Danfoss Termix Distribution Unit Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss Termix Distribution Unit Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
InstallationGuide
TermixDistributionunit
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Start-up..............................................................7
4.3Electricalconnections.............................................8
5.0Wiring.............................................................9
5.1Wiringdescription.................................................9
5.2Wiringdiagram.....................................................9
6.0Design.............................................................10
6.1Design...............................................................10
6.2Schematicdiagram................................................11
7.0Controls..........................................................12
7.1Maintenance........................................................12
8.0Troubleshooting..............................................13
8.1Troubleshootingingeneral......................................13
8.2TroubleshootingDHW............................................13
8.3Disposal.............................................................14
9.0Danfossinstallationsguide...............................15
9.1Danfossinstallationsguide......................................15
10.0Declaration......................................................19
10.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
1
InstallationGuideTermixDistributionunit
2
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
2.0Functionaldescription
TermixDistributionunit
Manifoldsystemforoorheating
TheTermixdistributionunitcanbedirectlyconnectedtothe
TermixVMTD,VMTDmixer,VXandVVXunits.Theunitissupplied
withmeterttingpiecefordomesticwater,safetysetorCombiluk
asrequired.
TheTermixdistributionunitforconnectionofwaterandheating
pipesinconnectionwithhiddenpipeinstallationsallowsforalarge
numberofconnectionsforcoldwater,hotwater,radiatorsandoor
heatingwithindimensionsof530x565x380mm(hxwxd).The
compactsolutionensuresthateventhoughallconnectionsarein
usetheunitstilltsintoa60cmcupboard.TheTermixdistribution
unitcanbemountedwithaspearinthegroundintheearlystages
ofbuilding.Whenthebuildingisnishedandprotectedagainst
thefttheTermixdistrictheatingunitcanbemounted.
Thereliabilityisveryhigh.Thewirelesscontrolscomplywiththe
newestEUstandards(868MHz)forelectronicequipment.Atthis
frequencytheriskofsignaldisturbancesfromotherelectronic
householdappliancesisverylow.
ThecontrolsfortheTermixdistributionunitincludeaprogram
forexerciseofvalvesandpumpandapumpstoptoprotectthe
circulationpump.
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
3
InstallationGuideTermixDistributionunit
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
Floorheatingowline(FHFL)
Floorheatingreturnline(FHRL)
Connectionsizes:
FHFL+FHRL:
G¾”(int.thread)
Dimensions(mm):
H710xW505xD175
Weight(approx.):20kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
5
InstallationGuideTermixDistributionunit
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
6
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
4.2Start-up
Start-up,Heatingwithmixingloop
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Ifthesystemoperatesinaccordancewithdesign,itcanbeput
toregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
7
InstallationGuideTermixDistributionunit
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
4.3.1Thermoactuators
Activatingthethermoactuators
Thethermoactuatorsaresuppliedwitha“rstopenfunction,such
thattheyareslightlyopenforfrostprotectionuntiltheelectrical
controllerisinstalled.Duringcommissioning,the“rstopen
functionisdisabledbyremovingtheredmountingsplitonthe
thermoactuator.
Pleasecheckthatthethermoactuatorscanfullyclosefollowing
disablementofthe“-rstopenfunction.
Seetheinstallationguideincludedwiththethermoactuator.
8
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
5.0Wiring
5.1Wiringdescription
Connectingthesystemscirculationpump
Thesystemscirculationpumpshouldbeconnectedtothe
contactrelayintheelectricaloorheatingcontroller,sothe
pumpcanautomaticallystartandstop,dependingonwhether
thethermoactuatorsareopenorclosed.Ifthepumppushes
againstclosedvalvesitcanoverheatandburnout.Theelectric
oorheatingcontrollerisnotapprovedtosupplypowertothe
circulationpump.
Thepumpmustthereforebesuppliedfromanexternalconnection
box,suchthatonlythe230Vphase(active)isfedthroughtherelay
contactontheelectricaloorheatingcontroller.
Theneutralandearthconnectionsmustnotentertheoorheating
controller.
5.2Wiringdiagram
Junctionbox
230VACconnector
plugwithEarth
DanfossCF-MC
MasterController
230VACpower
supply230Vplug
iscutoff!
