Bentone BG 450 M LME22 412 RT User manual

Type
User manual
Providing sustainable energy solutions worldwide
178 077 76-7 CR00461  2023-04-26
Installation- and maintenance instruction
BG 450 M
LME22.233C2
Jumo dTRON 316
MB-VEF 412
Translation of the original instructions.
2Bentone
example Beispielexempel
352011030141
Designation
Type
Model
Serial no.
Motor supply
Main supply
MADE IN SWEDEN BY
LIGHT OIL 35-90kW 1,25-6,0 cSt 7-14bar
BF 1 KS 76-24
BF 1
BF 1 KS 76-24
1234567
1~230V 1,0A 50Hz IP 20
Man.Year 2019
Cap. Min-Max
3
?
1
-sv
1. Manualer på övriga språk
2. www.bentone.com\
nedladdning eller scanna
QR-koden.
3. Skriv in brännarens
artikelnummer som nns på
din typskylt (se bild) och välj
ditt språk.
Detaljerad ecodesign
information kan laddas ner
på: www.bentone.com/
ecodesign.
-en
1. Manuals in other languages
2. www.bentone.com\
download or scan QR-code.
3. Enter the burner`s article
number on your data plate
(see picture) and select
language.
Detailed ecodesign
information can be
downloaded at:
www.bentone.com/
ecodesign.
-da
1. Manualer på andre sprog
2. www.bentone.com\
download eller scan
QR-koden.
3. Indtast brænderens
artikelnummer, der ndes
på typeskiltet (se billede), og
vælg dit sprog.
Detaljerede oplysninger om
ecodesign kan downloades
på: www.bentone.com/
ecodesign.
-fr
1. Manuels dans d’autres
langues
2. www.bentone.com\
download ou scannez le
code QR.
3. Saisir le numéro d’article
du brûleur sur votre plaque
signalétique (consultez
l’illustration) et sélectionnez
la langue.
Des informations détaillées
sur l’écodesign peuvent être
téléchargées à l’adresse:
www.bentone.com/
ecodesign.
-de
1. Gebrauchsanweisungen in
anderen Sprachen
2. www.bentone.com\
download oder scannen Sie
den QR-Code.
3. Geben Sie die
Artikelnummer des Brenners
auf Ihrem Typenschild ein,
(siehe Bild) und wählen Sie
die Sprache aus.
Detaillierte Informationen
zum Ecodesign können unter
www.bentone.com/ecodesign
heruntergeladen werden.
2
3 Bentone
Table of contents
1. General Information ............................................................4
1.1 Delivery inspection........................................................................ 4
1.2 Safety ............................................................................................... 4
1.3 What to do if you smell gas ......................................................... 5
2. Technical data .......................................................................6
2.1 Dimensions BG 450 M ................................................................. 6
2.2 Capacity range ............................................................................... 7
2.3 Gas categories, approved gases ................................................ 7
2.4 Technicalspecication ................................................................. 7
2.5 Workingeld .................................................................................. 7
2.6 Components ................................................................................... 8
2.7 Skeleton diagrams ....................................................................... 9
3. Electric equipment ............................................................. 10
3.1 Safety system .............................................................................. 10
3.2 Wiring diagram ............................................................................ 10
3.3 Function ........................................................................................ 11
3.4 Control program at faults; fault mode indicator LME .... ....12
4. Controller JUMO dTRON 316 .............................................14
4.1 Preface...........................................................................................14
4.2 Scope of delivery ......................................................................... 14
4.3 Mounting ...................................................................................... 14
4.4 Electrical connection .................................................................. 15
4.5 Displays and keys ........................................................................ 16
4.6 Operation ......................................................................................17
4.7 Parameter level „PArA“ .............................................................. 20
4.8 Congurationlevel„ConF“........................................................ 21
4.9 Autotuning .................................................................................... 24
4.10 Alarms ............................................................................................ 24
4.11 Factory settings Controller JUMO ............................................ 25
5. Installation ..........................................................................32
5.1 General instructions ................................................................... 32
5.2 Instructions .................................................................................. 32
5.3 Inspection and maintenance .................................................... 32
5.4 Preparation for assembly ......................................................... 32
5.5 Gas supply .................................................................................... 32
5.6 Electric connection ..................................................................... 32
5.7 Handling and lifting instruction ............................................... 33
6. Mounting ............................................................................34
6.1 Gas nozzle.....................................................................................35
6.2 De-aerating ...................................................................................36
6.3 Leakage control ...........................................................................36
