www.ismacontrolli.com
iSMA CONTROLLI S.p.A. - Via Carlo Levi 52, 16010 Sant’Olcese (GE) - Italy |
[email protected]DIM306en | 1st Issue | 07/2022 page 2
1 ingranaggio=10°
1 gear= 10°
Limitatore di rotazione
Adapter limiter
Limiti rotazione
6ANGLE LIMITATIONS
7
LEDs FUNCTIONALITY
WORKING MODE
LEDs STATUS
DESCRIPTION
RED ORANGE GREEN
SUPERCAPS PHASE
CHARGE
ON OFF OFF SUPERCAPs IN CHARGING
ON ON OFF SUPERCAP ALMOST CHARGED
ON ON ON SUPERCAP CHARGED
WORKING MODE
ON OFF 2 BLINKING CLOCKWISE DIRECTION MOVEMENT
ON OFF 3 BLINKING COUNTERCLOCKWISE DIRECTION MOVEMENT
EMERGENCY RETURN
MODE
OFF OFF ON CHARGE SUPERCAPS > 99%
OFF ON OFF CHARGE SUPERCAPS > 66%
ON OFF OFF CHARGE SUPERCAPS > 33%
The combination of IP54 means, that the product is dust protected (No. 5x) and protected against splash
water (No. x4). Guaranteed for front mounting only. Respect the specied monting positions (Box No. 5).
230 Vac: To isolate from the main power supply, the system must incorporate a device which disconnects the phase
conductor with at least a 3 mm contact gap).
Fix limiter
Adapter limiter
1 gear = 10°