INSTALLATION INSTRUCTIONS
for INFRA-RED WARMERS IFW-66 Series
Model: 7066-007
ELECTRICAL SPECIFICATIONS:
• 120 Volts; 250 Watts; 2 Amps.
• 240 Volts; 275 Watts; 1 Amp.
UL AND CSA REQUIRE:
• Wires of warmer are to be connected to
75°C wire.
• Wires to be installed with conduit
• Warmers are not to be installed closer
than 1” from a wall.
• Warmers cannot be closer than 16”
above a combustible surface
HOW TO INSTALL: (See Figure)
NOTE: Outlet box (7) and screws (5) are to be
furnished by customer.
1. Remove the two screws from the crown
plate (5) and pull off the canopy (4).
2. Run cord (3) up through threaded
nipple.
3. Cut cord to desired length.
4. Mount the strap (2) to the electrical
outlet box with two screws.
5. Attach ground wire from the ceiling to
the “GND” hold in the strap (2) with
green screw (6).
6. Wire the warmer leads to the outlet box
leads.
7. Screw canopy (4) to the crown plate (5)
with two sheet metal screws.
8. Screw the lamp into the socket.
Part Identification: (See figure)
1. Assembly socket
2. Strap-Ceiling
3. Cord
4. Canopy Kit
5. Crown Plate
6. Ground “GND” Screw
REPLACEMENT PARTS:
Lamp, Red (120V) 0820-001
Lamp, White (120V) 0820-033
Lamp, Red (240V) 0820-014
Socket 0822-030
Switch 0808-002
Cord 0810-042
Canopy Kit 7071