6.4 Calculationofgasow .............................................................. 37
7. Settings ...............................................................................38
7.1 Setting the combustion assembly ........................................... 38
7.2 Startup ........................................................................................... 38
7.3 Control of combustion .............................................................. 38
7.4 Settingtheairpressureswitch ................................................ 39
7.5 Settingthegaspressureswitch,min. ..................................... 40
7.6 Setting Damper motor, Modulating operation .................... 41
8. Gas valve, MultiBloc MB-VEF 407-412 .............................. 42
9. Service .................................................................................45
9.1 Burner Service Schedule, Gas .................................................. 45
9.2 Component replacement intervals ..........................................45
9.3 Combustion device ..................................................................... 46
9.4 Air damper .................................................................................... 47
9.5 Replacement, Damper motor air ............................................. 48
9.6 Fan ................................................................................................. 49
9.7 Vibrations ......................................................................................50
9.8 Controlofamemonitoringandionizationcurrent ........... 51
9.9 Replacement of electrical components .................................. 53
10. Handing over of the installation ......................................54
11. Troubleshooting ................................................................. 55
12. Service- and inspection protocol .....................................57
4Bentone
172 515 01-2  2021-10-05
1. General Information
The burner may only be used for its intended purpose in accordance with the
product’s technical data.
We reserve the right to make design changes and cannot be held liable for any
misprints or typographical errors.
Modifying the design or using accessories or components that have not been
approved by Enertech in writing is strictly prohibited.
This Installation and Maintenance manual:
is to be regarded as part of the burner and must always be kept near
the installation site.
must be read prior to installation.
is intended for use by authorised personnel.
1.1 Delivery inspection
Make sure everything is delivered and the goods have not been
damaged during transit. Transport damage should be reported to the
shipping company.
If something is wrong with a delivery, report it to the supplier.
1.2 Safety
- before installation:
Installation and work on the burner and associated system
components may only be carried out by persons who have undergone
relevant training.
The product is packaged to prevent damage from occurring when
handled – Handle the product with care! Lifting equipment must be
used to lift larger packages.
The products must be transported/stored on a level surface in a dry
environment, max. 80% relative humidity, no condensation.
Temperature -20 to +60 °C.
- installation:
The burner must be installed in accordance with local regulations for
re safety, electrical safety, and fuel distribution.
The premises must comply with local regulations pertaining to use of
the burner and must have adequate air supply.
The installation site must be free of chemicals.
Fire extinguisher with Class BE recommended.
Make sure when installing the burner that there is enough space to
service the burner.
The electrical installation must be professionally carried out in
accordance with current mains electricity regulations and in a
professional manner.
Make sure that the burner is suitable for the application (see Technical
Data).
All components must be installed without being bent, twisted or
subjected to mechanical or thermal forces that affect components.
5 Bentone
Care must be taken by the installer to ensure that no electrical cables
or fuel lines are pinched or otherwise damaged during installation or
service.
Sharp edges can occur on, for example: ame tube, fan wheel and air
damper.
The gas outlet from the pressure regulator must be congured in
accordance with applicable regulations and lead to a safe area.
- before rst start:
The burner must not be put into operation without proper safety and
protection devices.
Permitted ambient temperature during operation -10 to +60 °C. Max.
80% relative humidity, no condensation.
The surface temperature of the burner’s components may exceed
60 °C.
Handle with caution – the burner has moving parts, and there is risk
of crushing injuries.
Seal inspections must be performed during installation and servicing
to prevent leakage.
Fitting and installation work has been completed and approved.
Electrical installation has been correctly performed.
Flue gas ducts and combustion air ducts are not blocked.
All actuators and control and safety devices are in working order and
correctly set.
If the boiler is equipped with an access hatch, this must be equipped
with a hatch opening switch connected to the burner’s safety system.
When in operation, the burner’s noise level can exceed 85 dBA – use
hearing protection!
- operation:
Carry out all stipulated settings, service and inspection work within
the set time.
1.3 What to do if you smell gas
Turn off the fuel supply.
Turn off the device and remove the boiler from operation.
Open windows and doors.
Prevent open ames or sparking, e.g. do not turn lights on or off, do
not use any electrical appliances or mobile phones.
Evacuate the building.
Notify the installer or gas supplier of the problem so that it can be
rectied.
