EIM TEC2 Electric Actuator with
Model 500 Quick-Start Guide
(Model 500 Discontinued)
Welcome to TEC2
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
1Welcome to TEC2
Welcome to TEC2
The TEC2 actuator’s Local Display Module (LDM) and Remote Display Module (RDM) provide easy-to-read
actuator information.
The screen graphics will display the mode of operation, valve status, position, torque, and alarm symbols.
The message center will display actuator setup options, data entry feedback, and alarm messages.
Once you follow the simple steps outlined in this guide, the actuator will be ready for normal operation.
The bar graph, position digits, icons, and LEDs will indicate the valve status.
LED Indicators
Valve Torque
Display Diagnostic
Operating
Mode
Moving Status
Welcome to TEC2
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
2 Welcome to TEC2
Factory Settings
The actuator has been congured as specied in the order. No further changes should be necessary other than
setting the position limits, and, if network controlled, setting a unique network address. If full data was not
provided when ordering or if changes are needed, see the TEC2 Installation & Operation Manual
(E2K-420-0117), which can be found at www.emerson/eim.
Power Actuator
Verify the voltage rating on the unit nameplate. Connect power to the unit.
Are Position Limits Set?
Does “SET LIMITS BEFORE OPERATING,” “EE%, and the alarm icon appear, and is the yellow LED
blinking? If so, then position limits have not been set.
Setting Valve Position Limits Initially
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
3Setting Valve Position Limits Initially
Setting Valve Position Limits Initially
2 3 4
YES
LOCAL
YES,
NO,
YES,
NO
Release
quickly.
1
STOP
Place the selector knob in the STOP position. Then toggle the control knob in rapid succession to YES, then
NO, then YES, then NO and release. The Setup icon will be displayed on the display module and SETUP?” will
be displayed on the message center. Rotate the control knob to “YES.The message center will display “SET
LIMITS BEFORE OPERATING. Set position limits as described on the next pages.
Setting Position Limits for Electrical Operation
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
4 Setting Position Limits for Electrical Operation
Setting Position Limits for Electrical Operation
STEP 1: CLOSED Valve Position
2
3
4
YES
LOCAL
CLOSE
Hold until
desired
position is
reached.
1
STOP
Turn the selector knob to the “LOCAL” position. Hold the control knob in the “CLOSE” position until desired
position is reached. Dis-engage motor drive by setting the declutch lever in “HAND” mode.
Using handwheel, move the valve in the open direction for one handwheel turn to allow for motor coasting.
Re-engage motor drive by setting the declutch lever out of “HAND” mode.
Return the selector knob to the “STOP” position. Select “YES” to set new close limit.
Setting Position Limits for Electrical Operation
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
5Setting Position Limits for Electrical Operation
Setting Position Limits for Electrical Operation
STEP 2: OPEN Valve Position
Turn the selector knob to the “LOCAL” position. Hold the control knob in the “OPEN” position until
desired position is reached. Dis-engage motor drive by setting the declutch lever in “HAND” mode. Using
handwheel, move the valve in the close direction for one handwheel turn to allow for motor coasting. Re-
engage motor drive by setting the declutch lever out of “HAND” mode.
Return the selector knob to the “STOP” position. Select “YES” to set new open limit.
2
3
4
YES
LOCAL
OPEN
Hold until
desired
position is
reached.
1
STOP
Setting Position Limits for Manual Operation
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
6 Setting Position Limits for Manual Operation
Setting Position Limits for Manual Operation
STEP 1: CLOSED Valve Position
Turn the selector knob to the LOCAL position. At the CLOSE VALVE THEN SELECT STOP” prompt, depress the
declutch lever while rotating the handwheel until the clutch is fully engaged. Release the lever.
When the valve is fully closed. Return the selector knob to the STOP position.
At the ACCEPT CLOSE LIMIT” prompt, select “YES.
Advance to the “SAVE CHANGES?” prompt and answer YES to save the changes.
2 3 4
YES
LOCAL
1
STOP
5
Depress
declutch,
rotate
handwheel
until...
declutch is fully
engaged.
Release
declutch,
Setting Position Limits for Manual Operation
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
7Setting Position Limits for Manual Operation
Setting Position Limits for Manual Operation
STEP 2: OPEN Valve Position
Turn the selector knob to the LOCAL position. At the OPEN VALVE THEN SELECT STOP” prompt, depress the
declutch lever while rotating the handwheel until the clutch is fully engaged. Release the lever.
When the valve is fully opened. Return the selector knob to the STOP position.
At the “SAVE LIMITS” prompt, select “YES.
Advance to the “SAVE CHANGES?” prompt and answer YES to save the changes.
2 3 4
YES
LOCAL
1
STOP
5
Depress
declutch,
rotate
handwheel
until...
declutch is fully
engaged.
Release
declutch,
Check the Open/Closed Settings
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
8 Check the Open/Closed Settings
Check the Open/Closed Settings
Valve Closed
As you operate the valve in the close direction, verify
that the green LED is blinking. When fully closed is
reached, verify that the green LED stays ON and 0%
is displayed.
1
When turning to close,
green LED blinks.
2
When fully closed,
green LED remains lit.
Valve Open
As you operate the valve in the open direction, verify
that the red LED is blinking. When fully open is
reached, verify that the red LED stays ON and 100%
is displayed.
1
When turning to
open, red LED blinks.
2
When fully open,
red LED remains lit.
Note
It is also congurable to have a red LED for
Valve Closed.
Note
It is also congurable to have a green LED for
Valve Open.
Changing the Valve Settings
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
9Changing the Valve Settings
Changing the Valve Settings
Turn the selector knob to the STOP position then toggle the control knob in rapid succession to YES, then NO,
then YES, then NO and release. The setup icon will be displayed on the display module and “SETUP?“ will be
displayed on the message center. Rotate the control knob to YES. The message center will display “CHANGE
DISPLAY SETTINGS”.
2 3
YES
YES,
NO,
YES,
NO
Release
quickly.
1
STOP
Network Controlled
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
10 Network Controlled
Changing the Valve Settings
Answer NO to the Setup prompts until “CHANGE SETTINGS?” appears. Answer YES. ACCEPT PASSCODE
CHARACTER 1?X” appears. The factory default passcode is 000. Do not change the password without
recording the new password.
4 5
YES
NO
Until
appears.
Network Controlled
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
11Network Controlled
Changing the Valve Settings
Enter Passcode
Use the control knob and answer YES if the passcode character is correct. If not, use NO to advance
incrementally to the correct character. Repeat this process until three passcode characters are entered.
6
7
YES
NO
If passcode
character is
correct...
...to advance
to correct
character.
OR
Changing the Valve Settings
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
12 Changing the Valve Settings
Changing the Valve Settings
Setting Limits
Advance to the “SET VALVE TRAVEL LIMITS” prompt and answer YES. Proceed to set limits.
8
9
YES
NO
Network Controlled
September 2018
Quick-Start Guide
E2K-210-05-18 Rev. 3
13Network Controlled
Network Controlled
(CAM and Controlinc
®
option required)
In the “SETUP” mode advance to “NETWORK SETUP?” using the selector knob in the REMOTE position.
Answer YES. Hold the control knob in the NO position until the correct address appears. Answer YES. Unit
is now network controlled. If other conguration changes are needed, please see the TEC2 Installation &
Operation Manual (E2K-420-0117), which can be found at www.emerson/eim.
2 3
4
YES
NO
Until...
1
REMOTE
5
NO
Until
correct
address...
YES
Saving the Changes
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
14 Saving the Changes
Saving the Changes
Advance to the “SAVE CHANGES?” prompt and answer YES to save the changes.
1
2
YES
NO
C
HANGES
?
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at
info.actuationtechnologie[email protected]
World Area Confi guration Centers (WACC) offer sales support, service,
inventory and commissioning to our global customers.
Choose the WACC or sales offi ce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway
Houston TX 77065
USA
T +1 281 477 4100
Av. Hollingsworth
325 Iporanga Sorocaba
SP 18087-105
Brazil
T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road
#01-02 Singapore 629361
T +65 6777 8211
No. 1 Lai Yuan Road
Wuqing Development Area
Tianjin 301700
P. R. China
T +86 22 8212 3300
MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone
Dubai
T +971 4 811 8100
P. O. Box 10305
Jubail 31961
Saudi Arabia
T +966 3 340 8650
24 Angus Crescent
Longmeadow Business Estate East
P.O. Box 6908 Greenstone
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
www.emerson.com/eim
©2018 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
EIM
TM
is a mark of one of the Emerson family of companies.
All other marks are property of their respective owners.
The contents of this publication are presented for information purposes
only, and while every effort has been made to ensure their accuracy,
they are not to be construed as warranties or guarantees, express or
implied, regarding the products or services described herein or their use
or applicability. All sales are governed by our terms and conditions, which
are available on request. We reserve the right to modify or improve the
designs or specifications of our products at any time without notice.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

EIM TEC2 User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI