
service representative
in
advance
(usually a
two-week notice
is required) to
reserve
a
preferred startup
date.
Figure 1-1 Eaton 93E XL UPS (10-40 kVA)
1
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
sy
stem.
This load sharing
system provides
more capacity than a single UPS, and can provide
bac
kup
.
1.1
UPS Standard
Features
The UPS has many
standard features
that provide
cost-effective
and
consistently
reliable
power protection.
The
descriptions
in this
section
provide a brief
overview
of the UPS
standard f
eat
ures.
1.1.1
Installation
Features
Power
wiring can be
routed
to the rear of the
cabinet
with
connections made
to
accessible
terminals.
1.1.2
Control
Panel
The control panel,
located
on the front of the UPS,
contains
a liquid crystal display
(LCD)
and
pushbut
ton
switches
to control the
operation
of the UPS and to display the
status
of the UPS
system.
See
Chapter 6,
“UPS
Operating Instructions,
for additional inf
ormation.
1.1.3
Customer
Interface
Building Alarm Monitoring Up to
three
inputs in the UPS are available to
connect
the facility's
alarm
system contacts. Some system configurations
may limit the
number
of inputs available. The UPS
uses
these
inputs to monitor the building alarms in addition to the UPS
status.
See
Chapter 7,
“Communication,
for additional inf
ormation.
Mini-Slot
Communication Bays –
UPS equipped with two communication bays as
standard.
One of the two
communication bays slotted with a RS232 card as factory default. Min
i-Slot cards can be e a s i l y
installed at the
front (behind door) of the UPS and are
hot-pluggable.
See
Chapter
7,
“Communication,” f
or
additional
inf
ormation.
1.1.4
High-Efficiency
Mode
The 93E XL
Series
UPS offers a High-Efficiency
(HE)
normal
mode
with
double-conversion
on
demand
that
allo
ws
the UPS to
operate
in
standby bypass
mode.
This
mode
allows the 93E XL UPS to
achieve
98%
efficiency
while
still
protecting
the load. See
Chapter
6, “UPS
Operating Instructions,
for additional
information.
On
setting
the
UPS to work in High Efficiency
mode.
1.1.5
Advanced Battery
Management
A
three-stage
charging
system increases battery service
life by optimizing
recharge
time, and
protects
batteries
from
damage
due to high
current
charging and inverter ripple
currents.
Charging at high
currents can
overheat
and
damage
bat
teries.
1.1.6
Maintenance
Bypass
The internal
Maintenance Bypass
93 XL UPS
consists
of input,
output
and
bypass
input (Dual f
eeds)
switches used
to control the AC input to the UPS the inverter
output,
and a
Maintenance Bypass switch
used
to partially isolate the UPS so that a limited
number
of
components
can be
serviced without interrupting
po
w
er
to critical
sy
stems.
1.1.7 Dual input
93E XL series with dual feed input, with separate rectifier input and bypass input terminals.
1.2
Options and
Accessories
Contact
an Eaton
sales representative
for
information
about the following
options.
1.2.1
External Battery
Cabinet
Battery backup
protection
is provide by
equipping
the UPS
system
with up to four External Battery
Cabinets
(EBCs)
containing sealed
lead-acid,
maintenance-free batteries.
The EBCs are
housed
in single,
free-st
anding
cabinets designed
for
line-up-and-match
installation, but may be installed
separate
from the UPS
cabinet.
1.2.2
Parallel
System
A parallel UPS
system
with up to four UPSs can be installed to provide a parallel capacity and/or
redundant
2
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
depending
on the load and
configuration.
In addition,
when
one UPS is taken out of
service
for
maintenance or
is not
operating
properly, a
redundant
UPS
continues
to supply
uninterrupted power
to the critical load. A
Controller Area
Network
(CAN)
Bridge
provides connectivity
for
system metering
and
operational
mode
control.
1.2.3
Monitoring and
Communication
Mini-Slot Cards – Optional Mini-Slot cards
support several protocols,
such as WEB/SNMP,
RELAY
/ RS232
and
Modbus.
See
Chapter
7,
“Communication,
for additional
information
on
monitoring
and
communication
f
eat
ures.
1.3
Battery
System
The internal
battery system (Number of batteries depends on UPS model)
pro
vides
emergency short-term
backup
power
to
safeguard operation
during
brownouts, blackouts,
and other
po
w
er
inter
r
uptions.
The
battery
system
is
equipped
with lead-acid
bat
teries.
1.4 Basic
System
Configurations
The following basic UPS
system configurations
are
possible
(
model
dependent
)
:
Single UPS (internal
bat
ter
y selectable from 0-6 strings, each strings consists of 36 blocks of 9AH batteries).