6Bentone
2. Technical data
The burner is intended for:
Operation in installations according to EN 303 and EN 676.
Fuels:
Natural gas H, E, L, LL.
LPG, Butane and Propane.
2.1 Dimensions BG 450 M
172 535 71  2023-02-20
Length of
ame tube
Flame tube
measure A
Flame tube
measure B
Flame tube
measure C
256 226 ø159 ø162
356 326 ø159 ø162
456 426 ø159 ø162
* The above dimensions are max. measurements. Depending on the components used, the measurements may vary.
** Min. recommended distance to oor.
K
L
M
2.1.1 Measurements for connection to the boiler
I
øC
AG
E
D
øB
F
**J
160303-678
H
K L M
14 (Ø 210) Ø 255-290 ø170
D E *F G H *I **J
528 255 330 227 316 500 200
7 Bentone
2.3 Gas categories, approved gases
Only dry gas is permitted for use.
2.2 Capacity range
!Do not exceed working
eld.
2.5 Working eld
2.4 Technical specication
Measurements according to EN 15036-1:2006
Alt.1 The noise level of the burner can be
reduced by equipping the burner with
silencer. Installation must be done so
it does not prevent air supply to the
burner.
Alt.2 The burner’s noise level can be reduced
by connecting the burner’s air intake
to the air duct that opens into an
appropriate location. Installation must
be done so it does not prevent air supply
to the burner.
BG 450 M
Main supply 230V, 1~, 4.6A, 50Hz, IP20
Max fuse rating 10A
NOX-class 3
Noise level 88dBA
-1
0
1
2
3
4
5
6
7
8
9
100 150 200 250 300 350 400 450 500 550 600
mbar
kW
120-550 kW
160303-250
450 / 450i
G20  120 - 550 12.7 58.2 360
G25  120 - 550 14.8 67.7 360
G30  120 - 550 3.7 17.1 360
G31  120 - 550 4.9 22.5 360
    120 - 500 20.0 83.3 360
160303-681-2
Capacity
kW
Gas quantity
at min. power
Nm3/h
Gas quantity
at max. power
Nm3/h
Max.
connection
pressure mbar
Min
connection
pressure mbar
See data plate.
Biogas
Gas quantity and capacity vary according to grade of gas and connection pressure.
Category Country of destination Supply pressure
II2R3R AT, BE, BG, CH, CY, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HR, HU, IE,
IS, IT, LT, LU, LV, MK, MT, NL, NO, PL, PT, RO, RS, SE, SI, SK, TR 20 mbar
II2H3B/P AT, CH, CY, DK, FI, LT, RO, SE, SK 20 mbar
II2H3P GB, IE 20 mbar
II2L3B/P RO 20 mbar
II2E3B/P PL 20 mbar
I2E(R)B BE 20 mbar
I3P BE 20 mbar
II2EK3B/P NL 20 mbar
160302-239-4
8Bentone
2.6 Components
1. Flame tube
2. Brake plate
3. Nozzle
4. Nozzle assembly
5. Fixing ange
6. Transformer
7. Burner control
8. Contactor
9. Connection, gas
10. Cover, inspection glass
11. Electrical connection
12. Fan wheel
13. Motor
14. Reset button
15. Damper motor
16. Switch 0-I
17. Indication lamp, operation
18. Changeover switch, man-auto
19. Changeover switch, increase-
decrease
20. Air pressure switch
21. Ball valve
22. Air damper
23. Gas pressure switch, min
24. Air intake
25. Gas valve (MultiBloc)
26. Impulse line PL
27. Impulse line PF
28. Ignition electrode
29. Ionization electrode
1 3 4
10
12
5
160303-679
2 6 7 8
13
9
11
14
18
19
15
20 21 252322 24
27
26
160303-680
17
16
28 29
160303-682
9 Bentone
172 515 05  2018-01-02
2.7 Skeleton diagrams
1. Ball valve
2. Filter
3. Pressure regulator
4. Pressure gauge with shut-off cock
5a. Gas pressure switch, min
5b. Gas pressure switch, max
6a. Main valve, 2 -stage. In modulaing operation, this valve is equipped
with controls for variable opening.
6b. Safety valve
7. 1) Leakage control
9. Air pressure switch
10. Burner control
Pos. 5b, 7: Components not required according to EN 676.
1) Required over 1200 kW according to EN 676.
