1
1. Make sure to disconnect CF-MC Master Con-
troller from mains supply.
2. Remove red tabs from the actuators (only for
NC types).
3. Connect cables from actuators to CF-MC
Master Controller.
4. When all actuators are connected, connect
CF-MC Master Controller to mains supply.
5. Remove protection strip from batteries in
CF-R room thermostats.
6. Press
^
-button untill the Install LED flashes.
x1
x1 (= ch2)
x2 (= ch3)
x3 (= ch4)
ch1
ch2 ch4
ch3
7. Press OK button untill the Install LED is con-
tinuously on.
8. Press center button of CF-R room thermostat
once.
9. Select room thermostat with the > button.
21.0
°c
ch4
x 1
21.0
°c
x 5
21.0
°c
10. Press OK button to add the room thermo-
stat to CF-MC. Repeat steps 6 to 10 for each
device you wish to add.
11. To test the link connection, press center
button of the room thermostat once.
12a. LED flashes once: Link is established.
12b. LED flashes 5 times: Link has failed.
x 5
21.0
°c
x 1
21.0
°c
1.5 m
13. If link has failed: Find another place for the
thermostat and repeat step 11.
14. If link is established: Mount the thermo-
stat, see step 15.
15. Mounting height for a room thermostat
should be approx. 150 cm. Do not install a
room thermostat, where it will be subject
to direct sunlight.