The UPS
system configuration
can be
enhanced
by adding optional
accessories
such as
a
Remote Emergency Power-off
(REPO) control or Mini-Slot
communication
cards.
1.5
Using This
Manual
This manual
describes
how to install and
operate
the Eaton 93E XL 10-40
kVA.
Read and
understand
the
procedures described
in this manual to
ensure trouble-free
installation and
operation.
In particular,
be
thoroughly
familiar with the REPO
procedure
(see
paragraph
6.3.1
3).
The
information
in this manual is divided into
sections
and
c
hapters.
The
system, options,
and
accessories
being installed
dictate
which parts of this manual should be read. At a
minimum, Chapters
1
through 4
and
Chapter
6 should be
e
xamined.
Read
through
each
procedure before beginning
the
procedure. Perform
only
those procedures
that apply
to
the UPS
system
being installed or
operated.
1.6
Conventions Used in This
Manual
This manual
uses these
type
con
v
entions:
Bold type highlights
important concepts
in
discussions,
key
terms
in
procedures,
and
menu options, or
represents
a
command
or option that you type or
enter
at a
prompt.
Italic type highlights
notes
and new
terms where
they are
defined.
Screen
type
represents
information
that
appears
on the
screen
or LCD.
Icon
Description
Note
Information notes call attention to important features or
instructions.
[Keys]
Brackets are used when referring to
a
specific key, such
as
[Enter] and or [Ctrl].
In this manual,
the term UPS
refers
only to the UPS
cabinet
and its internal
elements.
The term UPS
sy
stem
refers
to the entire
power protection system
– the UPS
cabinet,
an
external battery system,
and
options or
accessories
inst
alled.
3
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
1.7
Symbols, Controls, and
Indicators
The following are
examples
of
symbols used
on the UPS or
accessories
to alert you to
important inf
ormation:
RISK OF
ELECTRIC
SHOCK
-
Observe
the warning
associated
with the risk of
electric
shock
symbol.
CAUTION:
REFER TO
O
P
ER
A
T
O
R
'
S
MANUAL
-
Refer to your
operator's
m
a
nu
a
l f
o
r
additional
information,
such as
important operating
and
maintenance
instr
uctions.
This symbol
indicates
that you should not discard the UPS or the UPS
batteries
in
the
trash.
This
product contains sealed,
lead-acid
batteries
and
must
be
disposed of
properly. For more
information, contact
your local
recycling/reuse
or
hazardous
w
aste
center.
T
h
i
s s
y
m
bo
l i
nd
i
ca
t
e
s
that you
s
hou
l
d
not
d
i
s
ca
r
d
waste
e
l
e
c
t
r
i
ca
l
or
e
l
e
c
t
r
on
i
c
equipment
(WEEE) in the
trash.
For proper
disposal, contact
your local
recy
cling/reuse
or
hazardous
waste center.
1.8
For More
Information
Refer to the External Battery Cabinet Installation Manual for the following additional inf
ormation:
Installation
instructions,
including site
preparation,
planning for installation, wiring and
safety inf
ormation,
and
detailed illustrations
of
cabinets
with
dimensional
and
connection
point
dra
wings
Visit
www.eaton.com/powerquality
or
contact
an Eaton
service representative
for
information
on how
to
obtain
copies
of
these manuals.
1.9
Getting
Help
If help is
needed
with any of the follo
wing:
Scheduling
initial
st
artup
Regional
locations
and
telephone numbers
A
question
about any of the
information
in this
manual
A
question
this manual
does
not
answ
er
Please
call your local
service
represent
ativ
e.
4
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
Chapter
2
Safety
Warnings
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE
INSTRUCTIONS
This manual
contains important instructions
that should be followed during installation
and
maintenance
of the UPS and
batteries.
Read all
instructions before operating
the
equipment and
save
this manual for future
ref
erence.
The UPS is
designed
for industrial or
computer
room
applications,
and
contains safety shields
behind
the door and front
panels. However,
the UPS is a
sophisticated power system
and should
be
handled
with
appropriate
care.
DANGER
This UPS
contains
LETHAL VOLTAGES. All
repairs and
service
should be
performed b
y
AUTHORISED
SERVICE
PERSONNEL
ON
L
Y
.
There are NO USER
SERVICEABLE
PARTS inside
the
UPS
.
W
ARNING
The UPS is
suitable
for
mounting
on
concrete
or other
non-combustible surfaces
only
.
The UPS is
powered
by its own
energy source
(bat
teries).
The
output terminals
may carry live
voltage even
when
the UPS is
disconnected
from an AC
source.
To
reduce
the risk of fire or electric shock, install this UPS in a
temperature
and
humidity
controlled,
indoor
environment,
free of
conductive contaminants.
Ambient
temperature must not exceed
25°C
(104°F). Do not
operate
near
water
or
excessive
humidity (95%
maximum).