Safetythermostat
PumpRelayin
DanfossCF-MC
MasterController
Circulatorpump
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
9
InstallationGuideTermixDistributionunit
6.0Design
6.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
J
Electroniccontrolleroorheating
35
Ballvalve/non-returnvalve
FHFL
Manifoldsystemforoorheatingowline
M
Electricalwiringbox
48
Airvent,manual
FHRL
Manifoldsystemforoorheatingreturnline
7
Thermostaticcontroller,HE
49
Safetythermostat
10
Circulationpump
55
Thermoactuator
20
Filling/drainvalve
10
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
6.2Schematicdiagram
(A)
(M)
(B)
(C)
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
(A)
Termixunit
J
Electroniccontrolleroorheating
35
Ballvalve/non-returnvalve
(B)
Floorheatingowline
1
Ballvalve
39
Connectionclosed
(C)
Floorheatingreturnline
7
Thermostaticvalve
48
Airvent,manual
(M)
Electricalwiringbox
10
Circulationpump
49
Safetythermostat
20
Filling/drainvalve
55
Thermoactuator
6.2.1Technicalparameters
Technicalparameters
Nominalpressure:PN10(PN16versionsareavailableonenquiry)
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper
Soundlevel:55dB
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
11
InstallationGuideTermixDistributionunit
7.0Controls
7.1Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
12
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
8.0Troubleshooting
8.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
8.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace.
Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout.
Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
13
InstallationGuideTermixDistributionunit
8.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
14
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
9.0Danfossinstallationsguide
9.1Danfossinstallationsguide
Installation-CF2
1. 2. 3.
7. 8.
x1
9.
x1 (= ch2)
x2 (= ch3)
x3 (= ch4)
ch1
ch2 ch4
ch3
10.
21.0
°c
ch4
4. 6.5.
x1
21.0
°c
11.
x
1
21.0
°c
x5
21.0
°c
A
B
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
15
InstallationGuideTermixDistributionunit
Installation-CF2
12.B
x1
21.0
°c
13.B
15.B 16.B
14.B
12.A 13.A 14.A
x1
21.0
°c
x5
21.0
°c
A
B
R
R
Installation-CF2
1. 2. 3.
4.
ch4
5.
x5
x
1
21.0
°c
6.
x1 (= ch2)
x2 (= ch3)
x3 (= ch4)
ch1
ch2 ch4
ch3
R
16
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
17
InstallationGuideTermixDistributionunit
18
DEN-GT
VI.GP .O2.02/LUK40900
DanfossDistrictEnergy
InstallationGuideTermixDistributionunit
10.0Declaration
10.1Declarationofconformity
Declarationofcompliance
We:
GeminaTermixA/S
MemberoftheDanfossGroup
Navervej15-17
DK-7451Sunds
doherebyonourownresponsibilitydeclarethatthefollowingproducts:
TermixSubstations
coveredbythisdeclarationisinconformitywiththefollowingdirective(s),
standard(s)orothernormativedocument(s),
providedthattheproductsareusedinaccordancewithourinstructions.
EUDirectives:
MachineryDirective2006/42/EEC
ENISO14121-1Safetyofmachinery-Riskassessment
EN60204-1Safetyofmachinery-Electricalequipmentofmachines
EMCDirective2004/108/EEC
EN61000-6-22007Electromagneticcompatibility
-Genericstandard:Immunityindustry
EN61000-6-32007Electromagneticcompatibility
-Genericstandard:Emissionforresidential,commercialandlightindustry
PEDDirective97/23/EEC
AllsubstationsthatfallsunderArticle3.3andcategory1shallnotbeCE-marked
accordingtothisdirective,howeverallessentialsafetyrequirementsfromthe
PEDDirective97/23/EECarefollowedtoensurehydraulicsafety
Thisdeclarationisimmediatelyannulled,iftheproductisinterferedwithinanyway,
whichinterfereswiththeabovementioneddirectivesandstandards,
withoutthewrittenconsentfromGeminaTermixA/S.
2010.01.05Sunds
Timeandplace
LarsGinnerup
Responsibleforquality
DanfossDistrictEnergy
VI.GP .O2.02/LUK40900
DEN-GT
19
InstallationGuideTermixDistributionunit