10 Bentone
E106174
3. Electric equipment
3.1 Safety system
The safety system (safety switch for hatches, doors, water level, pressure,
temperature and other safety devices) must be installed in the safety circuit in
accordance with current regulations for the system.
The cables of the safety system must be separated so that the outgoing signal
is not placed in the same cable as the incoming signal.
3.2 Wiring diagram
172 615 33-2
Bn Brown
Bu Blue
Gn Green
Ye Yellow
Gn/Ye Green/Yellow
Bk Black
Gy Grey
Rd Red
Wh White
Og Orange
Vt Violet
11 Bentone
3.2.1 Components
A1 Burner control
A6 Power control R316
A6 (2) PT 100-sensor, Thermocouple,
current/voltage
B1 Ionization electrode
F1 Operating fuse
F4 Operating fuse 1A
H1 Operating lamp
H3 Alarm signal 230V
K1 Contactor
M1 Motor
M2 Damper motor
P1 Time counter,
total operating time
S1 Operating switch
S3 Control thermostat
S4 Temperature limiter
S5 Safety switch for hinged door
S7 Main switch
S8 Air pressure switch
S9 Gas pressure switch, min
S11 Change-over switch, Man-Auto
S12 Change-over switch, Increase-
Decrease
T1 Ignition transformer
X1 Connection terminal board
X2 Earth terminal
X3 Plug-in contact, burner
X4 Plug-in contact, boiler
X9 Plug-in contact, power
controller R316, burner
X10 Plug-in contact, power
controller R316
Y1 Solenoid valve 1
Y3 Safety solenoid valve
!Mains connection and
fuse in accordance with
local regulations.
3.2.2 Technical data
LME22.232C2E
3 s
20 s
2.5 s
< 3 s
< 1 s
< 1 s
5 µA
20 µA
160303-325
Preiginition time
Prepurge time
Postignition time
Safety lockout time
Reset time after lockout
Reaction time on  ame failure
Min. ionisation current at  ame
Max. ionisation current
3.3 Function
1. Operating switch ON-Thermostat ON-Gas pressure switch ON-Air
damper closed.
Check that the air pressure switch does not indicate fan pressure,
then the motor starts.
2. Damper motor opens.
The damper motor opens the damper to the maximum load position.
Check that the air pressure switch indicates sucient fan pressure.
3. Damper motor closes.
The damper motor closes to the minimum load position, then the
ignition spark is produced.
4. Main and safety valves open.
The gas ignites and the ionisation electrode indicates ame.
5. The safety time ends.
Ignition spark and safety time cease. If the spark is missing or it
disappears after this time limit, the gas burner control is blocked.
6. Operating position.
The burner is in operating mode and can now switch to the capacity
controlled by the controller.
7. Stop.
The burner operation can be stopped with the operating switch or the
thermostat.
If the gas burner control is blocked
The red light in the gas burner control comes on. The burner is restarted by
pressing the reset button.
12 Bentone
Light period
(waiting period ≥ 10 s)
Blinking
code Pause Blinking code
Press the reset
button > 3 s
3.4 Control program at faults; fault mode
indicator LME ....
3.4.1 Colour codes
3.4.2 Diagnosting alarm causes
After alarm disconnection, the red alarm signal light is lit continuously.
The diagnosing of the alarm cause can be read according to the following
sequence:
3.4.3 Limiting of starting repetitions
LME 11... has a function with start repetition if the ame is not created at start
or disappears during operation.. LME 11... allows max. three repetitions during
continuous starting cycle.
Table colour codes for multi-coloured signal light (LED)
Status Colour codes Colours
Waiting period «tw», other waiting periods ○………………… O
Ignition phase, ignition controlled ●○●○●○●○●○● Blinking yellow
Normal operation □………………… Green
Operation, poor ame signal □○□○□○□○□○ Blinking green
Illegal ame signal during start-up □▲□▲□▲□▲□▲ Green-Red
Undervoltage ●▲●▲●▲●▲●▲ Yellow-Red
Fault, alarm ▲………………… Red
Blinking code for fault codes ▲○ ▲○ ▲○ ▲○ Blinking red
Interface diagnostics ▲▲▲▲▲▲▲▲ Red icking
…… Continuous
Off
Red
Yellow
Green
13 Bentone
During the diagnosing of the alarm cause, the control outputs are voltage-
free.
The burner is disconnected.
Exception, alarm signal «AL» at board 10.
Reconnection of the burner happens after resetting only.
Press the reset button 0.5...3 s.
3.4.4 Interface diagnostics
To change to interface mode, press and hold the reset button longer than 3 s.
To go back to the normal position, press and hold the reset button longer than
3 s. If the gas burner control is in the alarm position, it is reset by pressing the
reset button 0.5...3 s.
3.4.5 Alarm code table
Red blinking code on
signal lamp (LED)
Possible causes
Blinking 2 x
••
No ame creation at End of “TSA
defective or fouled ame monitoring.
defective or fouled fuel valves.
poor burner setting.
defective ring device.
Blinking 3 x
•••
“LP” defective
No air pressure switch signal after “t10”.
“LP” is welded in open position.
Blinking 4 x
••••
Illegal ame signal during start-up.
Blinking 5 x
•••••
Time out “LP”
“LP” is welded in open position.
Blinking 6 x
••••••
Free
Blinking 7 x
•••••••
Too many ame disappearances during operation.
poor burner setting.
defective or fouled fuel valves.
defective or fouled ame monitoring.
Blinking 8 x
••••••••
Free
Blinking 9 x
•••••••••
Free
Blinking 10 x
••••••••••
Connection fault or internal fault, outgoing contacts or
other faults.
Blinking 14 x
••••••••••••••
CPI contact not closed.
14 Bentone
170 095 02-5  2023-04-12
8. Controller JUMO dTRON 316
8.1 Preface
These brief operating instructions only cover those actions that are essential for
starting up the controller.
The complete conguration options can be found in the comprehensive
Operating Manual or can be downloaded from: http://www.jumo.net.
Type dTRON Panel cut-out
703041 316, in 48 mm x 48 mm format 45 +0,6mm x 45 +0,6mm
8.2 Scope of delivery
Controller
Seal
Mounting brackets
8.3 Mounting
8.3.1 Fitting in position
Fit the seal that is supplied onto the instrument body.
Insert the controller from the front into the panel cut-out.
From the back of the panel, push the mounting frame onto the
instrument body and press it against the back of the panel,
compressing the springs, until the latches snap into the notches
provided and it is rmly xed in position.
15 Bentone
8.4 Electrical connection
8.4.1 Connection diagram
5
6
7
8
6
7
8
1
1
2
3
4
1
2
2
3
4
8
3
4
6
7
3
5
L1(L+)
N(L-)
16 Bentone
8.5 Displays and keys
1 7-segment display (factory setting: process value)
four-digit, red, decimal place is congurable (automatic adjustment on
display overow)
2 Active setpoint (factory setting: SP1)
SP1, SP2, SP3, SP4 (SP=setpoint); green;
3 7-segment display (factory setting: setpoint)
four-digit, green, decimal place is congurable; also used for operator
prompting (display of parameter and level symbols)
4 Keys
5 Indication
yellow, for
- switch status of binary outputs 1—6 (display lights up = on)
- ramp/program function is active
- manual operation is active
6 16-segment display + dim. units
two-digit, green; for the unit °C/°F and symbols for h, min, %.
Dierent values can also be visualized on the display, see the comprehensive operating manual.
PGM EXIT
(1)
(3)
(2) (6)
(4)
(5)
1
2
3
4
6
5
17 Bentone
The diagram below shows the three instrument levels.
H
8.6 Operation
8.6.1 Levels
The diagram below shows the three instrument levels.
Time-Out
If no key is pressed for 30 sec, the
instrument returns to normal display.
h Press P and D simultaneously for >5 sec to enter the code.
hAlter code with P (display blinks)
hEnter code with I and D
hReturn to normal display with X or automatically after approx. 30 sec
6.3 Entering values
When entries are made within the levels, the parameter symbol is shown in the
lower display.
hSelect parameter with I or D
hChange to the entry mode with P (lower display blinks)
hAlter value with I and D
The value alters dynamically with the duration of the key stroke.
hAccept the setting with P or automatically after 2 sec
hor
hCancel entry with X.
The value is not accepted.
Code Operator level Parameter level Configuration level
0 enabled enabled enabled
1 enabled enabled inhibited
2 enabled inhibited inhibited
3 inhibited inhibited inhibited
ID/P
IIIIIIIIIIII
I
I
I
III
I
I
I
I I I I I I I I I I I I I
I
I
I
III
I
I
I
I
D
Select parameter Alter parameter
8.6.2 Level inhibit
The access to the individual levels can be inhibited by entering a code number.
18 Bentone
8.6.3 Entering times
When entering times (e.g. time of timer), the time unit is shown in addition.
The highest time unit of the
display is shown for the unit.
For example, if “h” is show
n for the hour, then the time format for the value is
hh:mm.
h
Select parameter with I or D
h
Change to the entry mode with P (lower display blinks)
h
Alter value with I and D
The value alters dynamically with the duration of the key stroke.
h
Accept the setting with P or automatically after 2 sec
or
h
Cancel entry with X.
The value is not accepted.
ID/
PI
D
IIIIIIIIIIII
I
I
I
III
I
I
I
I I I I I I I I I I I I I
I
I
I
III
I
I
I
Select
parameter Alter
parameter
8.6.4 Operation of the xed-setpoint controller
- the fixed-setpoint controller function has been configured ( Fnct = 0)
hAlter the present setpoint
with I and D
The value is accepted
automatically.
The controller output appears in the
lower display. The hand symbol and the
unit “%” light up in addition.
hAlter the output with I and D
In the case of a modulating controller,
the actuator is opened or closed using
the keys.
The output entry on a changeover is
configurable.
hReturn to the normal display with X
(press for more than 2 seconds)
Normal display Manual mode
19 Bentone
8.6.5 Operation of the program controller
The program is canceled in the event of a power failure.
HThe program controller will only function if
- the program controller function has been configured ( Fnct = 1 ...4)
- the program setpoints (SPP1 ... SPP8) and
segment times (tP 1 ... tP 8) have been entered
Normal display Program is running
(the symbol for ramp appears)
Program pause
hAlter the present
setpoint with I and D
The controller controls to
the present setpoint.
(The value is accepted
automatically after 2 sec.)
When the program is
paused, the lower display
blinks.
Alter setpoint
20 Bentone
8.6.6 Operator level „OPr“
8.7 Parameter level „PArA“
Two parameter sets, PAr1 und PAr2, can be stored.
Process data ProC
User data USEr (through the setup program only)
Any parameter (up to eight) can be displayed and edited here by using the setup
program.
Program data Pro (only with program controller/generator)
A program with up to eight segments is defined here, via the segment setpoints
SPP1 ... SPP8 and segment times tP 1 ... tP 8.
Symbol Meaning
SP 1 Setpoint 1 (editable)
SP 2 Setpoint 2 (editable)
SP 3 Setpoint 3 (editable)
SP 4 Setpoint 4 (editable)
SPr Ramp setpoint (only if configured)
InP1 Measurement of analog input 1
InP2 Measurement of analog input 2 (only if available)
F1 Calculated result of math formula 1 (only if available)
F2 Calculated result of math formula 2 (only if available)
yOutput
trun Program run time (only with program controller/generator)
trES Residual program time (only with program controller/generator)
t1 Timer: time 1 (only if configured)
t2 Timer: time 2 (only if configured)
Two parameter sets, PAr1 und PAr2, can be stored.
Parameter Symbol Value range Factory setting
Proportional band 1a
a. with Pb1/2=0, the controller structure is not effective; depending on the display configuration,
these values are shown with the corresponding decimal places
Pb 1 0 ... 9999 °C/°F 0 °C/°F
Proportional band 2b
b. for controller output 2 (with 3-state controllers)
Pb 2 0 ... 9999 °C/°F 0 °C/°F
Derivative timec
c. with dt=0, the controller has no differential action (e. g. PI controller)
dt 0 ... 9999 s 80 s
Reset timed
d. with rt=0, the controller has no integral action (e. g. PD controller)
rt 0 ... 9999 s 350 s
Actuator time tt tt 5 ... 3000 s 60 s
Cycle time 1 CY 1 0.0 ... 999.9 s 20 s
Cycle time 2 CY 2 0.0 ... 999.9 s 20 s
Contact spacing db 0.0 ... 999.9 °C/°F 0 °C/°F
Switching differential 1e
e. for controllers with Pb1/2=0
HYS1 0.0 ... 999.9 °C/°F 1 °C/°F
Switching differential 2 HYS2 0.0 ... 999.9 °C/°F 1 °C/°F
Working point y0 -100 ... +100 % 0 %
Output limiting (max.) y1 0 ... 100 % 100 %
Output limiting (min.) y2 -100 ... +100 % -100 %
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55