T
he system
is not
intended
for
outdoor
use.
As
a result of the
connected
loads high
leakage current
is
possible. Connection
to earth ground
is
required
for
safety
and proper
product operation.
Do not check UPS
operation
by any action
that
includes
removal of the earth (ground)
connection
with loads
at
t
ac
hed.
Ensure
all
power
is
disconnected before performing
installation or
ser
vice.
Batteries
can
present
a risk of electrical shock or burn from high
short-circuits cur
rent.
T
he
following
precautions
should be
observed:
1)
Remove watches,
rings, or other metal
objects;
2) Use tools with
insulated handles;
3) Do not lay tools or metal parts on top of
batteries; 4)
W
ear
rubber
gloves
and
boots.
ELECTRIC ENERGY HAZARD.
Do not
attempt
to alter any UPS or
battery
wiring or
connectors.
Attempting
to alter wiring can
cause injury
.
Do not open or
mutilate batteries. Released electrolyte
is harmful to the skin and
eyes.
It may
be
to
xic.
The UPS unit is not
suitable
for
IT
or
corner-earthed power distribution
sy
stems.
CAUTION
Installation or servicing should be
performed
by qualified
service personnel knowledgeable of
UPS
and
battery systems,
and
required precautions.
Keep
unauthorized personnel
away
from
equipment.
Consider
all
warnings, cautions,
and
notes before
installing or servicing
equipment.
DO NOT
DISCONNECT the
batteries
while the UPS is in Battery
mode.
See installation
instructions before connecting
to the
supply
.
Risk of
explosion
if
battery
is
replaced
by an
incorrect
type.
Dispose
of
used batteries according
to
the
instr
uctions.
Replace
batteries
with the
same number
and type of
batteries
as originally installed with
the
UPS
.
Disconnect
the charging
source
prior to
connecting
or
disconnecting terminals.
Determine
if the
battery
is
inadvertently grounded.
If it is,
remove
the
source
of the
ground.
Contacting
any part of a
grounded battery
can
cause
a risk of electric shock. An electric shock
is
less
2-1
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
likely if you
disconnect
the
grounding connection before
you work on the
bat
teries.
Proper
disposal
of
batteries
is
required.
Refer to local
codes
for
disposal
requirements.
Do not
dispose
of
batteries
in a fire.
Batteries
may
explode when exposed
to
flame.
Keep the UPS door
closed
and front
panels
installed to
ensure
proper cooling airflow and
to
protect
personnel
from
dangerous voltages
inside the
unit.
Do not install or
operate
the UPS
system
close to gas or electric heat
sources.
The
operating environment
should be
maintained
within the
parameters stated
in this
manual.
Keep
surroundings uncluttered,
clean, and free from
excess
moisture.
Observe
all DANGER,
CAUTION,
and WARNING
notices
affixed to the inside and
outside
of
the
equipment.
2-1
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
Chapter
3
UPS Installation Plan and
Unpacking
Use
the following
basic sequence
of
steps
to install the
UPS:
1.
Create
an installation plan for the UPS
system
(Chapter
3).
2.
Prepare
your site for the UPS
system
(Chapter
3).
3.
Inspect
and unpack the UPS
cabinet
(Chapter
3).
4. Unload and install the UPS
cabinet,
and wire the
system
(Chapter
4).
5. Inspect internal battery string, ensure internal breaker at open state, connect battery positive and negative
connections
6. Install
features, accessories,
or
options,
as applicable (Chapter
4).
7.
Complete
the Installation Checklist (Chapter
4).
8
..
Have
authorized service personnel perform
preliminary
operational checks
and start up the
sy
stem.
NOTE
Startup
and
operational checks
for parallel
systems
or
installations
with
accessor
y
cabinets must
be
performed
by an
authorized
Eaton
Customer
Service
Engineer,
or
the
warranty terms
may
become
void. This
service
is
offered
as part of the
sales contract f
or
the UPS.
Contact
an Eaton
service representative
in
advance
(usually a
two-week notice
is required) to
reserve
a
preferred startup
date.
CAUTION
It
must
be
ensured
that no line input
source
can
accidentally
be
connected
to the UPS
during
inst
allation.
WARNING
Installation may only be carried out by qualified
technicians
and in
conformity
with
the
applicable
safety
st
andards.
The UPS unit is not
suitable
for
IT
or
corner-earthed power distribution
sy
stems.
3.1
Creating an Installation
Plan
Before installing the UPS
system,
read and
understand
how this manual applies to the
system
being
inst
alled.
Use the
procedures
and
illustrations
in
paragraph
3.2 and
Chapter
4 to
create
a
logical plan for installing
the
sy
stem.
