5.2. Cannot read or write configuration
1, Ensure the normal operating status of the network (whether the ACT light and RUN light are normal)
2, Ensure that the serial server device and the connected host are in the same network segment, and whether the IP can
ping through
3, Ensure that the serial server is in application mode
4, if the above can not solve the problem try to power off and restart, if necessary, restore factory settings
5.3. Cannot send and receive data
1, Ensure that the serial port can be opened normally
2, Observe whether the system light is flashing fast or slow, flashing fast for the data sent and received, such as no flashing
fast check the connection between the serial port and the upper network, and the bottom serial device to check the wiring
5.4. Forget the previous configuration information
1. Determine the configuration information by reading the configuration, if the ip address is not remembered, then you can
search for
5.5. Transmitting and receiving data is messy code
1, Check if the wiring is correct,our 485 wiring is 1A+,2B-.
2, Check if the line distance has exceeded the standard distance and the quality of the line (also by lengthening the line
transceiver or optical isolation)
3, Check whether the baud rate set matches the bottom device
4, Separate from the client's top software, use the network or serial debugging assistant can receive normal data, if you can
receive normal data, may not be compatible with the top software
If none of the above ways can solve your problem, please contact the manufacturer