3.2
Preparing the
Site
For the UPS
system
to
operate
at peak efficiency, the installation site should
meet
the
en
vironment
al
parameters
outlined in this manual. If the UPS is to be
operated
at an altitude
higher than
1000m
(3300f
t),
contact
an Eaton
service representative
for
important information
about high altitude
operation.
The
operating environment must meet
the
weight, clearance,
and
environmental requirements specified.
3.2.1
Environmental and Installation
Considerations
The UPS
system
installation
must meet
the following
guidelines:
The
system must
be installed on a level floor
suitable
for
computer
or
electronic
equipment.
The
system must
be installed
on clean, dust-free, stable
concrete, non-corrosive,
non-combustible
3-1
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
UPS
Installation Plan and Unpacking
surfaces
only
.
The
UPS operating temperature at ambient 0-40°C
.
The
battery operating temperature at ambient 20-25°C
.
Relative humidity at 95%, non-condensing
The
system must
be installed in a
temperature
and humidity
controlled
indoor area free
of
conductiv
e
contaminants.
The
system If the UPS is to operate at altitude higher than 1000m (3300ft),
contact an Eaton service representative for further important information on
operating on higher altitude.
Failure to follow
guidelines
may void your
w
ar
rant
y
.
The UPS
equipment operating environment must meet
the
weight requirements shown in
Table 3-1 and
the
size
requirements shown
in Figure 3-1
through
Figure 3-5.
Dimensions
are in
millimetres (inc
hes).
T
able
3-1. UPS Cabinet
Weights
Model
Weight (
kg
)
Net Weight
Gross Weight
Descriptions
93E XL-10I-9Ah-MBS
770
859
93E XL-15I-9Ah-MBS
770
859
93E XL-20I-9Ah-MBS
770
859
93E XL-30I-9Ah-MBS
780
869
93E XL-40I-9Ah-MBS
790
879
I- Internal battery
MBS-with internal
MBS
The UPS
cabinet uses
forced air cooling to
regulate
internal
component temperature.
Air
inlets are in the
front
of the
cabinet
and
outlets
are in the back of the
cabinet.
Allow
clearance
in front of and in back of the
cabinet
for proper air
circulation. The
clearances required
around the UPS
cabinet
are
shown in
Table
3-2 and Table 3-3
T
able
3-2. UPS Cabinet
Clearances
From Top of
Cabinet
At least 300 mm (12") working
space
From Front of
Cabinet
At least 900 mm (36") working
space
From
Back of
Cabinet
At least 600 mm (36") working
space
From Right
Side
of
Cabinet
See Table No:
3-3
From Left
Side
of
Cabinet
See Table No:
3-3
8
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
UPS
Installation Plan and Unpacking
T
able
3-3. 93E XL Required
Clearances
93E XL
Required Clearance
for paralleled
adjacent
UPS or UPS and
adjacent PDU
Ambient L1(mm) L2(mm)
25
o
C
30
o
C
35
o
C
40
o
C
Notes:
600 50
L1-
clearance
to the rear
w
all.
L2-
clearance between
the
adjacent
paralleled UPS or UPS and
adjacent
PDU. Parallel UPS should be
as
close
as
possible.
Some models
that
feature
rear
connections
also require additional rear
clearance
to
enable
installation
and
connection.
CAUTION
If
battery systems
are
located
in the
same
room as the UPS, the
battery manuf
act
urer's
environmental requirements
should be followed if they are more
stringent
than the
UPS
requirements. Operating
temperatures
above the
recommended
range will result in
decreased
battery
life and
performance,
and may
reduce
or void the
battery
w
ar
rant
y
.
The UPS ventilation
requirements
are
shown in
Table
3-4.
T
able
3-4. Air
Conditioning or
V
entilation
Requirements During Full Load
Operation
Model Power Rating
Input
/
Output
V
oltage
Heat Dissipation (KC/H)
93E XL-10I-9AH-MBS
10 kVA
380/380 400/400
415/415 523
93E XL-10I-9AH-MBS
15 kVA
380/380 400/400
415/415 862
93E XL-10I-9AH-MBS
20 kVA
380/380 400/400
415/415 1149
93E XL-10I-9AH-MBS
30 kVA
380/380 400/400
415/415 1723
93E XL-10I-9AH-MBS
40 kVA
380/380 400/400
415/415 2298
9
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
UPS
Installation Plan and Unpacking
Front View
Right Side View Rear View
Figure
3-1.
UPS Cabinet Dimensions
10/15/20/30kVA (Front, Right
Side and Rear Views)
Dimension are in millimeters [inches]
10
Eaton 93E XL UPS (10-40kVA, 380/400/415V) Installation and Operation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

Eaton 93E XL Operating instructions

Category
Uninterruptible power supplies (UPSs)
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI